6-10KVA UPS battery pack user manual www.giga-net.co.uk
4
Fig. 5 (16pcs batteries connection)
2.2.2.
After
the battery installation and connection done, check if BAT+ to N & N to BAT- voltages
are correct with multimeter or other equipments. Install the cover if the voltages are correct.
NOTE
: Battery “+” “-” poles cannot be reversed, also cannot short the battery “+” “-” poles,
otherwise batteries would be damaged or other accidents would happen. Don’t touch the
battery “+” “-” poles at the same time. It’s better only single man make the operation.
3.
Battery pack accessories
A complete of 6-10KVA UPS battery pack includes below accessories.
No.
Name
Specification
PCS
1
Cable 1#
Black wire 1015 10AWG 250mm 250TC*2
12
2
Cable 2#
Red wire 1015 10AWG 730mm 250TC+PA75B2-H SB50
4
3
Cable 3#
Black wire 1015 10AWG 170mm 250TC+PA75B0-H SB50
4
4
Cable 4#
2wires white 1015 10AWG 200mm*2 PA75B9-H PC2320*3+SB50*3
1
5
Cable 5#
Black wire 1015 10AWG 300mm PA75B2-H PA75B0-H
SB50*2
4
6
Cable 6#
2wires white 1015 10/12AWG 920*2/80*4mm BN5.5*2+SB50+PA75B9-H
P30*4
1
7
Cable 7#
Red wire 1015 10AWG 800mm E6012+PA75B2-H SB50
1
8
Cable 8#
Black wire 1015 10AWG 800mm E6012+PA75B0-H SB50
1
9
Cable 9#
4wires Black 1015 12AWG 110/110/250/250mm P30*4+YI16
1
10
Cable 10#
4wires Red 1015 12AWG 110/110/250/250mm P30*4+YI16
1
11
Cable 11#
Green & Yellow 1015 12AWG 80mm OI5.5-6*2
1
12
Breaker
NDB2Z-63 C63/1 1P 63A/250VDC UL certified
2
13
Battery Pack
W483*H133*D735
1