5.2   Module type “1 door”

The “1 door” module type can be used for controlling one door. The connection of release switch, short-term 

release push button, reed contact and lock feedback is possible. The messages are forwarded via bus.

Connections

Assignment/function description

Input

1

 

à

rising flank

 - unlock

 

à

falling flank - 

lock

2

Short-term release is triggered with rising flank

3

Bolt feedback

4

Door contact

Output

1

Electric strike fail safe

2

Electric strike fail secure

3

Can be configured

 

à

inactive

 

à

Sabotage alarm

 

à

closed

 

à

Locked

 

à

closed and locked

4

Can be configured

 

à

inactive

 

à

Sabotage alarm

 

à

closed

 

à

Locked

 

à

closed and locked

Tab. 2-pin assignment module type “1-door”

current state – current state

State changes to

State changes with

unlocked 

In this state output 1 is enabled and output 

2 is disabled.  

Output 3 and 4 are enabled or disabled 

depending on the configuration. 

locked 

if time switch is not enabled.

 

à

falling flank from input 1

 

à

CAN command “lock”

 

à

BACnet command “lock”

 

à

sabotage

time switch (ZSU)

If ZSU is active and one of the above-men-

tioned release devices occurs.

locked 

In this state output 2 is enabled and output 

1 is disabled. 

Output 3 and 4 are enabled or disabled 

depending on the configuration. 

unlocked

 

à

rising flank from input 1

 

à

CAN command “unlock”

 

à

BACnet command “unlock”

short-term release (KZF)

 

à

rising flank from input 2

 

à

CAN command “short-term release”

 

à

BACnet command “short-term release”

time switch (ZSU)

If ZSU message is enabled and ZSU was not 

interrupted.

short-term release (KZF) 

In this state output 1 is enabled and output 

2 disabled. 

Output 3 and 4 are enabled or disabled 

depending on the configuration. KZF time 

can be extended by input 2 if “KZF re-

triggering” is enabled. 

locked

If KZF time has expired
If KZF interruptible is enabled and the door is 

closed again after opening. KZF is enabled for 

at least 2.5 seconds

unlocked

 

à

rising flank from input 1

 

à

CAN command “unlock”

 

à

BACnet command “unlock”

time switch (ZSU) 

In this state output 1 is enabled and output 

2 disabled. Output 3 and 4 are enabled or 

disabled depending on the configuration.

locked 

with enabled option time switch inter-

ruption

 

à

falling flank from input 1

 

à

CAN command “lock”.

 

à

BACnet command “lock”

locked 

without enabled option time switch inter-

ruption

 

à

sabotage 

 

à

If time switch message is no longer 

enabled.

Time switch interruption

If “time switch interruptible” is enabled in the IO 420 configuration, the “time switch” state can be interrupted using 

the “lock” command. The state then changes to “locked” and the flag “time switch aborted” is set. No further change 

in state can take place when the flag is set. The flag is reset again when the door is unlocked and locked. The message 

“time switch” has to be enabled.

5.3   Module type “2 doors”

The “2 doors” module type can be used for controlling two mutually independent doors. The connection of door 

contacts and lock feedback to the inputs is possible. The connection of a release switch is not designated for this 

module type.

Connections

Assignment/function description

Input

1

Lock feedback door #1

2

Door contact door #1

3

Lock feedback door #2

4

Door contact door #2

Output

1

Electric strike fail safe door #1

2

Electric strike fail safe door #2

3

Can be configured for door #1

 

à

Inactive

 

à

Sabotage alarm

 

à

closed

 

à

Locked

 

à

closed and locked

4

Can be configured for door #2

 

à

Inactive

 

à

Sabotage alarm

 

à

closed

 

à

Locked

 

à

closed and locked

Tab. 3: Pin assignment module type “2-doors”

current state – current state

State changes to

State changes with

unlocked 

In this state output 1 or 2 is enabled. 

Output 3 and 4 are enabled or disabled 

depending on the configuration. 

locked 

if time switch is not enabled.

 

à

CAN command “lock”

 

à

BACnet command “lock”

 

à

sabotage

time switch (ZSU)

If ZSU is active and one of the above-men-

tioned release devices occurs.

locked 

In this state output 1 or 2 is disabled. 

Output 3 and 4 are enabled or disabled 

depending on the configuration. 

unlocked

 

à

CAN command “unlock”

 

à

BACnet command “unlock” 

short-term release (KZF)

 

à

CAN command “short-term release”

 

à

BACnet command “short-term release”

time switch (ZSU)

If ZSU message is enabled and if ZSU was 

not interrupted.

short-term release (KZF) 

In this state output 1 or 2 is enabled. 

Output 3 and 4 are enabled or disabled 

depending on the configuration. KZF re-

triggering is not possible in this mode. 

locked

 

à

if KZF time has expired

 

à

if KZF interruptible is enabled and the 

door is closed again after opening. The 

min. KZF time is 2.5 seconds.

unlocked

 

à

CAN command “unlock”

 

à

BACnet command “unlock”

time switch (ZSU) 

In this state output 1 or 2 is enabled. 

Output 3 and 4 are enabled or disabled 

depending on the configuration.

locked 

with enabled option time switch interrup-

tion

 

à

CAN command “lock”.

 

à

BACnet command “lock”

locked 

without enabled option time switch inter-

ruption

 

à

sabotage 

 

à

If time switch message is no longer 

enabled.

Summary of Contents for IO 420

Page 1: ...IO 420 164898 04 EN User manual IO 420 161864 03 DE Benutzerhandbuch...

Page 2: ...iese Warnhinweise immer X Befolgen Sie alle Ma nahmen die mit dem Warnsymbol und Warnwort gekennzeichnet sind Warnsymbol Warnwort Bedeutung VORSICHT Informationen zur Vermeidung von Sachsch den zum Ve...

Page 3: ...0 erf llt folgende Normen DIN EN 61000 6 2 2005 entsprechend VDE 0839 Teil 6 2 M rz 2006 DIN EN 61000 6 6 2007 A1 2011 entsprechend VDE 0839 Teil 6 3 September 2011 3 Produkt bersicht Montagehinweise...

Page 4: ...microSD Card gelesen oder geschrieben wird LED 2 gelb LED leuchtet wenn CP Kondensatorplatine angeschlossen ist LED 3 rot LED blinkt bei St rung LED 4 gr n LED blinkt im normalen Betrieb LED 5 gr n LE...

Page 5: ...SDAY 0 1 40 ZSUMASTER1_FRIDAY 0 1 41 ZSUMASTER1_SATURDAY 0 1 0 0 0 0 0 0 0 Day configuration ZSU master group 1 0 as ZSU master group 1 inactive on this day of the week 1 as ZSU master group 1 active...

Page 6: ..._GR4 0 1 116 DOOR4_SLAVEZSU_GR5 0 1 0 0 0 0 0 Slave assignment of door 4 to ZSU master group 1 to 5 0 Door 4 is not part of this ZSU group 1 Door 4 is part of this ZSU group 117 DOOR4_SLAVEZSU_ABORT 0...

Page 7: ...longer enabled Time switch interruption If time switch interruptible is enabled in the IO 420 configuration the time switch state can be interrupted using the lock command The state then changes to l...

Page 8: ...atic 4 sec is enabled output 3 is switched off again after 4 seconds night falling flank input 1 CAN command night BACnet command night shop closed CAN command close shop BACnet command close shop per...

Page 9: ...Die Verwendung von Sonderzeichen ist nicht erlaubt ausgenommen Leerzeichen Unterstrich Bindestrich Punkt und Komma 4 Parametrierung GEZE IO 420 Die erste Parametrierung des IO 420 sollte grunds tzlich...

Page 10: ...rminal box The inputs and outputs of the IO 420 can be used as an IO extension for the TZ 320 KL 220 has 4 inputs and 6 outputs Since the IO 420 has 4 inputs and 4 outputs the configuration for the fi...

Page 11: ...e IO 420 functions as gateway as in module type DCU 1 2 and 8 Therefore drives require DCU light so that the lifetime report is forwarded to IO 420 via Can Active leaves and passive leaves can also be...

Page 12: ...sind folgende Punkte zu beachten Der Parametername einschlie lich dem Zeichen darf nicht ge ndert werden Das fungiert hier als Trennzeichen zwischen Titelteil und Wert Der Parameter Wert darf nur Zah...

Page 13: ...19 3 1 4 N Y 5 door1_command 1 19 4 1 1 3 Y Y 6 door2_state 1 19 5 1 4 N Y 5 door2_command 1 19 6 1 1 3 Y Y 6 door3_state 1 19 7 1 4 N Y 5 door3_command 1 19 8 1 1 3 Y Y 6 door4_state 1 19 9 1 4 N Y...

Page 14: ...d 1 19 4 1 1 3 Y Y 66 6 1 9 module type window Mandatory Optional Keyname Objectname device obj Inst object type object inst present value default min present value max present value command able supp...

Page 15: ...N 4 door_state_DCU_SF 3 4 N N 4 Device_IO420 8 1 N N notification_class_obj 15 50 N N module_type 19 1 1 13 N N 1 Alarm_TZ 19 2 1 15 N N 6 50 operating_mode_DCU 19 3 1 14 N N 84 mode_command 19 4 1 1...

Page 16: ...alarm de layed alarm active 61 automatic night shop close permanently open 62 night day release short time release 63 no command unlock lock short time release 66 enable watchdog disable watchdog shor...

Page 17: ...unlocked 230V failure 54_DPS comm err unknown error unknown error 57_Smoke alarm SF unknown error unknown error 60_Err in control unit GF 61_Battery flat no error 94 78_Excess temperature SF 79_Motor...

Page 18: ...4 sec Window Universal Conf relay 1 Conf ZSU slave 1 ZSU slave size 1 ZSU slave size 2 ZSU slave size 3 ZSU slave size 4 ZSU slave size 5 Yes no Yes no Yes no Yes no Yes no No No No No No Conf ZSU int...

Page 19: ...on sheet The object descriptions cannot be backed up and must be entered again manually Firmware update Firmware updates are provided by GEZE in electronic form Copy the hex file to the directory Flas...

Page 20: ...2Pfs bat 11 FlashData IO420 IO420_V1 RICHTIG Flasher STM32 ProgSTM32Pfs bat 3 FlashData IO420 IO420_V1 GEZE IO 420 35 Abb 7 COM Port Einstellung im Ger te Manager X Datei IO420_Flasher bat erneut ausf...

Page 21: ...nce fr geze com www geze fr Hungary GEZE Hungary Kft E Mail office hungary geze com www geze hu Iberia GEZE Iberia S R L E Mail info es geze com www geze es India GEZE India Private Ltd E Mail office...

Reviews: