EMC  interference resistance, 

(Type test)

Standards

EN 50081  (generic standard)

Conductes emission radio interference voltage 

(auxiliary supply)

150 kHz to 30 Mhz

CICPR 22, EN 5502, limit value class B

Radio field strenght

30 Mhz to 1000 MHz

CICPR 11, EN 55011, limit value class B

Mechanical tests

Vibration stress and shock loading steady state 

Standards

IEC 255-21, IEC 68-2

Vibration

sinusoidal

IEC 255-21-1, class I

10 Hz to 60 Hz: ± 0,035 mm amplitude

IEC 68-2-6

60 Hz to 150 Hz: 0,5 g acceleration
frequency sweep 1 octave/min.
20 cycles in the 3 axes vertical

Shock

half-sinusoidal

IEC 255-21-2, class I

acceleration 5 g, during 11 ms, 
3 shocks in both directions of the 3 axes each

Vibration with earthquake

sinusoidal

IEC 255-21-3, class I

1 Hz to 8 Hz: 

± 3,5 mm amplitude (hor. axis)

IEC 68-3-3

1 Hz to 8 Hz: 

± 1,5 mm amplitude (vert. axis)

8 Hz to 35 Hz: 

1 g acceleration (hor. axis)

8 Hz to 35 Hz: 

0,5 g acceleration (vert. axis)

frequency sweep 1 octave/min
1 cycle in the 3 axes vertical

Vibration stress and shock loading on transportation 

Standards

IEC 255-21, IEC 68-2

Vibration

sinusoidal

IEC 255-21-1, class II

5 Hz to 8 Hz: ± 7,5 mm amplitude

IEC 68-2-6

8 Hz to 150 Hz: 2 g acceleration
frequency sweep 1 octave/min.
20 cycles in the 3 axes vertical

Shock

half-sinusoidal

IEC 255-21-2, class I

acceleration 15 g, during 11 ms,

IEC 68-2-27

3 shocks in both directions of the 3 axes each

Continuous shock

half-sinusoidal

IEC 255-21-2, class I

acceleration 10 g, during 16 ms,

IEC 68-2-27

1000 shocks in both directions of the 3 axes

13/16

___________________________________________________________________________________________________________________________________________________________________________________________________________

__________________________________________________________________________________________________________________

GHIELMETTI AG |

 

Industriestrasse 6 | 4562 Biberist | Schweiz | www.ghielmetti.ch | [email protected] | +41 32 671 13 13 (Telefon) | +41 32 671 13 14 (Fax)

Summary of Contents for 674.115.420.20

Page 1: ...___________________________________________________________________________________________________________________________________ ____________________________________________________________________...

Page 2: ...on must be reviewed for familiarization with safety markings and instructions before operation This product has been designed and tested in accordance with international standards STOP Safety Earth Gr...

Page 3: ...plugs are inserted from the front and enable any vertical column signals from the protection relays to be connected to any horizontal line so that the tripping signals can be transmitted to the tripp...

Page 4: ...ion and do not light after inserting in the right position then the diode plug is o k Power ON indication LED green 4 16 Connecting and Diode plugs Control elements of the Tripping Matrix 60 Output di...

Page 5: ..._______________________________________________________________________________________________________________________________________________________________________ ________________________________...

Page 6: ...ilure Power Remote Remote Supply Reset LED Test Auxiliary output screw mount connectors ________________________________________________________________________________________________________________...

Page 7: ...___________________________________________________________________________________________________ ____________________________________________________________________________________________________...

Page 8: ...____________________________________________________________________________________ __________________________________________________________________________________________________________________...

Page 9: ...___________________________________________________________________________________ __________________________________________________________________________________________________________________ G...

Page 10: ...____________________________________________________________________________________ __________________________________________________________________________________________________________________...

Page 11: ...20 Diode plugs Type GDS 621 ZS 20 sw part no 674 212 002 00 Max reverse voltage 1000 V Max permissible current 1 A current flow direction from column to row Insulation Specification IEC 255 5 Max vol...

Page 12: ...s III Irradiation High frequency field pulse modulated 10 V m 900 MHz repetition rate 200 Hz IEC 1000 4 3 class III Fast transient bursts 2 kV 5 50 ns 5 kHz burst 15 ms IEC 255 22 4 repetition rate 30...

Page 13: ...cceleration vert axis frequency sweep 1 octave min 1 cycle in the 3 axes vertical Vibration stress and shock loading on transportation Standards IEC 255 21 IEC 68 2 Vibration sinusoidal IEC 255 21 1 c...

Page 14: ...to 30 days a year max 95 relative humidity bedewing unaccepable ________________________________________________________________________________________________________________________________________...

Page 15: ...____________________________________________________________________________ __________________________________________________________________________________________________________________ GHIELMET...

Page 16: ...____________________________________________________________________________ __________________________________________________________________________________________________________________ GHIELMET...

Reviews: