GI.BI.DI AS05920 Instructions For Installation Manual Download Page 8

SC130

SC130

8

9

UK

UK

ELECTRICAL DIAGRAM

1 2 3 4 5 6

7 8 9 10 11 12 13 14 15

PH

NEUT

MOT COM

CLOS

OPEN

LAMP

FCA

FCC

COST

A

PHOT

O

COM

UP

DOWN

+12VDC

COM

TL TP

RV3

JP1

P1

SW1

ANT

F1

5A

 M

DL1 DL2 DL3 DL4 DL5 DL6

DL7

230 V

ac ~ NEUTRAL

 -

230 V

ac ~ PHASE -

ON

TECHNICAL CHARACTERISTICS

Power supply

Working time

No. of motors

Pause time

Courtesy light time

Photocells power supply

Operating temperature

Courtesy light / Flasher

Learnable transmitters

Transmitters receiver

Limit switch

230 VCA single-phase 50/60 Hz (F1-5A)

Adjustable 7-120s (JP1open) with trimmer TL

Adjustable 7-40s (JP1 close) with trimmer TL

1 x 500W

3-200s with trimmer TP

Sum between working time and pause time both after Open and after Close

12VDc 2W (F2-500mA restorable)

-20 +55 °C

230V 100W

30

Built-in, not replaceable

Inputs FCA and FCC in terminal board

INSTALLATION WARNINGS

Before proceeding with the installation, it is necessary to fit a magneto-thermal and differential switch of 10A max. 
upstream of the system. The switch must guarantee an omnipolar separation of the contacts, with an opening 
distance of at least 3 mm.

Differentiate  and  keep  the  power  cables  (min.  section  1,5mmq)  separated  from  the  signal  cables,  that  can 
be 0,5mmq.

WARNINGS:

• During wiring, the control unit must not be powered. 

• The use of this control unit must follow and strictly respect the technical standards of reference. 

• The installation and/or maintenance must be carried out only by qualified personnel, in compliance with regulations

in force. 

• The  manufacturer  cannot  be  considered  responsible  for  possible  damages  caused  by  improper  and/or 

unreasonable use. 

• A wrong installation or use of the product can compromise the safety of the system.

• All the materials contained in the package must be kept away from children, since they pose a potential risk. 

WARNING: IMPORTANT SAFETY INSTRUCTIONS.

It is important for the safety of persons to follow these instructions. 
Keep this instruction manual. 

Summary of Contents for AS05920

Page 1: ...a di comando ISTRUZIONI PER L INSTALLAZIONE Electronic control unit INSTRUCTIONS FOR INSTALLATION SC130 AS05920 Platine lectronique de gestion INSTRUCTIONS POUR L INSTALLATION Cuadro electr nico de ma...

Page 2: ...ETTRICO I 2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 PH NEUT MOT COM CLOS OPEN LAMP FCA FCC COSTA PHOTO COM UP DOWN 12VDC COM TL TP RV3 JP1 P1 SW1 ANT F1 5A M DL1 DL2 DL3 DL4 DL5 DL6 DL7 230 Vac NEUTRAL 23...

Page 3: ...ipolare dei contatti con distanzadiaperturadialmeno3mm Differenziare e tenere separati i cavi di potenza sezione minima 1 5 mmq dai cavi di segnale che possono essere da0 5mmq AVVERTENZE Durante il ca...

Page 4: ...ANIMAANTENNA filo saldato su circuito Ingresso PEDONALE N O Luce cortesia Lampeggiante Ingresso linea 230 Vac NEUTRO COMUNE Motore CHIUDE Motore Comune Ingressi Uscite Accessori APRE Motore Ingresso S...

Page 5: ...di 2 secondi a forza massima In apertura la forza sempre massima per tutta la corsa e non regolabile Funzionamento Con jumper JP1 APERTO TL 7 120s Con jumper JP1 CHIUSO default TL 7 40s Ruotando in se...

Page 6: ...IN CHIUSURA E CHIUSURA AUTOMATICA Chiusura automatica abilitata Funzionamento in risposta al comando di START Cancello chiuso APRE Durante l apertura PAUSA il cancello si ferma e parte il timer della...

Page 7: ...2s i tasti 1 e 2 di un trasmettitore gi memorizzato La centrale entrer inAPPRENDIMENTO e sar possibile seguire la normale procedurapermemorizzarenuovitrasmettitori 7 SMALTIMENTO GI BI DI consigliadir...

Page 8: ...RICAL DIAGRAM 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 PH NEUT MOT COM CLOS OPEN LAMP FCA FCC COSTA PHOTO COM UP DOWN 12VDC COM TL TP RV3 JP1 P1 SW1 ANT F1 5A M DL1 DL2 DL3 DL4 DL5 DL6 DL7 230 Vac NEUTRAL...

Page 9: ...The switch must guarantee an omnipolar separation of the contacts with an opening distance of at least 3 mm Differentiate and keep the power cables min section 1 5mmq separated from the signal cables...

Page 10: ...OSING opens again In PAUSE operates as STOP and cancels the automatic reclosing Protected by F1 5A Protected by F2 500mA resettable The gate opens for 7 s A START makes open all and interdicts the ped...

Page 11: ...2 s at max force In opening the force is always max for the complete stroke and it is not adjustable Operation With jumper JP1 OPEN TL 7 120s With jumper JP1 CLOSE default TL 7 40s Turning clockwise t...

Page 12: ...utomatic closing enabled Operation in reply to a START command Gate close OPEN During opening PAUSE the gate stops and the timer of the automatic closing starts Gate open CLOSE During closing Inverts...

Page 13: ...denies the pedestrian COMPLETE CANCELLATION OF TRANSMITTERS MEMORY Push the button P1 the led blinks then turns on and keep it pushed as long as the led will blink again and turn off 10s When you rele...

Page 14: ...A DE CABLAGE 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 PH NEUT MOT COM CLOS OPEN LAMP FCA FCC COSTA PHOTO COM UP DOWN 12VDC COM TL TP RV3 JP1 P1 SW1 ANT F1 5A M DL1 DL2 DL3 DL4 DL5 DL6 DL7 230 Vac NEUTRAL 2...

Page 15: ...voir en amont de l installation un interrupteur magn tique thermique et diff rentiel ayant une capacit maxi de 10A L interrupteur doit assurer une s paration omnipolaire des contacts avec une distanc...

Page 16: ...poser DIP1 en ON et DIP 9 en OFF En OUVERTURE arr t et libre l obstacle par 2 s En FERMETURE ouvre de nouveau En PAUSE marche comme STOP et annule la nouvelle fermeture automatique Prot g avec F1 5A...

Page 17: ...e 2 s force maxi En ouverture la force est toujours maxi par toute la course et n est pas r glable Fonctionnement Avec jumper JP1 OUVERT TL 7 120s Avec jumper JP1 FERME d faut TL 7 40s Tournant dans l...

Page 18: ...VRE par 7s Pendant l ouverture STOP Portail ouvert FERME Pendant la fermeture STOP Apr s un STOP il faut une commande et le mouvement part de nouveau dans la direction oppos e au mouvement pr c dent T...

Page 19: ...FACEMENT TOTAL MEMOIRE EMETTEURS appuyer sur la touche P1 le led clignote et puis s allume et le maintenir appuy jusqu quand le led clignotera de nouveau et s teindra 10s Quand on rel che la touche le...

Page 20: ...MA EL CTRICO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 PH NEUT MOT COM CLOS OPEN LAMP FCA FCC COSTA PHOTO COM UP DOWN 12VDC COM TL TP RV3 JP1 P1 SW1 ANT F1 5A M DL1 DL2 DL3 DL4 DL5 DL6 DL7 230 Vac NEUTRAL 2...

Page 21: ...en tablero de bornes Antes de proceder a la instalaci n hay que preparar aguas arriba de la misma un interruptor magneto t rmico y diferencial con capacidad m xima de 10A El interruptor debe garantiz...

Page 22: ...DIP1 en ON y DIP 9 en OFF En APERTURA para y libera el obst culo por 2 s En CIERRE abre de nuevo En PAUSA funciona como STOP y anula el recierre autom tico Protegida con F1 5A Protegido por F2 500mAq...

Page 23: ...e arranque de 2 s a fuerza m xima En apertura la fuerza es siempre m xima por toda la carrera y no es regulable Funcionamiento Con jumper JP1 ABIERTO TL 7 120s Con jumper JP1 CERRADO por defecto TL 7...

Page 24: ...rrada ABRE por 7s Durante la apertura STOP Cancela abierta CIERRA Durante el cierre STOP Despu s de un STOP es necesario un mando y el movimiento parte de nuevo en direcci n opuesta al movimiento prec...

Page 25: ...TRANSMISORES Apretar el bot n P1 el led destella y luego se enciende de nuevo y mantenerlo apretado hasta cuando el led destellar de nuevo y se apagar 10s Cuando se solta el bot n el led se enciende...

Page 26: ...SC130 26 NOTE NOTES...

Page 27: ...SC130 27 NOTE NOTES...

Page 28: ...DI S r l 46025 Poggio Rusco MN ITALY Tel 39 0386 52 20 11 Fax 39 0386 52 20 31 E mail info gibidi com Numero Verde 800 290156 Via Abetone Brennero 177 B w w w g i b i d i c o m Cod AIC9959 12 2017 Re...

Reviews: