TTM-000W Series
BA_MA_TTM-00XW_EN_V1.00
29 / 37
6.7
Communication
No. Character
Name
Description
Initial Value
1
5Et
6
Setting Mode Selection
Screen
Communication Setting
Mode
Setting of the communication parameter.
2
_
Prt
Setting of Communication
Protocol
0
0
Dedicated Protocol
1
MODBUS (RTU)
2
MODBUS (ASCII)
3
_C
om
Setting of Communication
Parameters
B8n2
_C
om
※
*
☆★
BCC Checking Function
※
□□□ Type
n
OFF
b
ON
Selection of Data Length
*
Type
7
7
bit
8
8
bit
Parity Check Function
☆
Type
n
OFF
o
Odd
E
Even
Stopbit Length Function
★
Type
1
1 bit
2
2 bits
・
If MODBUS (RTU) is selected:
Only
8n2
,
8o1
and
8e1
can be selected.
・
If MODBUS (ASCII) is selected:
Only
7n2
,
7o1
and
7e1
can be selected.
BCC checking will be disabled.
4
_
bP5
Setting of Communication
Speed
9.6
1.2
1200bps
2.4
2400bps
4.8
4800bps
9.6
9600bps
19.2
19200bps
5
_
Adr
Communication Address
Setting
Setting Range: Dedicated Protocol
・・・
1-99 stations
MODBUS
・・・
1-247 stations
1
6
_
Awt
Setting of Response Delay
Time
Setting Range: 0-250ms
0
7
_
mod
Setting of the Switching of
Communication Mode
rw
R0
Communication R is available.
rw
Communication RW is available.
Switching is disabled in MODBUS mode.