4. Menu Functions
VIEW Menu:
is displayed during standard operation.
•
Press UP or DOWN buttons to view process parameters.
•
Press UP and DOWN buttons at the same time, to exit any
other display and return to VIEW menu.
•
Display will return to VIEW menu in 10 minutes unless a key
is pressed.
CALIBRATE Menu:
contains display setup and output
parameters. A security code feature prevents unauthorized
tampering. To access CALIBRATE menu:
•
Press ENTER button for 2 seconds to display:
•
Press UP, UP, UP, DOWN buttons in sequence
to display:
OPTIONS Menu:
contains setup and display features for minor
display or output adjustments. To access OPTIONS menu:
•
Press ENTER button for 5 seconds to display:
•
Press UP, UP, UP, DOWN buttons in sequence
to display:
Menu Tips
•
Right button scrolls to right, from top to bottom row, and allows
editing when ">" symbol is shown.
•
In CALIBRATE or OPTIONS menus, the transmitter will
continue to measure and control outputs. When > is pressed,
the input value is held at the last measured process value.
•
When sensor is not connected, unit will display CHECK
SENSOR and any output controlled by sensor will be at 3.6 mA
or OFF.
LAST CAL:
08-01-99
LAST CAL:
01-01-99
+GF+ SIGNET
LAST CAL:
01-01-99 >
Example
To change date, first enter CALIBRATE menu (Press ENTER button for 2 seconds; Press UP, UP, UP, DOWN buttons in sequence)
Once in CALIBRATE menu, press UP button 1 time.
SAVING
ENTER
1.
I Display shows right
I
arrow
3.
I Press buttons to scroll
I
through numbers.
2.
I Press RIGHT button
I
to display "01" blinking
4.
I Press ENTER button
I
to save
5.
I Display now reads
I
new date
ENTER
LAST CAL:
08-01-99
ENTER
ENTER
+GF+ SIGNET
ENTER
+GF+ SIGNET
+GF+ SIGNET
+GF+ SIGNET
CALIBRATE: ----
Enter Key Code
CALIBRATE: XXXX
Enter Key Code
OPTIONS: ----
Enter Key Code
OPTIONS: XXXX
Enter Key Code
3.4 Differential Mode (2 Sensor Inputs Required)
The selected open-collector or current output is based on the
difference of Sensor 1 minus Sensor 2. To enable differential
mode, the selected output's "Source" selection must be set to
differential mode "DF", "DT", or "DP".
Sensor 1 - Sensor 2 = Difference
1. Unit of measure is based on Sensor 1.
2. Decimal is based on Sensor 2. Sensor 2 should be the
smallest unit measured or negative values will be generated.
3. Difference calculated in units only; not percentage.
+GF+ SIGNET
ENTER
Sensor 1 (80)
Sensor 2 (20)
For pressure and temperature transmitters ensure Sensor 1 is
equal to ID 1:
Sensor 1 - Sensor 2
Difference = 60
Example: 4-20 mA
Loop1 Range: 0-120
Loop1: = 12.00 mA
Example: Output
Output1 Mode: Low
Output1 Setpoint: 70
Output1 = ON