Gira 5023 00 Manual Download Page 4

Switching actuator / blind actuator 16 A Standard & Komfort

Normally open contact: switch on = close relay, switch off = open relay
Normally closed contact: switch on = open relay, switch off = close relay
The LEDs (4 + 8 + 11) always indicate the relay status.

The LEDs (4) optionally indicate the status of the outputs only temporarily (depending on
the parameters).

Operating modes

Bus operation: Operation via push-button sensors or other bus devices

Temporary manual control: manual control locally with keypad, automatic return to bus
control

Continuous manual mode: Exclusively manual operation on the device

No bus operation is possible in manual mode.

After a bus failure and restoration the device switches to bus operation.

The manual mode can be disabled in ongoing operation via a bus telegram.

Switching on the temporary manual control

Operation using the button field is programmed and not disabled.

Press button 

ǃ

 (6) briefly.

LED 

ǃ

 (7) flashes, LEDs A1... (4) of the first configured output or output pair flash.

Short-time manual operation is switched on.

After 5 s without a key-press, the actuator returns automatically to bus operation.

Switching off temporary manual operation

The device is in short-term manual mode.

No button-press for 5 s.
- or -

Press 

ǃ

 (6) button briefly as many time as necessary until the actuator leaves the

short-time manual mode.
Status LEDs A1... (4) no longer flash, but rather indicate the relay status.

Short-time manual operation is switched off.

Switching outputs: depending on the programming, the output relays switch to the position
that is active after the manual mode is switched off, e.g. to the forced position, logic func-
tion.

Blind/shutter outputs: depending on the programming, the hangings move to the position
that is active after the manual mode is switched off, e.g. to the forced position, safety or
sun protection position.

Switching on permanent manual control

Operation using the button field is programmed and not disabled.

Press the 

ǃ

 (6) button for at least 5 s.

LED 

ǃ

 (7) lights up, LEDs A1... (4) of the first configured output or output pair flash.

Continuous manual mode is switched on.

Switching off permanent manual control

The device is in continuous manual mode.

Press the 

ǃ

 (6) button for at least 5 s.

LED 

ǃ

 (7) is off.

Continuous manual mode is switched off. Bus operation is switched on.

4 / 9

82402612

23.09.2020

Summary of Contents for 5023 00

Page 1: ...utside the technical specifications Danger of electric shock Device is not suitable for disconnection from supply voltage Danger of electric shock on the SELV PELV installation Do not connect loads fo...

Page 2: ...out with the aid of the ETS version 5 7 3 and above Intended use Switching of electrical loads with potential free contacts Switching of electrically driven Venetian blinds roller shutters awnings and...

Page 3: ...us manual mode active Flashing temporary manual control active 8 LED ON relay outputs closed manual operation active 9 Button Short switch on adjust slats or stop Long Move hanging upwards 10 Button S...

Page 4: ...ey press the actuator returns automatically to bus operation Switching off temporary manual operation The device is in short term manual mode No button press for 5 s or Press 6 button briefly as many...

Page 5: ...gs The device is in continuous manual mode Press the ALL OFF button 7 Switching outputs All outputs switch off NO operating mode relay output opened NC op erating mode relay output closed Venetian bli...

Page 6: ...Mount device on DIN rail In secure operation The device certificate must be removed from the device and stored securely Connecting the device Figure 3 Device connection connection example Connect bus...

Page 7: ...program Only the system software of the device is still functional ETS diagnosis functions and pro gramming of the device are possible Manual operation is not possible Activating the safe state mode S...

Page 8: ...transport temperature 25 70 C KNX KNX medium TP256 Commissioning mode S mode Rated voltage KNX DC 21 32 V SELV Current consumption KNX Order no 5023 00 5028 00 5033 00 5038 00 5 18 mA Order no 5030 0...

Page 9: ...stranded without conductor sleeve 0 5 4 mm Finely stranded with conductor sleeve 0 5 2 5 mm Connection torque screw terminals max 0 8 Nm 7 Warranty The warranty is provided in accordance with statuto...

Reviews: