TS 5000 E
GB 5
Mounting and securing
24 V connection
6.4
Connect 24 V cable to luster terminal. Electrical hold-open device is powered.
X
red = ”+” (terminal 1)
white = ”-” (terminal 2)
Fig.: 6.4.1
Adjusting Electrical hold-open device
6.5
Open door leaf to desired hold-open angle and fix it there (
X
1.).
Remove cable protection foils from guide rail (
X
2.).
Loosen clamping screws of electrical hold-open device (
X
3.).
Move electrical hold-open device until catch contacts sliding block
X
(4.).
Screw down electrical hold-open device securely
X
(5.).
To prevent loops from forming, tighten cable and fasten cable protection at hold-open device end (
X
6.).
Store cable in cable protection and in upper cable chamber behind electrical hold-open device (
X
7.).
Secure stored cable with cable protection foil (
X
8.).
CAUTION!
Check free upward movement of the rocker!
X
9.
Fig.: 6.5.1
If necessary, the holding force can be adjusted (9.). According to EN 1155, the release torque should
amount to 40 Nm - 120 Nm for a door with 90° hold- open angle.