Installation and Operating Manual GEWAS 191 AN / N 

page 4 of 6

 

Installation and commissioning 

5.1    Installation of the solenoid valve 

Lock water feed lines

.  

Insert sieve sealing ring

Please take care having clean sealing surfaces

Connect solenoid with sleeve nut to the water feed by means of a 
right-hand turn. 

Check leak tightness by turning on the water supply

 

In case of leakage repeat the process above

Screw water connection tube onto the outlet of the solenoid valve 
(use sealing ring or make sure that the tube itself is properly 
sealed!

 ). 

If the installation has been carried out correctly the sleeve nut can be 
tightened by hand. In case of leakage check if sealing has been inserted 
and if all sealing surfaces are clean; also check if the installation has been 
carried out correctly. If necessary repeat installation process. 

Hint for commissioning:    The solenoid will not be opened unless it has 

been connected to the activated control device.  

Please ensure that the connection to the water feed are 
completely tight !! 
A water leakage on this position can´t be stoped by the  
solenoid! 

Do not apply turning force at housing, while mounted at tap - upper valve connection could be 
unscrewed and therefore getting untight ! 

5.2    Installation of the control unit and the water sensor 

-  

Make a rule to read the operating and maintenance advices before starting up the device. 

Place water sensor at desired position and fix it, if necessary. 

Note: 

Choose best position for the water sensor, that both metal electrodes come into contact with water 

as early and reliable as possible! (Keep an eye on floor unevenness).Protect against unintended shifting, e.g. 
by using a screw or mounting tape.

 

-  

Please take care that the sensor electrodes do not touch any metallic surfaces, this may cause errors. 

Connect water sensor to the control unit. 

Open water feed line unless you have already done so. 

Plug in control device into a socket outlet with earthing contact. 
=> Device is now active, the solenoid is open. 

Check water connection tubes for leakage. 

Connect device which is to be switched off in case of alarm to the socket outlet with earthing contact of the 
control device. 

 

! Well done, your GEWAS device is now ready for use ! 

Function 

If the water film at the water sensor exceeds 0.5 mm the control device automatically triggers an audible alarm and 
switches off the solenoid.  
The GEWAS 191 AN also switches off the device connected to the control device.  

To remove the alarm disconnect control device for a short time. 
Note: The alarm will also be activated if the water sensor has been disconnected. 

Alarm und operating signals 

audible alarm at 1s interval: 

alarm condition 

audible alarm, short signal every 10s: 

solenoid is not connected or defective 

solenoid continuously switches on and of 

insufficient power supply 

audible alarm at 2.5s interval 

insufficient power supply. 

 

 

water feed 
(tap) 

 

sieve sealing (inte-
grated in valve) 
sleeve nut 

water flow direction 
solenoid 

sealing ring 
sleeve nut 

water feed tube 
 

 

 

 

 

Summary of Contents for GEWAS 191 AN

Page 1: ...Tel 49 9402 9383 0 info greisinger de www greisinger de Installation and Operating Manual Alarm and protection device Leak water detector GEWAS 191 AN N Please read these instructions carefully before use WEEE Reg Nr DE 93889386 Please consider the safety instructions Please keep for future reference ...

Page 2: ...hing machine dish washer connected to the control de vice To be able to operate safely the device has to be checked for its correct function at regular basis please refer to Operating and maintenance advices of this document Operation is only allowed with the defined scope of supply or with original accessory for this device Application range Alarm and protection device for prevention of water dam...

Page 3: ...ety may be a risk when the device has visible damages is not working as specified has been stored under unsuitable conditions for a longer time In case of doubt please return device to manufacturer for repair or maintenance 5 Warning Do not use this product as safety or emergency stop devices or in any other applica tion were failure of the product could result in personal injury or material damag...

Page 4: ...nsor at desired position and fix it if necessary Note Choose best position for the water sensor that both metal electrodes come into contact with water as early and reliable as possible Keep an eye on floor unevenness Protect against unintended shifting e g by using a screw or mounting tape Please take care that the sensor electrodes do not touch any metallic surfaces this may cause errors Connect...

Page 5: ...ort circuiting both water sensor contacts by means of a metal object e g spoon knife etc Disconnect device and reconnect the device The solenoid has to react with a clearly audible clack sound This is to make sure that even if the water is calcareous and even if it is not regularly operated the solenoid is fully operational regard less of the calcareous deposits 5 The control device should not ope...

Page 6: ...feed 50 kPa 0 5 bar Working temperature 0 to 50 C Dimensions control unit 110 x 65 x 45 mm L x W x H solenoid valve 82 x 102 x 42 mm L x W x H Directives and standards The instruments confirm to following European Directives 2014 30 EU EMC Directive 2014 35 EU Low Voltage directive 2011 65 EU RoHS Applied harmonized standards EN 61326 1 2013 emissions level class B emi immunity according to table ...