Signet 2100 Turbine Sensor Operating Instructions

WARNING!

1.  Do not remove from pressurized lines.
2.   Never install sensor without O-rings.
3.  Confi rm chemical compatibility before use.
4.  Do not exceed maximum temperature/pressure specifi cations.
5.  Wear safety goggles and faceshield during installation/service.
6.  Failure to follow safety instructions could result in severe personal injury.

Contents

1. Installation/Mounting
2. Sensor Wiring
3. Calibration
4. Specifi 

cations

5. Parts and 

Accessories

1.  Installation/Mounting

1.  Install sensor with arrow pointing in the direction 
 

of fl ow.  All mounting angles acceptable.

2.  Slide union nut onto pipe or fl exible tubing.
3. Install 

end 

connectors.

4.  Hand tighten union nut to secure.

2. Sensor Wiring

Wiring Tips:

• 

Use 2-conductor twisted-pair shielded cable (Belden #8451 or 
equivalent) for sensor cable splices up to 300 m (1000 ft) max.

• 

Maintain cable shield through cable splice.

• 

Route sensor cable away from AC power lines.

• 

Suitable for clear or opaque fl uids.  Suspended solids may 
cause mechanical failure.

• 

Upstream/downstream mounting requirements: 

10x I.D.

5x I.D.

Inlet

Outlet

Flange

15x I.D.

5x I.D.

Reducer

40x I.D.

5x I.D.

2 x 90° Elbow

50x I.D.

Valve/Gate

5x I.D.

20x I.D.

5x I.D.

90° Elbow

25x I.D.

5x I.D.

2 x 90° Elbow

64 mm

(2.5 in.)

33.3 mm
(1.3 in.)

43.2 mm
(1.5 in.)

12.2 mm

(.48 in.)

Pipe

End Connector

Union Nut

Reversible
electronics

O-rings
(factory installed)

Press to release

Input

Gnd.

10 kΩ 

+

5 to 24
VDC

-

Black  

Shield

Red

Other
instrument

Black (5 to 24 VDC)

Red (Signal out)

Shield (DC return)

Blk 
Power

Red 
Freq. input
Shld
Gnd

Signet

2100 Turbine

Flow Sensor

Other

Instrument

Signet

Instrument

*3-2100.090-1*

3-2100.090-1 

Rev. F  8/05 

English/German/French/Spanish

English

German

French

Spanish

Summary of Contents for Signet 3-2100-2H

Page 1: ...uctor twisted pair shielded cable Belden 8451 or equivalent for sensor cable splices up to 300 m 1000 ft max Maintain cable shield through cable splice Route sensor cable away from AC power lines Suit...

Page 2: ...IR connector kit PVDF DN 15 3 2100 36 159 000 010 Metric Socket connector kit PVC DN 15 3 2100 37 159 000 011 SCH 80 Socket connector kit PVC 1 2 in 3 2100 38 159 000 012 NPT Thread Socket connector...

Page 3: ...Verdrahtung 2 adriges verdrilltes abgeschirmtes Kabel Belden Nr 8451 oder gleichwertig f r Sensorkabelsplei e bis maximal 300 m 1000 Fu verwenden Kabelabschirmungen m ssen durch den Kabelsplei gef hrt...

Page 4: ...lonen min Rohrgr e DN 15 1 2 Zoll Schlauchgr e 1 2 Zoll 3 8 Zoll 1 4 Zoll Genauigkeit 3 des Me wertes Wiederholbarkeit 0 5 des Me wertes Gewicht 151 g 0 33 lbs Material Sensork rper Rotor PVDF Welle L...

Page 5: ...er l ensemble 2 C blage du capteur Suggestions de c blage Utiliser un c ble blind paire torsad e 2 conducteurs Belden n 8451 ou quivalent pour les pissures de c ble de capteur jusqu un maximum de 300...

Page 6: ...C 4 Sp ci cations G n ralit s Plage de d bit faible 0 38 3 8 l min 0 1 1 gallon U S min lev 3 38 l min 0 8 10 gallon U S min Dimension du tuyau DN 15 1 2 po Dimension du exible 1 2 po 3 8 po 1 4 po Pr...

Page 7: ...eado del sensor Sugerencias para el cableado Utilizar un cable blindado trenzado de dos conductores Belden n 8451 o equivalente para empalmes de cable de sensor hasta de 300 m 1000 pies Mantener el bl...

Page 8: ...ujo L 0 38 a 3 8 l min 0 1 a 1 galones min H 3 a 38 l min 0 8 a 10 galones min Tama o de tuber a DN 15 1 2 pulgada Tama o de manguera 1 2 3 8 1 4 pulgada Exactitud 3 de la lectura Repetibilidad 0 5 d...

Reviews: