Operation
21
7.2.4
Changing the Setpoint:
To change the setpoint:
•
P
ress the “Prg” key and the main menu w
ill be displayed
•
Highlight the menu labeled “B. SETPOINT” and press the “Enter” key
. The page will look similar to
Error! R
eference source not found.
•
Pr
ess the “Enter” key again
and move the cursor over the fluid setpoint temperature
•
Use the
“
” and “
”
keys to change the temperature and press the “Enter” key to accept
•
Press the “Esc” key to return to the main menu
7.2.5
Viewing Alarms
When an alarm occurs, the red alarm light on the PGD display will light up (a buzzer will activate if not disabled).
To view this alarm, press the “Alarm” key and the alarms will be displayed. To view all active alarms, use the
arrow keys to scroll up and down. To cl
ear all inactive alarms, press and hold the “Alarm” key. At the end of the
alarms a page similar to
Error! Reference source not found.
will be displaye
d. Press the “Enter” key and you will b
e taken to the Alarm Log page where you can view the alarm history.
7.2.6
Sequence of Operation:
Upon system start, with all compressors and pumps enabled, a brief delay will occur and then the pump that
didn’t run during
the last operation cycle will start first. If flow is established, the pump will continue to run. If
no flow is established for the defined flow fault delay time, the opposing pump will automatically start. Pumps
will rotate once every 24 hours to balance run time. Once flow is established and cooling demand increases to
25%, the compressor with the least run time will start. As cooling demand increases to 50%, the compressor in
the alternate set with the least run time will start. At a cooling demand of 75% and 100% the remaining
compressors will stage up. When cooling demand decreases by 25% from a compressor start percentage, a
compressor will cycle off. C
ompressors drop out in a ‘first in
-
first out’ sequence. The cooling demand signal is
proportional and integral driven so the cycling of compressors should slowly correct to be centered about the
set point.
Summary of Contents for Koolant Koolers WO2-2-10000
Page 1: ...Original Instructions 800 968 5665 dimplexthermal com User Manual...
Page 17: ...Installation 11 Figure 7 Removal or Doors Blockers 3 8 DOOR BOLT 3 8 BLOCKER BOLT BLOCKER DOOR...
Page 18: ...Installation 12 Figure 8 Removal of Lower Doors LATCHES...
Page 28: ...Operation 22 Figure 10 Controller Restart Warning Figure 11 Controller Home Page...
Page 30: ...Operation 24 Figure 15 Controller On Off Menu Figure 16 Controller Pump Enable Disable Menu...
Page 31: ...Operation 25 Figure 17 Controller Setpoint Menu Figure 18 Controller Alarm Menu...
Page 37: ...Internal Components 31 Figure 20 Door Side PUMP 2 PUMP 1 FLOAT SWITCH...
Page 44: ...Appendix A Plumbing 38 Appendix A Plumbing...
Page 45: ...Appendix B Pump Curve 39 Appendix B Pump Curve...
Page 46: ...Appendix C Refrigeration WO2 2 5000 40 Appendix C Refrigeration WO2 2 5000...
Page 47: ...Appendix C Refrigeration WO2 2 7500 41 WO2 2 7500...
Page 48: ...Appendix C Refrigeration WO2 2 10000 42 WO2 2 10000...