GEZE IQ Box KNX
8
6
Overview of the KNX communication objects of the IQ box KNX
Object no.
Object name
Function
DPT
Flags
Length Direction
Operation and automatic
1
Window - Drive command
Open/Close
1.019
C W
1 Bit
IN
R
2
Window - Drive command
Step/Stop
1.007
C W
1 Bit
IN
R
3
Window - Position
Value [%]
5.001
C W
1 Byte
IN
R
4
Window - Gap ventilation
Trigger
1.017
C W
1 Bit
IN
T
5
Window - Time ventilation
Trigger
1.017
C W
1 Bit
IN
T
6
Window - Lock 1
Switch
1.001
C W
1 Bit
IN
T
7
Window - Lock 2
Switch
1.001
C W
1 Bit
IN
T
8
Automatic - Drive command
Open/Close
1.019
C W
1 Bit
IN
R
9
Automatic - Lock
Switch
1.001
C W
1 Bit
IN
T
10
Window - Speed next drive
Value [%]
5.001
C W
1 Byte
IN
R
11
Window - Actual position
State value [%]
5.001
C T
1 Byte
OUT
T
12
Window - Position between
State
1.002
C T
1 Bit
OUT
T
13
Window - Opened
State
1.002
C T
1 Bit
OUT
T
14
Window - Closed
State
1.002
C T
1 Bit
OUT
T
15
Window - Not closed
State
1.002
C T
1 Bit
OUT
T
16
Window - Do open
State
1.002
C T
1 Bit
OUT
T
17
Window - Do close
State
1.002
C T
1 Bit
OUT
T
Alarm
21
Alert - Safety
Switch
1.001
C S
1 Bit
IN
R
22
Alert - Wind speed
Value [m/s]
9.005
C S
2 Byte
IN
T
23
Alert - Wind alert
Switch
1.001
C S
1 Bit
IN
R
24
Alert - Rain alert
Switch
1.001
C S
1 Bit
IN
R
External push button
31
Button 1 (Cl.33) - Drive command
Open/Close
1.019
CT
1 Bit
OUT
T
32
Button 1 (Cl.33) - Drive command
Step/Stop
1.007
CT
1 Bit
OUT
T
33
Button 1 (Cl.33) - Position
Value [%]
5.001
CT
1 Byte
OUT
T
34
Button 2 (Cl.32) - Drive command
Open/Close
1.019
CT
1 Bit
OUT
T
35
Button 2 (Cl.32) - Drive command
Step/Stop
1.007
CT
1 Bit
OUT
T
36
Button 2 (Cl.32) - Position
Value [%]
5.001
CT
1 Byte
OUT
T
Service
41
Service - Check unit
State
1.005
CT
1 Bit
OUT
T
42
Service - Error unit
State
1.005
CT
1 Bit
OUT
T
43
Service - Error collection
State byte
5.010
CT
1 Byte
OUT
T
R
Standard object
T
Object becomes active by setting the parameter
Flags: K = Communication
S = Write
Ü = Transmit
Summary of Contents for IQ box KNX
Page 1: ...IQ box KNX 166560 00 EN Commissioning manual Prog Ru n...
Page 22: ...GEZE IQ Box KNX 22...
Page 23: ...GEZE IQ Box KNX 23...