Global Fire ORION-EX V2 Installation Operation & Maintenance Download Page 5

 

 

Global Fire Equipment // 

globalfire.pt 

ma_oexv2_01_010001_en_180730

 

 

 

FAULTS

 

 

SUPPLY FAULT

 – This LED will be ON whenever the Main Supply has been removed or has dropped below 20 Volts. 

 

BATTERY FAULT

 – Indicates that there is low voltage level on the batteries or the battery charger circuit has failed. 

 

SOUNDER FAULT

If there is a conventional sounder circuit fault, the general fault LED will be lit and Sounders LED in the

 

   

 

     

 

 

 

 

 

 

 

 

     

 

 

   

 

Faults section will be flashing.

 

 

EARTH FAULT

– When this indicator is ON, there is leakage current flowing between the Earth connection/wiring and any

 

   

 

 

   

 

   

 

 

 

 

 

 

 

 

 

other wire connected to the panel. 
 

 
ZONES & INPUTS 

 
Individual zone and monitored input indicators are provided for both FIRE/ALARM, EXTINGUISH and FAULT conditions. If

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   

any of these inputs is disabled, then its Fault LED will also be used to indicate the disablement of that particular zone/ input.

   

 

   

 

   

 

 

 

   

   

 

 

   

 

 

 

 

The zone/ input Disabled LED will be ON along with the associated disabled status LED. Flashing Fault LED along with

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

general Fault LED indicates fault on that zone. 
 
Zone 3 LEDs provides status indication for both Z3F (for fire detection) and Z3X (for extinguishing and fire detection). Both

   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Z3F and Z3X share the same status indicators in conjunction.   
 

 
CONTROL KEYS 

 
These four keys can have more than one function. They are numbered to indicate that they are used to enter digits from 1 to

 

 

 

 

 

 

 

 

 

 

 

   

 

 

 

 

   

 

 

     

4 for code entry. 
 

BUZZER SILENCE (1)

– At Access Level 1 this button is used to silence the panel's internal buzzer. At Access Level 2 and

 

 

 

   

 

   

 

   

   

 

 

 

 

   

 

   

 

3 used to confirm/accept changes in programming. Buzzer must be always silenced before entering the access code to other

 

   

 

   

 

 

   

 

 

 

 

 

 

   

 

levels. 
 

RESET (2) 

– Press this button to reset the panel at Access Level 2 or 3. 

 

LAMP TEST (3)

– Press this button at Access Level 1 or 2 to test all LED indicators and the panel's internal buzzer. Release

 

 

   

 

 

   

 

         

   

 

 

 

 

 

 

 

 

when test is finished. At Access Level 3, press this button to enter in “one man” test mode. 
 

SOUNDERS (4)

– Press once to activate/silence sounders in Level 2. If sounders are active, for example, during a FIRE

 

 

 

 

   

 

   

     

 

 

 

 

 

   

 

condition or in the event of an Evacuation action, pressing this button will stop the sounders. Auxiliary Relays are not

 

   

 

   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

affected by this action. When selected the disablements in Level 2, this button is used to select the desired disablement. I

n

 

 

 

 

 

 

 

   

   

 

   

   

 

 

 

 

 

Access Level 3, combined with the delay activation button, it is used to select the desired delay. 

 

 
 

 

 

Summary of Contents for ORION-EX V2

Page 1: ...ices smoke and or heat detectors and call points per zone Active End of Line for Zone wiring monitoring 10uF 50V bipolar capacitor Programmable Pre Release and Extinguishing times Monitored inputs for...

Page 2: ...EL Before connecting zones or sounder cables power up the control panel with the Active EOL connected to the zone inputs and the EOL resistors for the sounder output lines connected Then connect mains...

Page 3: ...ote Input Manual Start extinguishing cycle CAP F ABORT Remote Input Manual Abort extinguishing cycle CAP G S1 Output Circuit S1 Active with Fire 10K RES H S2 EXT Output Circuit S2 Active during exting...

Page 4: ...s LED used to indicate that the panel has features that have been disabled TEST This LED is active whenever panel is in TEST MODE activated in Engineering Mode Access Level 3 only SUPPLY Multi functio...

Page 5: ...Z3F for fire detection and Z3X for extinguishing and fire detection Both Z3F and Z3X share the same status indicators in conjunction CONTROL KEYS These four keys can have more than one function They...

Page 6: ...ones Z1 Z2 and Z3 F X 1 When switch is pressed associated LED will also be lit 2 Select the required ZONE by pressing consecutively the RED BUTTON 4 until the FAULT LED for the required ZONE is lit 3...

Page 7: ...ilence Buzzer Silence Buzzer Confirm Disablement Disablements Confirm Delay Selection see delay config table RESET 2 insert user code Reset Panel Reset Panel LAMP TEST 3 insert user code Lamp Test Lam...

Page 8: ...detector zone should be terminated in the relevant terminal blocks at the control panel and the cable screens connected to earth NOTE Zone 3F is independent from extinguishing cycle Upon activation b...

Page 9: ...Global Fire Equipment globalfire pt ma_oexv2_01_010001_en_180730 POLARIZED DEVICES NON POLARIZED DEVICES RELAYS SOLENOIDS OR BELLS PYROTECHNIC ACTUATORS 9...

Page 10: ...ne monitoring is achieved with a 4K7 resistor that mimics relay coil resistance therefore resistance should be removed after connecting relay NOTE Relay must have a 24V DC coil rating AUXILIARY INPUTS...

Page 11: ...m This input has no effect on the panel outputs INS Extinguishing Immediate Activation This input starts the configured automatic extinguishing cycle ABORT Immediate Stopping of Extinguishing Cycle Th...

Page 12: ...red these must be acknowledged by pressing the Buzzer Silence button to acknowledge each Fault or Fire event before code entry will be accepted LEVEL 3 Engineering Functions 4321 It is accessed from L...

Page 13: ...ct batteries Observe correct polarity COMMISSIONING 1 If all is normal only the Green supply LED should be illuminated 2 If any Faults are indicated they should be corrected before proceeding 3 Initia...

Page 14: ...ond to required day it s lit up Please refer to below table for additional details 3 Confirm the selection by pressing GREEN 1 key Upon confirmation the Red FIRE LED will be activated Remove selection...

Page 15: ...PHICAL OVERVIEW Z1 Z2 ZONES Z1 ON OFF Z2 ON OFF OUTPUTS S1 ON OFF S2 ON OFF RM ON OFF DELAYS TIMERS PRE RELEASE ON OFF RELEASE ON OFF Z3X ZONES Z3F Z3X ON OFF OUTPUTS S1 ON OFF S2 ON OFF RM ON OFF DEL...

Page 16: ...s timer elapses both S2 and RM outputs will be deactivated if programmed to do so Sounder Circuit 1 is silenced using Sound Resound Alarms button upon entering access level 2 After Sounder Circuit 1 i...

Page 17: ...This type of fault will indicate that there is either a short or open circuit condition on zone circuit Revise wiring Supply Fault Associated with a low voltage below 20 V present at the input of the...

Page 18: ...oard and interface are connected using the 5 way flat cable provided The cable is fitted with 2 polarized connectors of the Molex type For details about connection please refer to repeater installatio...

Page 19: ...side of ORION EX V2 main board to MPX 5 way connection on GFE MPX SNDR V2 or GFE MPX REL V2 board ORION EX V2 GFE MPX SNDR V2 or GFE MPX REL V2 Connection to ORION EX Mini Repeater V2 or ADLI V2 Modul...

Page 20: ...ING Active EOL 10uF 50V Bipolar Capacitor BS5839 DETECTOR REMOVAL COMPLIANT YES provided diodes are fitted to detector base DEVICES PER ZONE 32 maximum EN54 pt 2 ALARM RESISTANCE VALUE INPUTS 270 1000...

Page 21: ..._01_010001_en_180730 GLOBAL FIRE EQUIPMENT S A S tio dos Barrab s Armaz m Nave Y Caixa Postal 908 Z 8150 016 S o Br s de Alportel PORTUGAL Tel 351 289 896 560 Sales sales globalfire pt Technical Suppo...

Reviews: