Three binary inputs for potential-free contacts, usable as extension inputs for local
operation
-
Supply via bus, no additional power supply necessary
Blind function
-
Blind position directly controllable
-
Slat position directly controllable
-
Feedback of movement status, blind position and slat position
-
Forced position through higher-level controller
-
Safety function: 3 independent wind alarms, rain alarm, frost alarm
-
Sun protection function
Actuator function
-
Switching operation or PWM operation
-
Actuators with characteristics opened or closed without power
-
Overload-protected, short circuit-protected
-
Protection against jamming valves
-
Forced position
-
Cyclical monitoring of the input signals configurable.
i
PWM operation: electrothermal actuators only have the positions Open and Closed. In
PWM operation, switch-on and switch-off during the drive's cycle time achieves an almost
constant behaviour.
4 Information for qualified electricians
4.1 Fitting and electrical connection
DANGER!
Electrical shock when live parts are touched.
Electrical shocks can be fatal.
Before working on the device, disconnect the power supply and cover up live
parts in the working environment.
Connecting and mounting the device
DANGER!
When connecting the bus/extensions and mains' voltage wires in a shared
appliance box, the KNX bus cable may come into contact with the mains
voltage.
The endangers the safety of the entire KNX installation. People at remote
devices may also receive an electric shock.
Do not place bus/extensions and mains voltage terminals in a shared
connection compartment. Use an appliance box with a fixed partition wall
(Figure 5) or separate boxes.
32572302
10499188 I00
20.05.2011
4/8
KNX/EIB