SPECIAL CASES OF USE

The following image shows an installation in which, or for di

erent properties reasons , or for number of 

devices to be controlled exceeds 500 (Max 500 for each GE552Y058), it is necessary to create four 

di

erent networks of GE552Y053 Repeaters.

Obviously the following is valid also in cases where there are 2, 3, 5 or a higher number of Repeaters 

networks.

In order to avoid interferences between the various systems, assign to each GE552Y058 a di

erent 

Mesh 

network ID

. The setting is done on GE552Y058 through its web interface;

 Settings / Wireless Devices / 

Wireless Setup / Setup Mesh Network

.

The same 

Mesh network ID

 setting must be carried out also on all Repeaters that are part of the 

network of the GE552Y058 which they have to communicate with.

For this procedure it is necessary to connect a PC to the Repeater to be con

gured (via USB cable).

Use the 

GE552Y056 

software (downloadable from the download section of it.giacomini.com and follow 

the instructions in the manual.

SETTING OF MESH NETWORK ID

Note

: It is recommended not to change the Mesh Network  Channel (default = 13 both on GE552Y058

and on Repeaters), because the change may involve the transmission power of the devices.

LOADING ON REPEATERS OF A W. M-Bus DEVICES LIST IN THE PLANT

(ONLY ON REPEATERS WITH FIRMWARE VERSION FWRPT1_V1R20.hex ONWARDS)

Referring to the same image of the previous installation, the various Repeaters receive W. M-Bus signal 

from their plant devices but they can also receive the signal from devices of adjacent plants.

If one or more Repeaters receive the signal from more than 500 devices (Max 500 for each repeater),

REPEATERS FIRMWARE UPGRADE

You should always check the possible release of the latest 

rmware available version of the Repeaters,  

compared to the one installed on the devices in the production phase.

For this procedure it is necessary to connect a PC to the repeater to be con

gured (via cable

USB). Use the 

GE552Y056 

software (downloadable from the download section of it.giacomini.com and 

follow the instructions in the manual.

CONFIGURATION REPEATER THROUGH FUNCTIONALITY OF KEYS

Change ID MESH - GE552Y053

1. Press keys 2 and 3 (2s. < T <6s) simultaneously.

2. On release all the LEDs (8) will 

ash at the same time to indicate 

    that you have entered edit mode ID MESH

3. Now press button 3 (at least 1s.) to switch the ID MESH.

    - ID MESH 1 => Green LED (8.1) on - the others o

    - ID MESH 2 => Green LED (8.2) on - the others o

    - ID MESH 3 => Green LED (8.3) on - the others o

    - ID MESH 4 => Green LED (8.4) on - the others o

4. To SAVE press keys 2 and 3 simultaneously for more than 1s. 

    Press the 2 button to exit without saving.

5. Verify that the blue LED does not remain on steady. 

    Otherwise, restart from point 1. by selecting another MESH ID.

6. If, after switching on all four MESH IDs, the blue LED continues to 

    remain on steady, it will be necessary to con

gure the 

    GE552Y053 via GE552Y056 software.

7. Repeat for each GE552Y053.

Activate SND_IR mode (Installation Mode) - GE552Y053

a) It typically involves the installation of the AMR system and 

    subsequently the installation of the heat cost allocators

b) Both the AMR system and the distributors must be con

gured to work 

     in this mode

c) SND_IR mode activation procedure on a newly installed 

    GE552Y053

1. Press button 2 (t> 6s.). When pressing button 2, the green LED (8.1) 

    

ashes every second, until you are under the 6s. Once the 6s have 

    passed, the LED (8.1) 

ashes every 500ms => this indicates that the 

    "SND_IR" scan mode has been changed.

2. RPT enters the "SND_IR" scan mode. RPT receives and takes over all 

    the devices that transmit the installation W-M-Bus telegram. 

    (This frame contains no data)

3. Scan duration without user intervention 12 hours -> Manual stop of 

    the scan => press key 2 (no coded pressure time)

   Note: GE552Y053 automatically exits the SCAN mode after 

             12 hours.

Accept mode activation ALL - GE552Y053

a) It is used when the commissioning is carried out after with respect to 

    the installation of the heat cost allocators

b) To activate the accept ALL mode on a newly installed GE552Y053

1. Press button 2 (2s. < T < 6s)

2. When pressing button 2, the LED (8.1) 

ashes every second. When the 

    key 2 is released, the LED (8.1.) remains lit to indicate the activation of 

    the accept ALL mode.

3. RPT receives and takes charge of all devices transmitting in W.M-Bus 

    including frames in Installation Mode (SND_IR) - The 

rst green LED 

    lights up permanently - Scan duration without user intervention 12 hours

4. press the button 2 (no coded pressure time) to stop the scan manually

Note: if during the scan the RPT connects into the MESH network the mode 

of operation will automatically change with the value set on the GE552Y058.

GE552Y053 - S - T - C Mode of operation modi

cation

1. Press keys 2 and 3 simultaneously (t > 6s.)

 

during the simultaneous pressing of keys 2 and 3, the green LEDs 

   (8.1) and (8.2) will 

ash every second, until you are under the 6s. 

   Exceeded the 6s. they 

ash every 500ms

 

When keys 2 and 3 are released, one of the green LEDs (8) starts to 

    

ash (500ms) to indicate the currently active mode of operation on 

    that GE552Y053

2. The mode of operation is changed by pressing the 3 key brie

y

• Mode C+T => Green LED (8.1) on - the other o

 

 

Factory setting

• Mode S => Green LED (8.2) on - the other o

• Mode T => Green LED (8.3) on - the other o

3. save settings by pressing the 2 and 3 button (t> 2s.)

4. exit => key 2 for ESC function without saving (during programming 

    status). Automatic ESC from programming status after 10 minutes 

    later.

Note: GE552Y053 automatically exits the SCAN mode after 

          12 hours.

Restore factory settings

1. Press and hold keys 2 and 3 simultaneously.

2. Then press the reset button 4, without releasing the keys 2 and 3

3. As soon as all the LEDs (8) and (9) 

ash quickly, release all three keys.

9

1

2

1 - 100..240Vac power supply input (screw clamps)

2 - “Multi-function” button

3 - “Multi-function” button

4 -  Reset button

5 -  USB Port

3 4

6 - MESH network TX-RX LED

7 - W. M-Bus network TX-RX LED

8 - Signal level LED 

9 - Status LED 

5

6 7

8

GE552Y053_QSG_2.5_en

Giacomini

 reserves the right to make changes to this product without any notice 

GE552Y053 - Setup Repeater

Wireless M-Bus 868 MHz REPEATER

DOWNLOAD DOCUMENTATION

: https://giacomini.com/en/products/ge552-w

those exceeding 500 are ignored, and may in fact belong to the plant to be checked.

In this case it is necessary to charge, in the same Repeater, a 

le with a list of devices that are part of 

its plant (Maximum 500); after uploading the 

le, the signal of the devices that are not included in the list 

is ignored by the Repeater.

The 

le, whose name must be 

list.rpt

, must be a CSV 

le with a format such as the one shown in the 

following 

gure.

For this procedure it is necessary to connect a PC to the Repeater to be con

gured (via USB cable).

Use the 

GE552Y056 

software and follow the instructions in the manual.