background image

A

ctuAtor

 

with

 

integrAted

 

regulAtor

, K282

for

 r298 

And

 r298n 

mixing

 

vAlve

0262EN 

May 2013

047U31758

3

ISO

9001

0006/7

ISO

14001

0032A/2

OHSAS

18001

0064L/0

Installation

• Unscrew the hand-wheel protecting body before assembling and adjust 
the shutter manually on R298 or R298N valve.
• Fix K282 actuator through its apposite brass fixing ring: the ring must be 
screwed to the valve body up to end stroke in order to ensure max. stroke 
to the shutter.
• Insert the immersion probe in a R227 pit, downstream of the secondary 
circulator, and block by means of the fixing screw.

Positions of the linear stem of the actuator

The action of the digital regulator integrated in K282 actuator associates 
the stem completely retracted to the position of complete closure (0%) as 
shown in the picture; the stem completely protruding from the actuator 
body is associated to the position of complete opening (100%).

Correct installation positions of K282 actuator

Dimensions

Compliance

- CE
- EMC 2004/108/CE
- Low voltage directive 2006/95/CE

Motorized manual control of the valve

The manual positioning (open ring) of the mixing valve is useful when 
starting a system or in order to check the functioning. This operation can 
be made with K282 actuator by extracting the apposite jumper on the 
board, after removing the upper shell: the rotating potentiometer position 
represents the required opening for the mixing valve in this manual state 
of functioning. The opening of the direct way from the boiler of the valve 
increases by rotating the potentiometer clockwise when Giacomini mixing 
valves are used. The stem of the actuator is completely retracted (0%) and 
the mixing valve closes the direct way completely (by-pass position), when 
the rotating potentiometer is completely rotated anticlockwise; the stem 
of the actuator is protruding (100%) and the mixing valve opens the direct 
way completely, when potentiometer is completely rotated clockwise.

For the manual positioning:
• Remove 24 V~ supply to K282 actuator
• Loosen the actuator ring fixing to valve body and unscrew the actuator 
completely
• Remove the upper shell of the actuator by removing the 4 fixing screws
• Extract the jumper placed on the electronic board as shown in the picture
• Position the upper shell of the actuator again through the 4 fixing screws
• Assemble K282 actuator on the valve body again
• Activate 24 V~ supply
• The actuator resets completely until it closes the direct way completely 
(0%)
• The actuator positions at the indicated opening through the rotating 
potentiometer.
When the functioning test is finished, follow the instructions and insert the 
jumper placed on the electronic board.

1

2

3

4

6

7

8

2

1

1

2

1

2

3

4

6

7

8

1  Jumper for manual control (open ring) of the actuator

2  8 way microswitch for actuator addressing

Caution!

Manual positioning tests of the valve must be carried out once 
the jumper on the electronic board has been extracted and 
after assembling again and fixing with the 4 apposite screws the 
upper shell of the actuator. Do not activate 24 V~ supply before 
assembling the upper shell again. The manual positioning of the 
valve must be carried out by qualified staff only.

Caution!

The reading of immersion delivery temperature probe is not taken 
into account during the manual positioning test of the valve. Make 
sure that the delivery temperature is not over or under the safety 
limits according to the kind of system. The manual positioning of 
the valve must be carried out by qualified staff only.

Retracted stem,

by-pass position of R298 valve

Protruding stem,

opening position of the

direct way of R298 valve

70

78

48

Dimensions in mm

Summary of Contents for Giacoklima Series

Page 1: ...er winter switching has been made through selector position the rotating potentiometer at the desired set according to the appropriate graduated scale the scale working during the winter is indicated with red numbers range from 20 C to 60 C ascending clockwise the scale working during the summer is indicated with blue numbers range from 15 C to 25 C ascending anticlockwise Both controls are used i...

Page 2: ...tuator and KM203 network controller are transfered through the system bus connection to primary bus by using RT RT and Com terminals In addition the supply for the communication function is carried through the system bus by using V and Com terminals Max 3 K282 actuators can be connected to KM203 network controller 1 2 3 4 6 7 8 2 1 1 2 1 2 3 4 6 7 8 1 Jumper for manual control open ring of the act...

Page 3: ...en the rotating potentiometer is completely rotated anticlockwise the stem of the actuator is protruding 100 and the mixing valve opens the direct way completely when potentiometer is completely rotated clockwise For the manual positioning Remove 24 V supply to K282 actuator Loosen the actuator ring fixing to valve body and unscrew the actuator completely Remove the upper shell of the actuator by ...

Page 4: ...923 372 6 39 0322 923 255 consulenza prodotti giacomini com This pamphlet is merely for information purposes Giacomini S p A retains the right to make modifications for technical or commercial reasons without prior notice to the items described in this pamphlet The information described in this technical pamphlet does not exempt the user from following carefully the existing regulations and norms ...