Gira 2164 00 Operating Instructions Manual Download Page 1

Window actuator flush-mounted 

Order-No. : 2164 00 

Blind actuator 1-gang flush-mounted 

Order-No. : 2165 00 

Heating actuator 1-gang flush-mounted 

Order-No. : 2166 00 

Operating instructions 

1 Safety instructions 

Electrical equipment may only be installed and fitted by electrically skilled persons. 

Failure to observe the instructions may cause damage to the device and result in fire and 
other hazards. 

The device is not suitable for disconnection from supply voltage. 

The connected actuators are not electrically isolated from the mains – even when 
switched off. 

Do not connect any external voltage to the inputs, since doing so may damage the 
device(s), and the SELV potential on the KNX bus line will no longer be available. 

For parallel connection of several drives to an output it is essential to observe the 
corresponding instructions of the manufacturers, and to use a cut-off relay if necessary. 
There is otherwise risk of irreparable damage to the drives. 

Use only shutter drives with mechanical or electronic limit switches. Check the limit 
switches for correct adjustment. Observe the specifications of the motor manufacturers. 

These instructions are an integral part of the product, and must remain with the end 
customer. 

2 Device components 

Figure 1: Window actuator 

1/8 

32572302 

20.05.2011 

10499188 I00 

KNX/EIB 

Summary of Contents for 2164 00

Page 1: ...off Do not connect any external voltage to the inputs since doing so may damage the device s and the SELV potential on the KNX bus line will no longer be available For parallel connection of several d...

Page 2: ...2 Programming button and LED 3 Connection of mains and power cables Connection assignment power cables BK black connection L BN brown connection of Venetian blind up PK pink connection of Venetian bl...

Page 3: ...s An updated version of the product database technical descriptions and conversion programs and other auxiliary programs are available on our Internet website Intended purpose Window actuator Figure 1...

Page 4: ...tors only have the positions Open and Closed In PWM operation switch on and switch off during the drive s cycle time achieves an almost constant behaviour 4 Information for qualified electricians 4 1...

Page 5: ...en the mains voltage and bus extension wires 4 mm Figure 6 o Connect the load Figure 7 Use the supplied sprung screwless terminals Flexible cable ends must be tin plated o Connect the device to KNX o...

Page 6: ...tion software o Switch on the bus voltage o Assign physical addresses and load application software into the device o Note the physical address on the device label 5 Appendix 5 1 Technical data Window...

Page 7: ...tions Ambient temperature 5 45 C Storage transport temperature 25 70 C Venetian blind output Contact type Switching current AC1 3 A Minimum switching current AC 100 mA Motors 230 V 600 VA Motors 110 V...

Page 8: ...KNX medium TP 1 Commissioning mode S mode Rated voltage KNX DC 21 32 V SELV Power consumption KNX max 240 mW Connection mode KNX Connection terminal on control cable 5 2 Warranty The warranty is prov...