20
BE12
UK
10 - DIP SWITCH DIP2
2_4
ON
OFF
2_5
ON
OFF
2_6
ON
OFF
SPIA
/
FLASHING LIGHT
Terminal M2_7 and M2_8 work as WARNING LIGHT.
Terminal M2_7 and M2_8 work as FLASHING LIGHT.
The settings are stored during the rest phase (gate closed).
The default settings are highlighted in the boxes with grey background.
Description
DIP
Status
Function
2_7
ON
OFF
FUNCTIONING
TERMINAL 18
Terminal 18 works as START input, but it will not make the automatic closing even
if enabled.
Terminal 18 works as PEDESTRIAN input.
The pedestrian manoeuvre is made with condominium logic on leaf 1 and is not
modifiable. The automatic closing is active if the automatic general closing is active.
Disables the final stroke in closing function
ON
FINAL STROKE
IN CLOSING
UNUSED
2_8
2_10
Enables the final stroke in closing function
Operation:
After slowing down, the movement continues in slow down mode for 1s to facilitate
the locking of the electric lock.
During the final stroke in closing the safety devices and the commands are not
active (PHOTO, EDGE, START, etc.)
OFF
Long deceleration (~33% of the total stroke).
Irrelevant if DIP2_4=OFF.
2_9
Short deceleration (~25% of the total stroke).
ON
DECELERATION
DISTANCE
OFF
changing this setting will
reset the control board and
a new learning cycle will be
required.
UNUSED
UNUSED
21
BE12
UK
12 - DIP SWITCH DIP3
Transmitter button 1.
3_1
3_2
OFF
OFF
START COMMAND
ALLOCATION TO
TRANSMITTER
BUTTON
Description
DIP
Status
Function
OFF
ON
Transmitter button 2.
ON
OFF
Transmitter button 3.
ON
ON
Transmitter button 4.
3_3
3_4
OFF
OFF
PEDESTRIAN
COMMAND
ALLOCATION TO
TRANSMITTER
BUTTON
OFF
ON
ON
OFF
ON
ON
If this setting is the same as
DIP3_1 and DIP3_2,
PEDESTRIAN is disabled.
3_5
OFF
UNUSED
3_6
ON
OFF
UNUSED
Keep this OFF, do not change.
In order to store the new settings It’s necessary to power down and power up the control board.
The default settings are highlighted in the boxes with grey background.
Transmitter button 1.
Transmitter button 2.
Transmitter button 3.
Transmitter button 4.
Description
JUMPER
Status
Function
SW4
FUNCTIONING
TERMINAL 21
N.C. devices are connected to STOP/EDGE (21) input
8,2KOhm (8K2) resistive devices are connected to STOP/EDGE (21) input.
The settings are stored during the rest phase (gate closed).
The default settings are highlighted in the boxes with grey background.
11 - JUMPER SW4
Summary of Contents for AS06260
Page 50: ...50 BE12 NOTE NOTES NOTES NOTAS ...