Addressing
The addressing through microswitch with several ways is not relevant when
K282 actuator is used as single device (stand-alone configuration): it is not
necessary to make any configuration in this application.
The addressing through microswitch with several ways is vital for the correct
configuration of the device in those applications in which the actuator is used
in combination with KM20x network controller.
All microswitch sliders are positioned on “OFF” (side with 1-8 numbers)
on delivery. K282 actuator uses selectors from 1 to 6 to assign an address
between 0 and 31: check the address to assign on the design documentation
of the system.
Signalling elements
The led on the frontal side of K282 actuator provides two kinds of information:
the application type, stand-alone or with bus signal network connection to
KM203 network controller and summer/winter mode set to regulate the
delivery temperature.
Fixed red: indicates stand-alone functioning in WINTER mode.
Fixed green: indicates stand-alone functioning in SUMMER mode.
Flashing red: indicates the functioning in combination with KM203 network
controller in WINTER mode.
Flashing green: indicates the functioning in combination with KM203
network controller in SUMMER mode.
Flashing alternate red/green: indicates that K282 actuator, used in combination
with KM203 network controller, is no more supervised by KM203 because of
an anomaly (deactivation of supply to network controller or communication
problems on bus network).
The operating set has become the one set on the rotating potentiometer and
the real mode, that is the one imposed by the supervisor, is not coherent with
the operating mode imposed by the manual selector on the frontal side. With
this signal, it is recommended to check the correct supply to the network
controller and the correct functionality of bus network.
When 24 V~ supply is activated to K282 actuator, the integrated electronic
regulator starts a cycle of adjustment in which the stem of the actuator is
led to complete by-pass position (the whole stem has gone back in the
actuator body).
Connection to bus
Data between K282 actuator and KM203 network controller are transfered
through the system bus (connection to primary bus) by using RT+, RT- and
Com terminals. In addition, the supply for the communication function is
carried through the system bus by using V and Com terminals. Max. 3 K282
actuators can be connected to KM203 network controller.
1
2
3
4
6
7
8
2
1
1
2
1
2
3
4
6
7
8
1 Jumper for manual control (open ring) of the actuator
2 8 way microswitch for actuator addressing
SHUTOFF
K282X002
24V
50/60 Hz
5VA
SENSOR DELIVER
Y TEMP
.
BLU WHITE GREEN YELLOW
V Com R
T-
RT
+
GRA
Y
24V
BUS
BROWN
SHUTOFF PINK
Conductor color
Function
BROW
24 V~ supply connection
GRAY
24 V~ supply connection
Conductor color
Function
YELLOW
RT+ Signal (RS485 standard)
GREEN
RT- Signal (RS485 standard)
WHITE
Com Common ( supply)
BLUE
V SELV supply
Caution!
Before connecting K282 actuator, make sure that network tension IS
NOT CONNECTED and that it corresponds to the one written on the
back of the device (24 V~). The device must be installed by qualified
staff only.
Caution!
Before the connection to the system bus, make sure that
KM203 network controller is not supplied, not to damage the
communication module of K282 actuator. In case more than 3
actuators are connected to KM20x controller (through primary bus),
it is necessary to provide a separated supply of the devices. The bus
cable of K282 actuator must be placed in a canalization with an
electrical protective covering independent from canalizations that
carry network tension or that control actuators.
Position of microswitch ways
Ind.
1
2
3
4
5
6
0
OFF
OFF
OFF
OFF
OFF
OFF
1
ON
OFF
OFF
OFF
OFF
OFF
2
OFF
ON
OFF
OFF
OFF
OFF
3
ON
ON
OFF
OFF
OFF
OFF
4
OFF
OFF
ON
OFF
OFF
OFF
5
ON
OFF
ON
OFF
OFF
OFF
6
OFF
ON
ON
OFF
OFF
OFF
7
ON
ON
ON
OFF
OFF
OFF
8
OFF
OFF
OFF
ON
OFF
OFF
9
ON
OFF
OFF
ON
OFF
OFF
10
OFF
ON
OFF
ON
OFF
OFF
11
ON
ON
OFF
ON
OFF
OFF
12
OFF
OFF
ON
ON
OFF
OFF
13
ON
OFF
ON
ON
OFF
OFF
14
OFF
ON
ON
ON
OFF
OFF
15
ON
ON
ON
ON
OFF
OFF
16
OFF
OFF
OFF
OFF
ON
OFF
17
ON
OFF
OFF
OFF
ON
OFF
18
OFF
ON
OFF
OFF
ON
OFF
19
ON
ON
OFF
OFF
ON
OFF
20
OFF
OFF
ON
OFF
ON
OFF
21
ON
OFF
ON
OFF
ON
OFF
22
OFF
ON
ON
OFF
ON
OFF
23
ON
ON
ON
OFF
ON
OFF
24
OFF
OFF
OFF
ON
ON
OFF
25
ON
OFF
OFF
ON
ON
OFF
26
OFF
ON
OFF
ON
ON
OFF
27
ON
ON
OFF
ON
ON
OFF
28
OFF
OFF
ON
ON
ON
OFF
29
ON
OFF
ON
ON
ON
OFF
30
OFF
ON
ON
ON
ON
OFF
31
ON
ON
ON
ON
ON
OFF
Caution!
Make sure that the assigned address is correct: it is not possible
to have two devices with the same address in the same system.