IQ box KNX

166560-00

EN     Commissioning manual

Prog

Ru n

Summary of Contents for IQ box KNX

Page 1: ...IQ box KNX 166560 00 EN Commissioning manual Prog Ru n...

Page 2: ...diagram 6 5 Test operation and commissioning of the IQ windowdrives 7 5 1 Test operation 7 5 2 KNX commissioning 7 5 2 1 Load ETS product database IQ box KNX 7 5 2 2 Assign physical address of the IQ...

Page 3: ...is enclosed with the IQ box KNX and contains the most important product information and instruc tions about the electrical connection and about commissioning of the IQ box KNX IQ windowdrives install...

Page 4: ...k Ensure that the connection to the power supply is only carried out by a qualified electrician The power con nection and safety earth conductor test must be carried out in accordance DIN VDE 0100 610...

Page 5: ...4 V external 3 2 2 IQ box KNX top hat rail fitting to top hat rail IQ box KNX top hat rail Power supply NT 1 5 4 2 A 24 V HS GEZE surface housing ID 152010 with 35 mm top hat rail for 6 modules Prog R...

Page 6: ...mounting wiring diagram 8 9 10 11 12 A B S L GND 24V 33 32 COM A S LIN B S L L A B S A B 230V AC Fenster window 4 24 V DC max 6 A 3 5 7 6 IQ box KNX KNX KNX KNX 1 1 2 4 2 IQ box KNX top hat rail wirin...

Page 7: ...first time the closing position of the window is detected during the first closing procedure and is saved automatically Should the drive reverse after reaching the closing position drive opens by app...

Page 8: ...ndow Closed State 1 002 C T 1 Bit OUT T 15 Window Not closed State 1 002 C T 1 Bit OUT T 16 Window Do open State 1 002 C T 1 Bit OUT T 17 Window Do close State 1 002 C T 1 Bit OUT T Alarm 21 Alert Saf...

Page 9: ...cure windows against jamming a leaf speed of 5 mm s can be required within the framework of a safety analysis Drive noise increases as speeds increase Operation Interval ventilation Settable step widt...

Page 10: ...lation speed Not suitable for RWA Alarm Wind alarm Rain alarm For wind alarm a binary wind alarm and a wind alarm as threshold value in m s can be selected After the end of the wind rain alarm and a s...

Page 11: ...time 1 second 5 seconds 10 seconds 30 seconds 1 minute 2 minutes 5 minutes 10 minutes 20 minutes 30 minutes Open window Off time 1 second 5 seconds 10 seconds 30 seconds 1 minute 2 minutes 5 minutes...

Page 12: ...ventilation Disabled Enabled Window position 0 100 50 4 Window Gap ventilation Trigger Time ventilation Disabled Enabled Window position 0 100 50 5 Window Time ventilation Trigger Ventilation time 5 1...

Page 13: ...omatic Lock Switch Locked to close Unlock Via object 9 Automatic Lock Switch Until timeout Locking time min 1 300 30 9 Automatic Lock Switch Locked to open and close Unlock Via object 9 Automatic Lock...

Page 14: ...d state Disabled On change 12 13 14 15 16 17 Window Position between State Window Opened State Window Closed State Window Not closed State Window Do open State Window Do close State Cyclic Cycle time...

Page 15: ...action on safety alert Close window Open window Type wind alert Binary 23 Alert Wind alert Switch Threshold Threshold windspeed m s 2 30 4 22 Alert Wind speed value m s Behavior after wind rain alert...

Page 16: ...without self locking Close 32 Button 1 Cl 33 Drive com mand Step Stop Position Window position 0 100 50 33 Button 1 Cl 33 Position Value Button 2 Cl 32 Disabled Lokal Drive type Tip op eration with se...

Page 17: ...ion Disabled On change 41 Service Check unit State Error information Disabled Error unit Send condition On change 42 Service Error unit State Cyclic Cycle time min 1 255 50 Error collection Send condi...

Page 18: ...n group Local push button Expanded function examples KNX Easy ventilation controls All basic functions can be realised through the grouping of several windows centrally for the entire ventilation grou...

Page 19: ...tion examples KNX Automatic closing when the air conditioning is activated If the air conditioning is activated the windows are closed automatically Blocking of the manual opening As long as the air c...

Page 20: ...idity are exceeded intelligent ventilation is ap plied until the air quality returns to the requirements Controls depending on times of day and usage Ventilation at certain times depending on room us...

Page 21: ...ox KNX Check length of the connection cable to the drive The overall cable length between IQ box KNX and window must not exceed max 15 m Check software version of the drives on the identification plat...

Page 22: ...GEZE IQ Box KNX 22...

Page 23: ...GEZE IQ Box KNX 23...

Page 24: ...om cn France GEZE France S A R L E Mail france fr geze com www geze fr Hungary GEZE Hungary Kft E Mail office hungary geze com www geze hu Iberia GEZE Iberia S R L E Mail info geze es www geze es Indi...