E44.X.01.6C-04
Mounting- and Operating Manual GIR 300
page 17 of 34
on.rG
Active,
(displays the selected limit)
The measuring range limit is exactly
bounded by the input signal. When ex-
ceeding or shortfalling the input signal the
device will display the selected
lower/upper display value.
[e.g. humidity: when shortfalling or ex-
ceeding, the device will display 0% or
100%]
Hint:
When exceeding the measuring range limit > 10% independently from the setting, the device
will always display an error message (“Err.1“ or “Err.2“).
-
Press button 1 to validate the selection, the display shows “
Li
“ again.
- When
pressing button 1 again, the display will show “
FiLt
“ (Filter
= digital filter
).
- Use button 2 and button 3 to select the desired filter [in sec.].
Selectable values: 0.01 ... 2.00 sec.
Explanation: this digital filter is a digital replica of a low pass filter.
Note: when using the input signal 0-50 mV a filter value of at least 0.2 is recommended
-
Press button 1 to validate your value, the display shows “
FiLt
“ again.
Now your device is adjusted to your signal source. Now the only thing left to do is to adjust the outputs of
the device.
-
When pressing button 1 again, the display shows “
outP
“. (output)
For configuring the outputs of the device, please follow the instructions given in chapter 6.9.
6.4 Measuring temperature
(Pt 100, Pt 1000 RTD probes and thermocouples type J, K, N, S or T)
This chapter describes how to configure the device for temperature measuring with the help of external
platinum RTD probes
or thermocouple probes. This instruction demands that you selected “
t.res
“ or “
t.tc
“
as your desired input type like it is explained in chapter 6.2. The device has
to display “
InP
“.
-
When pressing button 1 the display shows “
SEnS
“.
- Use button 2 or button 3 (middle or right button) to select your desired input signal.
Display
Input signal
(thermocouples)
Notes
niCr
NiCr-Ni (type K)
Meas. range: -270 ... +1350 °C
(-454 ... + 2462 °F)
S
Pt10Rh-Pt (type S)
Meas. range: -50 ... +1750 °C
(- 58 ... + 3182 °F)
n
NiCrSi-NiSi (type N)
Meas. range: -270 ... +1300 °C
(-454 ... + 2372 °F)
J
Fe-CuNi (type J)
Meas. range: -170 ... + 950 °C
(-274 ... + 1742 °F)
t
Cu-CuNi (type T)
Meas. range: -270 ... + 400 °C
(-454 ... + 752 °F)
-
Validate the selected input signal by pressing button 1. The display shows “
SEnS
“ again.
-
Press button 1 again, the display will show “
dP
“ (decimal point, for the resolution).
This menu parameter is only available at input signal Pt 100 and Pt 1000!
Display
Input signal
(RTD)
Notes
P100
Pt100
(3-wire)
Meas. range: -50.0 ... +200.0 °C
(-58.0 ... + 392.0
°F)
Meas. range: -200 ... + 850 °C
(-328 ... + 1562 °F)
1000
Pt1000
(2-wire)
Meas. range: -100.0 ... +200.0 °C
(-148.0 ... +
392.0 °F)
Meas. range: -200 ... + 850 °C
(-328 ... + 1562 °F)
F,LT
OVTP
SENS
DP