ON

ON

STEP-BY-STEP 

WITH PAUSE 
IN OPENING, 

INVERSION

IN CLOSING 

AND 

AUTOMATIC 

CLOSING

Automatic closing enabled 
(if DIP8=OFF).
Operation in reply to a PEDESTRIAN 
command:
• Gate close: OPEN for 7s.
• During opening: PAUSE 
  (if DIP8=OFF), the gate stops and the
  timer of the  automatic closing starts. 
  STOP (if DIP8=ON).
• Gate open: CLOSE.
• During closing: STOP.
• After a STOP: It is necessary 
  a command and the motion starts 
  again in the opposite direction 
  of the previous motion.

OFF

ON

STEP-BY-STEP 

WITH STOP 

AND 

AUTOMATIC 

CLOSING

Automatic closing enabled.
Operation in reply to a START 
command:
• Gate close: OPEN.
• During opening: STOP.
• Gate open: STOP.
• During closing: STOP.
• After a STOP: It is necessary 
  a command and the motion starts 
  again in the opposite direction 
  of the previous motion.

Automatic closing disabled.
Operation in reply to a PEDESTRIAN 
command:
• Gate close: OPEN for 7s.
• During opening: STOP.
• Gate open: CLOSE.
• During closing: STOP.
• After a STOP: It is necessary 
  a command and the motion starts 
  again in the opposite direction 
  of the previous motion.

Automatic closing enabled.
Operation in reply to a START 
command:
• Gate close: OPEN.
• During opening: PAUSE, 
  the gate stops and the timer of the  
  automatic closing starts.
• Gate open: CLOSE.
• During closing: Inverts the motion.

TEST

TRANSMITTERS LEARNING

Push the button 

P1 for 2 s

 when you turn it on, the control unit starts in 

OPEN

.

Once reached the 

OPENING limit switch

 starts again in 

CLOSING

. Once reached the 

CLOSING limit switch

 it stops.

In this way you have the correct control unit/motor operation.

Push the button 

P1

, the control unit will enter in LEARNING (the led blinks, then turns on fixed), push the buttons 

of the transmitter to store:
• START function will be assigned to the first button pushed of a new transmitter.
• PEDESTRIAN function will be assigned to the second button pushed of the same transmitter.
It is possible to store in sequence some new transmitters as long as the led is turned off fixed.

After the learning of last transmitter, it is necessary to wait that led turns off (3s), indicating the system is ready to work 
in a normal way. 

WARNING

: After  learning  the  first  transmitter,  the  system  will  accept  only  that  family  of  codes  (if  the  first  one 

is Rolling, all the transmitters must be Rolling). It can learn 30 transmitters, when you arrive to the 31st the led blinks 
because the memory is full.  

PEDESTRIAN MANOEUVRE

With the 2nd button learned by the transmitter or DOWN from terminal board, the gate opens for 7 s, a START makes 
open all and denies the pedestrian.

COMPLETE CANCELLATION OF TRANSMITTERS MEMORY

: Push the button P1 (the led blinks, then turns on) 

and keep it pushed as long as the led will blink again and turn off (10s). When you release the button, the led turns on 
again, indicating that the system is ready to learn a new transmitter. 

LEARNING  OF  TRANSMITTERS  WITHOUT  ACCEDING  TO  THE  CONTROL  UNIT  (ROLLING 
TRANSMITTERS)

: Push the buttons UP and DOWN of the terminal board at the same time for 1 s or the buttons 

1 and 2 of a transmitter already stored at the same time for 2 s. The control unit will enter in LEARNING and it will be 
possible to follow the usual procedure to store the new transmitters.                                      

DISPOSAL

GI.BI.DI. advises recycling the plastic components and to dispose of them at special authorised 
centres for electronic components thus protecting the environment from polluting substances.

Summary of Contents for AS05920

Page 1: ...a di comando ISTRUZIONI PER L INSTALLAZIONE Electronic control unit INSTRUCTIONS FOR INSTALLATION SC130 AS05920 Platine lectronique de gestion INSTRUCTIONS POUR L INSTALLATION Cuadro electr nico de ma...

Page 2: ...ETTRICO I 2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 PH NEUT MOT COM CLOS OPEN LAMP FCA FCC COSTA PHOTO COM UP DOWN 12VDC COM TL TP RV3 JP1 P1 SW1 ANT F1 5A M DL1 DL2 DL3 DL4 DL5 DL6 DL7 230 Vac NEUTRAL 23...

Page 3: ...ipolare dei contatti con distanzadiaperturadialmeno3mm Differenziare e tenere separati i cavi di potenza sezione minima 1 5 mmq dai cavi di segnale che possono essere da0 5mmq AVVERTENZE Durante il ca...

Page 4: ...ANIMAANTENNA filo saldato su circuito Ingresso PEDONALE N O Luce cortesia Lampeggiante Ingresso linea 230 Vac NEUTRO COMUNE Motore CHIUDE Motore Comune Ingressi Uscite Accessori APRE Motore Ingresso S...

Page 5: ...di 2 secondi a forza massima In apertura la forza sempre massima per tutta la corsa e non regolabile Funzionamento Con jumper JP1 APERTO TL 7 120s Con jumper JP1 CHIUSO default TL 7 40s Ruotando in se...

Page 6: ...IN CHIUSURA E CHIUSURA AUTOMATICA Chiusura automatica abilitata Funzionamento in risposta al comando di START Cancello chiuso APRE Durante l apertura PAUSA il cancello si ferma e parte il timer della...

Page 7: ...2s i tasti 1 e 2 di un trasmettitore gi memorizzato La centrale entrer inAPPRENDIMENTO e sar possibile seguire la normale procedurapermemorizzarenuovitrasmettitori 7 SMALTIMENTO GI BI DI consigliadir...

Page 8: ...RICAL DIAGRAM 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 PH NEUT MOT COM CLOS OPEN LAMP FCA FCC COSTA PHOTO COM UP DOWN 12VDC COM TL TP RV3 JP1 P1 SW1 ANT F1 5A M DL1 DL2 DL3 DL4 DL5 DL6 DL7 230 Vac NEUTRAL...

Page 9: ...The switch must guarantee an omnipolar separation of the contacts with an opening distance of at least 3 mm Differentiate and keep the power cables min section 1 5mmq separated from the signal cables...

Page 10: ...OSING opens again In PAUSE operates as STOP and cancels the automatic reclosing Protected by F1 5A Protected by F2 500mA resettable The gate opens for 7 s A START makes open all and interdicts the ped...

Page 11: ...2 s at max force In opening the force is always max for the complete stroke and it is not adjustable Operation With jumper JP1 OPEN TL 7 120s With jumper JP1 CLOSE default TL 7 40s Turning clockwise t...

Page 12: ...utomatic closing enabled Operation in reply to a START command Gate close OPEN During opening PAUSE the gate stops and the timer of the automatic closing starts Gate open CLOSE During closing Inverts...

Page 13: ...denies the pedestrian COMPLETE CANCELLATION OF TRANSMITTERS MEMORY Push the button P1 the led blinks then turns on and keep it pushed as long as the led will blink again and turn off 10s When you rele...

Page 14: ...A DE CABLAGE 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 PH NEUT MOT COM CLOS OPEN LAMP FCA FCC COSTA PHOTO COM UP DOWN 12VDC COM TL TP RV3 JP1 P1 SW1 ANT F1 5A M DL1 DL2 DL3 DL4 DL5 DL6 DL7 230 Vac NEUTRAL 2...

Page 15: ...voir en amont de l installation un interrupteur magn tique thermique et diff rentiel ayant une capacit maxi de 10A L interrupteur doit assurer une s paration omnipolaire des contacts avec une distanc...

Page 16: ...poser DIP1 en ON et DIP 9 en OFF En OUVERTURE arr t et libre l obstacle par 2 s En FERMETURE ouvre de nouveau En PAUSE marche comme STOP et annule la nouvelle fermeture automatique Prot g avec F1 5A...

Page 17: ...e 2 s force maxi En ouverture la force est toujours maxi par toute la course et n est pas r glable Fonctionnement Avec jumper JP1 OUVERT TL 7 120s Avec jumper JP1 FERME d faut TL 7 40s Tournant dans l...

Page 18: ...VRE par 7s Pendant l ouverture STOP Portail ouvert FERME Pendant la fermeture STOP Apr s un STOP il faut une commande et le mouvement part de nouveau dans la direction oppos e au mouvement pr c dent T...

Page 19: ...FACEMENT TOTAL MEMOIRE EMETTEURS appuyer sur la touche P1 le led clignote et puis s allume et le maintenir appuy jusqu quand le led clignotera de nouveau et s teindra 10s Quand on rel che la touche le...

Page 20: ...MA EL CTRICO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 PH NEUT MOT COM CLOS OPEN LAMP FCA FCC COSTA PHOTO COM UP DOWN 12VDC COM TL TP RV3 JP1 P1 SW1 ANT F1 5A M DL1 DL2 DL3 DL4 DL5 DL6 DL7 230 Vac NEUTRAL 2...

Page 21: ...en tablero de bornes Antes de proceder a la instalaci n hay que preparar aguas arriba de la misma un interruptor magneto t rmico y diferencial con capacidad m xima de 10A El interruptor debe garantiz...

Page 22: ...DIP1 en ON y DIP 9 en OFF En APERTURA para y libera el obst culo por 2 s En CIERRE abre de nuevo En PAUSA funciona como STOP y anula el recierre autom tico Protegida con F1 5A Protegido por F2 500mAq...

Page 23: ...e arranque de 2 s a fuerza m xima En apertura la fuerza es siempre m xima por toda la carrera y no es regulable Funcionamiento Con jumper JP1 ABIERTO TL 7 120s Con jumper JP1 CERRADO por defecto TL 7...

Page 24: ...rrada ABRE por 7s Durante la apertura STOP Cancela abierta CIERRA Durante el cierre STOP Despu s de un STOP es necesario un mando y el movimiento parte de nuevo en direcci n opuesta al movimiento prec...

Page 25: ...TRANSMISORES Apretar el bot n P1 el led destella y luego se enciende de nuevo y mantenerlo apretado hasta cuando el led destellar de nuevo y se apagar 10s Cuando se solta el bot n el led se enciende...

Page 26: ...SC130 26 NOTE NOTES...

Page 27: ...SC130 27 NOTE NOTES...

Page 28: ...DI S r l 46025 Poggio Rusco MN ITALY Tel 39 0386 52 20 11 Fax 39 0386 52 20 31 E mail info gibidi com Numero Verde 800 290156 Via Abetone Brennero 177 B w w w g i b i d i c o m Cod AIC9959 12 2017 Re...

Reviews: