System 3000 

RF operating top unit

7.2.1 Safe-state mode and master reset

Safe-state mode

The safe state mode stops the execution of the loaded application program.

If the device does not work properly - for instance as a result of errors in the project design or
during commissioning - the execution of the loaded application program can be halted by activ-
ating the safe-state mode. The device remains passive in safe-state mode, since the application
program is not being executed (state of execution: terminated).

Only the system software of the device is still functional. ETS diagnosis functions and pro-
gramming of the device are possible.

Activating the safe-state mode

Switch off the voltage.

Wait about 15 s.

Press the top right and bottom right button.

With the buttons pressed, switch the voltage back on and keep the buttons pressed for
more than 10 seconds.
The safe-state mode is activated. The status LED flashes red slowly (approx. 1 Hz).

Only release the the top right and bottom right buttons when the LED flashes.

Deactivating safe-state mode

Switch off the voltage (wait approx. 15 s) or carry out ETS programming.

Master reset

The master reset restores the basic device setting (physical address 15.15.255, firmware re-
mains in place). The device must then be recommissioned with the ETS.

During secure operation: A master reset deactivates device security. The device can then
be recommissioned with the device certificate.

Devices can be reset to factory settings with the ETS Service App. This function uses the
firmware contained in the device that was active at the time of delivery (delivery state).
Restoring the factory settings causes the devices to lose their physical address and con-
figuration.

If the device - for instance as a result of errors in the project design or during commissioning -
does not work properly, the loaded application program can be deleted from the device by per-
forming a master reset. The master reset resets the device to delivery state. Afterwards, the
device can be put into operation again by programming the physical address and application
program.

Performing a master reset

Precondition: The safe-state mode is activated.

Press and hold down the top right and bottom right button for more than 5 seconds until
the status LED flashes.

Release the top right button and bottom right button.
The device performs a master reset. The status LED flashes quickly (approx. 4 Hz).

The device restarts and is in delivery state.

11 / 12

32403802

10867449

10.11.2021

Summary of Contents for 5104 005

Page 1: ...w manual fully Danger of electric shock Always disconnect before carrying out work on the device or load In so doing take all the circuit breakers into account which support dangerous voltages to the...

Page 2: ...Device components Front view 1 channel Figure 1 and 2 channel Figure 2 Figure 1 Device components 1 channel Figure 2 Device components 2 channel 1 Rockers 2 Status LED 3 Cover frame 4 System 3000 inse...

Page 3: ...trans mitter 1 byte 2 bytes 3 bytes and 6 bytes brightness values temperatures calling up and saving of light scenes Operation in cabled KNX systems via media coupler see chapter Accessories Operatio...

Page 4: ...ration concept single area operation dual area operation Rocker function Each rocker can perform an indi vidual function Button function Two buttons above one another per form the same function Each b...

Page 5: ...ased Move Venetian blind Long press on button Stop or adjust Venetian blind Short press on button Set value e g brightness or temperature setpoint Short press on button Open scene Short press on butto...

Page 6: ...ce combination is not functional The insert cover align ment identifies this case as a swapping of the covers for example after renovating a room The insert cover alignment reports an error via the st...

Page 7: ...ard configuration The device combination does not transmit RF telegrams The ETS can reset the device to the delivery state with the Unload device command Status LED in the delivery state The status LE...

Page 8: ...netian blind or room temperature controller insert or 3 wire extension are mounted and connected properly see instructions of the relevant inserts The mains voltage has been switched off Fit the cover...

Page 9: ...channel Figure 6 Activating programming mode 2 channel Precondition The device is connected and ready for operation Activate programming mode Press the top right button and bottom right button simulta...

Page 10: ...mming is successfully completed the status LED carries out its parameterised function For Dimming The load must be connected before ETS commissioning Without a con nected load the ETS aborts the progr...

Page 11: ...r reset restores the basic device setting physical address 15 15 255 firmware re mains in place The device must then be recommissioned with the ETS During secure operation A master reset deactivates d...

Page 12: ...ld typ 100 m Receiver category 2 Ambient conditions Ambient temperature 5 45 C Storage transport temperature 25 70 C Relative humidity max 93 no condensation Gira Giersiepen GmbH Co KG Elektro Install...

Reviews: