4-channel blind/shutter actuator 230 V~
Installation Instructions
4-channel blind/shutter actuator 230 V~
1/07
Page 5 of 10
Connecting the device without running time
detection
• Connect the bus line to the bus terminal (Fig. 3).
• Connect the mains voltage supply (Fig. 3).
Observe the admissible load rating (Technical data).
3
• Connect the drives (Fig. 4).
4
Connecting the device with automatic running
time detection
If programmed and connected accordingly, the shut-
ter actuator detects the running time of the individual
blinds/shutters and stores them. The actuator mea-
sures the voltage against the connected N terminal at
the drives and can thus recognize the limit positions.
In operation, the shutter actuator can adapt itself to
changes in the running times of the blinds/shutters
that are due, for instance, to ageing of the motors.
Information for qualified electricians
The running time detection function is activated in the
software.
The blinds/shutters are not blocked.
• Connect the bus line to the bus terminal (Fig. 3).
• Connect the mains voltage supply (Fig. 3).
CAUTION
When the N conductor is connected and when
the concerned output is energized without inter-
ruption for a prolonged time due to retriggering,
the device may heat up excessively.
Risk of irreparable damage to the device.
Do not connect the N conductors.
L1
L3
L2
N
BUS
A1
A2
A3
A4
L
N
ALL OFF
M1
M2
1(L)
A1
1(N)
3(L)
A3
A2
A4
3(N)
2(L)
4(L)
2(N)
4(N)
230 V
12-48 V
i
The N conductor terminals are only used
for running time detection purposes and
are not at neutral potential.
L1
L3
L2
N
M1
M2
1(L)
A1
1(N)
3(L)
A3
A2
A4
3(N)
2(L)
4(L)
2(N)
4(N)
i
The automatic running time detection can-
not be used for 110 V AC drives, for DC
drives, for drives with electronic limit
switches and for drives connected to the
outputs via isolating relays.
Only for 230 AC drives with mechanical
limit switches.
i
Connect only one drive to an output.