5.4.5. Weather alarm
The unit constantly evaluates the measurement signal to determine the weather intensity at a scale from 0 to 10 to allow alarm
actions based on weather intensity.
1.
In the Alarm settings tab, open the Weather alarm sub tab.
2.
Press "+ Add weather alarm". Input fields appear on the right.
3.
Enter desired threshold level on weather intensity alarm (default is 1).
4.
Enter timeout, the shortest time the weather alarm is active. Each time the weather intensity exceeds the threshold, the
timeout is reset. Default time is 10 minutes.
5.
Press the Add button to confirm the settings.
6.
Create Alarm actions for the weather alarm by pressing "+ Add action". Input fields appear on the right.
7.
Choose action event type.
Connect to URL
If the weather intensity threshold is exceeded, the unit alarms to the URL.
- Enter desired URL, for example the VMS server.
- Depending on VMS, alarm disable URL can be needed.
Relay action
Activates the internal relay.
Disable reference point
If the weather intensity threshold is exceeded, reference point alarms are ignored.
8.
Press the Add action button to confirm settings.
5.5. Logout
1.
Press the "Logout" tab in the top menu.
2.
You will automatically be logged out if anybody logs in from another computer.