FAULTS
SUPPLY FAULT
– This LED will be ON whenever the Main Supply has been removed or has dropped below 20 Volts.
BATTERY FAULT
– Indicates that there is low voltage level on the batteries or the battery charger circuit has failed.
SOUNDER FAULT
–
If there is a conventional sounder circuit fault, the general fault LED will be lit and Sounders LED in the
Faults section will be flashing.
EARTH FAULT
– When this indicator is ON, there is leakage current flowing between the Earth connection/wiring and any
other wire connected to the panel.
ZONES & INPUTS
Individual zone and monitored input indicators are provided for both FIRE/ALARM, EXTINGUISH and FAULT conditions. If
any of these inputs is disabled, then its Fault LED will also be used to indicate the disablement of that particular zone/ input.
The zone/ input Disabled LED will be ON along with the associated disabled status LED. Flashing Fault LED along with
general Fault LED indicates fault on that zone.
Zone 3 LEDs provides status indication for both Z3F (for fire detection) and Z3X (for extinguishing and fire detection). Both
Z3F and Z3X share the same status indicators in conjunction.
CONTROL KEYS
These four keys can have more than one function. They are numbered to indicate that they are used to enter digits from 1 to
4 for code entry.
BUZZER SILENCE (1)
– At Access Level 1 this button is used to silence the panel's internal buzzer. At Access Level 2 and
3 used to confirm/accept changes in programming. Buzzer must be always silenced before entering the access code to other
levels.
RESET (2)
– Press this button to reset the panel at Access Level 2 or 3.
LAMP TEST (3)
– Press this button at Access Level 1 or 2 to test all LED indicators and the panel's internal buzzer. Release
when test is finished. At Access Level 3, press this button to enter in “one man” test mode.
SOUNDERS (4)
– Press once to activate/silence sounders in Level 2. If sounders are active, for example, during a FIRE
condition or in the event of an Evacuation action, pressing this button will stop the sounders. Auxiliary Relays are not
affected by this action. When selected the disablements in Level 2, this button is used to select the desired disablement. I
n
Access Level 3, combined with the delay activation button, it is used to select the desired delay.
5