Connecting the device without running time 

detection

• Connect the bus line to the bus terminal (Fig. 3).
• Connect the mains voltage supply (Fig. 3).

Observe the admissible load rating (Technical data).

3

• Connect the drives (Fig. 4).

4

Connecting the device with automatic running 

time detection

If programmed and connected accordingly, the shut-
ter actuator detects the running time of the individual 
blinds/shutters and stores them. The actuator mea-
sures the voltage against the connected N terminal at 
the drives and can thus recognize the limit positions.

In operation, the shutter actuator can adapt itself to 
changes in the running times of the blinds/shutters 
that are due, for instance, to ageing of the motors.

Information for qualified electricians

The running time detection function is activated in the 
software.

The blinds/shutters are not blocked.

• Connect the bus line to the bus terminal (Fig. 3).
• Connect the mains voltage supply (Fig. 3).

CAUTION

When the N conductor is connected and when 
the concerned output is energized without inter-
ruption for a prolonged time due to retriggering, 
the device may heat up excessively.
Risk of irreparable damage to the device.
Do not connect the N conductors.

L1

L3

L2

N

BUS

A1

A2

A3

A4

L

N

ALL OFF

M1

M2

1(L)

A1

1(N)

3(L)

A3

A2
A4

3(N)

2(L)
4(L)

2(N)
4(N)

230 V
12-48 V

i

The N conductor terminals are only used 

for running time detection purposes and 

are not at neutral potential.

L1

L3

L2

N

M1

M2

1(L)

A1

1(N)

3(L)

A3

A2

A4

3(N)

2(L)

4(L)

2(N)

4(N)

i

The automatic running time detection can-
not be used for 110 V AC drives, for DC 
drives, for drives with electronic limit 
switches and for drives connected to the 
outputs via isolating relays.

Only for 230 AC drives with mechanical 
limit switches.

i

Connect only one drive to an output.

Summary of Contents for 1039 00

Page 1: ...run time detection with 230 V AC drives Direct control of blind shutter position Direct control of slat position Scene function Checkback of run status blind shutter position and slat position for bus...

Page 2: ...Fig 2 5 indicate the out put states Off output is off On output is on up or down Flashing slowly output in manual control mode Flashing fast output disabled in permanent manual control mode Modes of o...

Page 3: ...y for at least 5 s LED is on LEDs A1 are flashing permanent manual mode is activated Deactivating the permanent manual control mode The device is in the permanent manual control mode Press the key for...

Page 4: ...5 s The selected output A1 A4 is enabled The LEDs of the selected output are flashing slow ly Activate the bus mode deactivate the permanent manual control mode Information for qualified electricians...

Page 5: ...ation for qualified electricians The running time detection function is activated in the software The blinds shutters are not blocked Connect the bus line to the bus terminal Fig 3 Connect the mains v...

Page 6: ...the label Fig 7 7 Sliding on the protective cap To protect the bus lines against dangerous voltages at the connecting terminal slide on the protective cap Lead out the bus line at the rear of the devi...

Page 7: ...orehand The running times must be stored in undisturbed conditions i e without any control operations being performed and in the ab sence of wind snow and obstacles The automatic running time detectio...

Page 8: ...ge temperature 25 C 70 C Mounting width 72 mm 4 modules Weight approx 300 g Help in case of trouble Manual control with keypad not possible Cause 1 Manual control mode not programmed Program the devic...

Page 9: ...nic limit switches are being used Deactivate the automatic running time de tection Correct the electrical connection and re move the N conductor Blind shutter does not move to limit position po sition...

Page 10: ...ee in accordance with the corresponding legal provisions Please return the unit postage paid to our central service department giving a brief description of the fault Gira Giersiepen GmbH Co KG Servic...

Reviews: