GEZE IO 420
GEZE IO 420
13
12
5.2 Module type “1 door”
The “1 door” module type can be used for controlling one door. The connection of release switch, short-term
release push button, reed contact and lock feedback is possible. The messages are forwarded via bus.
Connections
Assignment/function description
Input
1
à
rising flank
- unlock
à
falling flank -
lock
2
Short-term release is triggered with rising flank
3
Bolt feedback
4
Door contact
Output
1
Electric strike fail safe
2
Electric strike fail secure
3
Can be configured
à
inactive
à
Sabotage alarm
à
closed
à
Locked
à
closed and locked
4
Can be configured
à
inactive
à
Sabotage alarm
à
closed
à
Locked
à
closed and locked
Tab. 2-pin assignment module type “1-door”
current state – current state
State changes to
State changes with
unlocked
In this state output 1 is enabled and output
2 is disabled.
Output 3 and 4 are enabled or disabled
depending on the configuration.
locked
if time switch is not enabled.
à
falling flank from input 1
à
CAN command “lock”
à
BACnet command “lock”
à
sabotage
time switch (ZSU)
If ZSU is active and one of the above-men-
tioned release devices occurs.
locked
In this state output 2 is enabled and output
1 is disabled.
Output 3 and 4 are enabled or disabled
depending on the configuration.
unlocked
à
rising flank from input 1
à
CAN command “unlock”
à
BACnet command “unlock”
short-term release (KZF)
à
rising flank from input 2
à
CAN command “short-term release”
à
BACnet command “short-term release”
time switch (ZSU)
If ZSU message is enabled and ZSU was not
interrupted.
short-term release (KZF)
In this state output 1 is enabled and output
2 disabled.
Output 3 and 4 are enabled or disabled
depending on the configuration. KZF time
can be extended by input 2 if “KZF re-
triggering” is enabled.
locked
If KZF time has expired
If KZF interruptible is enabled and the door is
closed again after opening. KZF is enabled for
at least 2.5 seconds
unlocked
à
rising flank from input 1
à
CAN command “unlock”
à
BACnet command “unlock”
time switch (ZSU)
In this state output 1 is enabled and output
2 disabled. Output 3 and 4 are enabled or
disabled depending on the configuration.
locked
with enabled option time switch inter-
ruption
à
falling flank from input 1
à
CAN command “lock”.
à
BACnet command “lock”
locked
without enabled option time switch inter-
ruption
à
sabotage
à
If time switch message is no longer
enabled.
Time switch interruption
If “time switch interruptible” is enabled in the IO 420 configuration, the “time switch” state can be interrupted using
the “lock” command. The state then changes to “locked” and the flag “time switch aborted” is set. No further change
in state can take place when the flag is set. The flag is reset again when the door is unlocked and locked. The message
“time switch” has to be enabled.
5.3 Module type “2 doors”
The “2 doors” module type can be used for controlling two mutually independent doors. The connection of door
contacts and lock feedback to the inputs is possible. The connection of a release switch is not designated for this
module type.
Connections
Assignment/function description
Input
1
Lock feedback door #1
2
Door contact door #1
3
Lock feedback door #2
4
Door contact door #2
Output
1
Electric strike fail safe door #1
2
Electric strike fail safe door #2
3
Can be configured for door #1
à
Inactive
à
Sabotage alarm
à
closed
à
Locked
à
closed and locked
4
Can be configured for door #2
à
Inactive
à
Sabotage alarm
à
closed
à
Locked
à
closed and locked
Tab. 3: Pin assignment module type “2-doors”
current state – current state
State changes to
State changes with
unlocked
In this state output 1 or 2 is enabled.
Output 3 and 4 are enabled or disabled
depending on the configuration.
locked
if time switch is not enabled.
à
CAN command “lock”
à
BACnet command “lock”
à
sabotage
time switch (ZSU)
If ZSU is active and one of the above-men-
tioned release devices occurs.
locked
In this state output 1 or 2 is disabled.
Output 3 and 4 are enabled or disabled
depending on the configuration.
unlocked
à
CAN command “unlock”
à
BACnet command “unlock”
short-term release (KZF)
à
CAN command “short-term release”
à
BACnet command “short-term release”
time switch (ZSU)
If ZSU message is enabled and if ZSU was
not interrupted.
short-term release (KZF)
In this state output 1 or 2 is enabled.
Output 3 and 4 are enabled or disabled
depending on the configuration. KZF re-
triggering is not possible in this mode.
locked
à
if KZF time has expired
à
if KZF interruptible is enabled and the
door is closed again after opening. The
min. KZF time is 2.5 seconds.
unlocked
à
CAN command “unlock”
à
BACnet command “unlock”
time switch (ZSU)
In this state output 1 or 2 is enabled.
Output 3 and 4 are enabled or disabled
depending on the configuration.
locked
with enabled option time switch interrup-
tion
à
CAN command “lock”.
à
BACnet command “lock”
locked
without enabled option time switch inter-
ruption
à
sabotage
à
If time switch message is no longer
enabled.