OPERATING AND PROGRAMMING THE PANEL 

 
There are three access levels on the ORION-EX: 
 

LEVEL 1 – General User Controls 

● Perform LEDs and Buzzer test 
● Silence Internal buzzer 
● Put the panel into Access Level 2 or 3 using required access codes. 

 
LEVEL 2 – Authorized user controls (2244) or Access Key 

This level allows the user to: 
● Silence and re/activate S1 sounder output 
● Reset after an Alarm or Fault 
● Manually activate the sounders (Evacuate function) 
● Silence Internal Buzzer 
● Disable/Enable: Outputs; Zones & Monitored Inputs; Activate & Abort Extinguishing Cycle. 
 

NOTE: 

When any zone or function is disabled, the Disabled LED on the STATUS area of the Control 

Panel display will be lit together with the corresponding function or zone disablement LED. Disabled 
zones will have their corresponding FAULT/DISABLED LED illuminated. 

 
Level 2 Access is gained by entering the code 

2244

 using the numbered buttons. When in panel is in Level 2 the Green LED 

will flash with a frequency of 1 Hz. 
 
Each successful button press is indicated by the illumination in sequence of the top screen Fault LEDs. If the code is not 
completed within 20 seconds of the last key press, the system reverts to Level 1. 
 

NOTE:

 If any Fire or Fault events have occurred these must be acknowledged 

by pressing the Buzzer 

Silence

 button to acknowledge each Fault or Fire event

 before code entry will be accepted. 

 
LEVEL 3 – Engineering Functions (4321) 

It is accessed from Level 1 and allows: 
● One Man Test 
● Panel Reset 
● Set Extinguishing Pre-Release Delay and Extinguishing Timer. 
 

NOTES: 
1)

Changes made at this level affect the factory default settings and the operation of the system. They

 

   

 

 

 

 

 

 

 

 

 

   

 

 

 

should only be made by qualified personnel who are fully aware of their effects. 

2)

If any Fire or Fault events have occurred, these must be acknowledged by pressing the Buzzer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Silence button to acknowledge each fault and Fire event before code entry will be accepted. 

3)

When in Access Level 3, the occurrence of any Fire or Fault condition the system will automatically

   

 

   

 

   

 

   

 

 

 

 

 

 

exit from Level 3 and revert to Level 2. 

 
To enter Engineering Mode (Access Level 3) enter the code 4321, using the numbered keys (from 1 to 4), which are

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

     

 

 

 

available on the top right-hand side of the control panel display. Each successful button press is indicated by the illumination

 

 

 

 

 

   

 

 

 

 

 

 

 

   

   

 

 

in sequence of the Fault LEDs for zones 3, 4, 5 and 6. If the code is not completed within 20 seconds of the last key press,

 

   

 

 

 

 

       

     

 

   

 

 

   

   

 

 

 

 

the system reverts to Level 1. 
 
Once this mode is entered the Green LED (SUPPLY) will flash once every 0,5 seconds. 
To exit this mode at any time, press the RESET button. The panel will revert to Access Level 1. 

Total removal of power during the programming phase could cause changes not to be saved.

 

 

 

12 

Summary of Contents for ORION-EX V2

Page 1: ...ices smoke and or heat detectors and call points per zone Active End of Line for Zone wiring monitoring 10uF 50V bipolar capacitor Programmable Pre Release and Extinguishing times Monitored inputs for...

Page 2: ...EL Before connecting zones or sounder cables power up the control panel with the Active EOL connected to the zone inputs and the EOL resistors for the sounder output lines connected Then connect mains...

Page 3: ...ote Input Manual Start extinguishing cycle CAP F ABORT Remote Input Manual Abort extinguishing cycle CAP G S1 Output Circuit S1 Active with Fire 10K RES H S2 EXT Output Circuit S2 Active during exting...

Page 4: ...s LED used to indicate that the panel has features that have been disabled TEST This LED is active whenever panel is in TEST MODE activated in Engineering Mode Access Level 3 only SUPPLY Multi functio...

Page 5: ...Z3F for fire detection and Z3X for extinguishing and fire detection Both Z3F and Z3X share the same status indicators in conjunction CONTROL KEYS These four keys can have more than one function They...

Page 6: ...ones Z1 Z2 and Z3 F X 1 When switch is pressed associated LED will also be lit 2 Select the required ZONE by pressing consecutively the RED BUTTON 4 until the FAULT LED for the required ZONE is lit 3...

Page 7: ...ilence Buzzer Silence Buzzer Confirm Disablement Disablements Confirm Delay Selection see delay config table RESET 2 insert user code Reset Panel Reset Panel LAMP TEST 3 insert user code Lamp Test Lam...

Page 8: ...detector zone should be terminated in the relevant terminal blocks at the control panel and the cable screens connected to earth NOTE Zone 3F is independent from extinguishing cycle Upon activation b...

Page 9: ...Global Fire Equipment globalfire pt ma_oexv2_01_010001_en_180730 POLARIZED DEVICES NON POLARIZED DEVICES RELAYS SOLENOIDS OR BELLS PYROTECHNIC ACTUATORS 9...

Page 10: ...ne monitoring is achieved with a 4K7 resistor that mimics relay coil resistance therefore resistance should be removed after connecting relay NOTE Relay must have a 24V DC coil rating AUXILIARY INPUTS...

Page 11: ...m This input has no effect on the panel outputs INS Extinguishing Immediate Activation This input starts the configured automatic extinguishing cycle ABORT Immediate Stopping of Extinguishing Cycle Th...

Page 12: ...red these must be acknowledged by pressing the Buzzer Silence button to acknowledge each Fault or Fire event before code entry will be accepted LEVEL 3 Engineering Functions 4321 It is accessed from L...

Page 13: ...ct batteries Observe correct polarity COMMISSIONING 1 If all is normal only the Green supply LED should be illuminated 2 If any Faults are indicated they should be corrected before proceeding 3 Initia...

Page 14: ...ond to required day it s lit up Please refer to below table for additional details 3 Confirm the selection by pressing GREEN 1 key Upon confirmation the Red FIRE LED will be activated Remove selection...

Page 15: ...PHICAL OVERVIEW Z1 Z2 ZONES Z1 ON OFF Z2 ON OFF OUTPUTS S1 ON OFF S2 ON OFF RM ON OFF DELAYS TIMERS PRE RELEASE ON OFF RELEASE ON OFF Z3X ZONES Z3F Z3X ON OFF OUTPUTS S1 ON OFF S2 ON OFF RM ON OFF DEL...

Page 16: ...s timer elapses both S2 and RM outputs will be deactivated if programmed to do so Sounder Circuit 1 is silenced using Sound Resound Alarms button upon entering access level 2 After Sounder Circuit 1 i...

Page 17: ...This type of fault will indicate that there is either a short or open circuit condition on zone circuit Revise wiring Supply Fault Associated with a low voltage below 20 V present at the input of the...

Page 18: ...oard and interface are connected using the 5 way flat cable provided The cable is fitted with 2 polarized connectors of the Molex type For details about connection please refer to repeater installatio...

Page 19: ...side of ORION EX V2 main board to MPX 5 way connection on GFE MPX SNDR V2 or GFE MPX REL V2 board ORION EX V2 GFE MPX SNDR V2 or GFE MPX REL V2 Connection to ORION EX Mini Repeater V2 or ADLI V2 Modul...

Page 20: ...ING Active EOL 10uF 50V Bipolar Capacitor BS5839 DETECTOR REMOVAL COMPLIANT YES provided diodes are fitted to detector base DEVICES PER ZONE 32 maximum EN54 pt 2 ALARM RESISTANCE VALUE INPUTS 270 1000...

Page 21: ..._01_010001_en_180730 GLOBAL FIRE EQUIPMENT S A S tio dos Barrab s Armaz m Nave Y Caixa Postal 908 Z 8150 016 S o Br s de Alportel PORTUGAL Tel 351 289 896 560 Sales sales globalfire pt Technical Suppo...

Reviews: