E40.0.5X.6C-01
Operating Manual EASY
LOG
80IMP…
page 13 of 16
9. Specifications
Measuring range
0 … 60000 pulse / measuring cycle
Signal input
Note: input is not isolated from EASYBus
EASYLog 80IMP/S
Electrically isolated switching contact
contact closed (R < 50 Ohm)
contact open (R > 200 kOhm)
EASYLog 80IMP/T
TTL-signal input (active signal)
signal low: 0 – 0.5 V
signal high: 2.7 – 10 V (or input current limited to 2 mA)
Signal edge
Selectable (rise, fall resp. contact opens, closes)
Input resistance
EASYLog 80IMP/T Ri > 30 kOhm
Time base
1 … 9999 seconds,
resp. 0 = off (time base = measuring cycle of logging)
Display range
-2040 … 14000 Digit, programmable
Decimal point
any position.
Display unit
programmable, a selection of more than 25 units is given in
the software used
Resolution
1 digit
Accuracy
±0.1 % FS (at nominal temperature)
Display
two 4½-digit LCD-displays (about 7 and 5.8 mm high)
Interface
EASYBus
Busload
equals to 2 EASYBus-elements
Battery
1x fixed lithium cell (Li / SOCl2) 3.6V / 1200 mAh (= 4.32
Wh)
Battery life time
depending on the chosen measuring cycle about 5 years
(at 15 minutes and nominal temperature).
Measured value memory
250.000 measuring values
Measuring cycle
2 seconds to 5 hours (18000 seconds)
Memory type:
›cyclic logger‹
• recording can be activated by start/stop function (i.e. key-
press, boundaries).
• 64 independent recording sets are possible.
›ring logger‹
The logger records continuously;
as soon as the whole memory is used the old data of the
beginning are overwritten.
Recording period
depending on the chosen measuring cycle
i. e. 521 days at 3 min measuring cycle
7.1 years at 15 min measuring cycle