Modes 9/10
Modes
9/10
Addressable
Mode 9 and 10 Ductgards in this option are normally controlled, by a remote switch on the Motor Supply.
Note: To interface with Gilberts remote indicators it is easier to switch the negative rather than the positive.
Mode 9 and 10 Ductgards in this option are interfaced with our Gardex Controlleras described on Page 11. Motorised
dampers are fitted with the Belimo BLF-T range as standard. Other actuators are available upon request.
1
2
-
+
M
Control Option A
1
2
-
+
M
Control Option B
S1
S2
S3
S4
S5
S6
5°
80°
S1
S2
S3
S4
S5
S6
5°
80°
L N E
M
N L 1 2 3 4 5 6
+ + - - S S
1 2 3 4 5 6
2 Core Screened
Communication Cable
Belimo Damper Motor
DCM Damper Control Module
240V 50HZ
Fused Spur
(option 24V DC)
24 V WIRING DIAGRAM
Power Supply
24V AC +-20%
50/60 Hz
24V DC +-20%
Current Rating
380mA AC max
POWER CONSUMPTION
Opening
5 watts
Holding
2.5 watts
S1 - S2 made when damper
closes
S4 - S6 made when damper
open
240V WIRING DIAGRAM
Power Supply
240V AC +15% -10%
50/60 Hz
240V AC +10% 50Hz
Current Rating
200mA AC max
POWER CONSUMPTION
Opening
approx 6 watts
Holding
approx 3 watts
10