GEZE IO 420
GEZE IO 420
19
18
5.8.1 Active leaf
current state – current state
State changes to
State changes with
night
Outputs 1, 2 and 3 are disabled.
day
à
BACnet command “day”
à
CAN command “day”
released
à
rising flank of input “release”
à
BACnet command “release”
à
CAN command “release”
short-term release (KZF)
à
rising flank of input “KZF”
à
BACnet command “short-term release”
à
CAN command “short-term release”
day
Output 2 is enabled
night
à
falling flank from input “day/night”.
à
BACnet command “night”
à
CAN command “night”
released
à
rising flank of input “release”
à
BACnet command “release”
à
CAN command “release”
short-term release
à
rising flank of input “KZF”
à
BACnet command “short-term release”
à
CAN command “short-term release”
released
Output 3 is enabled.
night
à
falling flank of input “release” (the last
previous state was “night”)
à
BACnet command “night”
à
CAN command “night”
day
à
BACnet command “day”
à
CAN command “day”
short-term release
à
Not possible
short-term release
Output 1 is enabled.
night
à
falling flank of input “release” (the last
previous state was “night”)
à
BACnet command “night”
à
CAN command “night”
day
à
BACnet command “day”
à
CAN command “day”
released
à
rising flank of input “release”
à
BACnet command “release”
à
CAN command “release”
error
The error can be acknowledged with
any command.
5.8.2 Passive leaf
current state – current state
State changes to
State changes with
unlock
(shown as “release” in VAT 220): Output 4 is
enabled.
lock
à
BACnet command “lock”
à
CAN command “lock”
lock
(shown as “night” in VAT 220): Output 4 is
disabled.
unlock
if ZSU is not enabled.
à
the rising flank of input “release_IL”
à
BACnet command “unlock”
à
CAN command “unlock”
into lock
(shown as “day” in VAT 220): This state is an
intermediate state between “unlock” and
“lock”.
into unlock
(shown as “day” in VAT 220): This state is
an intermediate state between “lock” and
“unlock”.
error
(shown as “error” in VAT 220):
The error can be acknowledged with any
command.
5.9 Module type “RWS + KL”
In the module type “RWS + KL” the IO 420 works as a gateway between the CAN bus and BACnet and translates
the lifetime message of the TZ 320 into the BACnet protocol. The control commands generated are turned into
CAN commands by the IO 420 and forwarded to the TZ 320.
Gateway CAN BACnet
à
TZ 320 transmits a lifetime message every second, which is transformed into the BACnet protocol and forward-
ed on BACnet MS/TP level.
à
BACnet object multi state value 4 is defined for activating the TZ 320. This object comprises three commands:
“short-term release”, “unlock” and “lock”.
à
The bus functions of the TZ 320 e.g. “collective locking”, “BMA group over BUS” etc. are currently not supported
by the IO 420. The bus function “timer” is implemented and is supported.
à
If a ZSU master transmits a ZSU message via BACnet, the IO 420 translates this into a CAN message.
à
If the IO 420 is configured as a timer master, the IO 420 transmits the ZSU message both via CAN bus and
BACnet.
Terminal box
The inputs and outputs of the IO 420 can be used as an IO extension for the TZ 320.
KL 220 has 4 inputs and 6 outputs. Since the IO 420 has 4 inputs and 4 outputs, the configuration for the fifth and
sixth output of the KL 220 is not evaluated.
Fig. 3: Composition BACnet MS/TP and CAN for GEZE IO 420 as Gateway for TZ 320
Setting in TZ 320 and IO 420
à
CAN: The CAN address in TZ 320 and IO 420 must be identical for both devices to be able to communicate with
one another via CAN.
à
CAN terminating resistor The CAN terminating resistor in TZ 320 and IO 420 must be switched on.
à
The terminating resistor for the GEZE bus in IO 420 must be switched on. This setting is important for the “ter-
minal box” function.
à
Timer function:
The TZ 320 must be configured as a “slave”.
The IO 420 per segment must be configured as “master”.
à
The ZSU master function is supported by the IO 420 with the following module types:
à
1-door solution
à
2-door solution
à
4-door solution
à
Universal
GEZE IO 420
19
5.9 Modultyp „RWS + KL“
Im Modultyp „RWS + KL“ arbeitet das IO 420 als Gateway zwischen CAN-Bus und BACnet und übersetzt die Life-
time-Meldung des TZ 320 ins BACnet-Protokoll. Die erzeugten Steuerbefehle werden vom IO 420 in CAN-Befehle
umgesetzt und an TZ 320 weitergeleitet.
Gateway CAN BACnet
à
TZ 320 sendet jede Sekunde eine Lifetime-Meldung, die ins BACnet-Protokoll umgewandelt und auf BACnet
MS/TP-Ebene weitergeleitet wird.
à
BACnet-Objekt multistate value 4 ist für die Ansteuerung der TZ 320 definiert. Dieses Objekt umfasst drei
Befehle: „Kurzzeitfreigabe“, „Entriegeln“ und „Verriegeln“.
à
Die Bus-Funktionen der TZ 320, z.B. „Sammelverriegelung“, „BMA-Gruppe über BUS“, u. A. werden vom IO 420
derzeit nicht unterstützt. Die Bus-Funktion „Zeitschaltuhr“ ist implementiert und wird unterstütz.
à
Wenn ein ZSU-Master über BACnet ZSU-Meldung sendet, übersetzt das IO 420 diese in eine CAN-Meldung.
à
Wenn das IO 420 als Zeitschaltuhr-Master konfiguriert ist, sendet das IO 420 die ZSU-Meldung sowohl über
CAN-Bus als auch über BACnet.
Klemmenbox
Die Ein- und Ausgänge der IO 420 können als IO-Erweiterung für die TZ 320 verwendet werden.
Die KL 220 hat 4 Eingänge und 6 Ausgänge. Da das IO 420 4 Eingänge und 4 Ausgänge hat, wird die Konfigurati-
on für den fünften und sechsten Ausgang der KL 220 nicht ausgewertet.
Abb. 3: Aufbau BACnet MS/TP und CAN für GEZE IO 420 als Gateway für TZ 320
Einstellung in TZ 320 und IO 420
à
CAN: Die CAN-Adresse in TZ 320 und IO 420 muss identisch sein, damit die beiden Geräte miteinander über
CAN kommunizieren können.
à
CAN-Abschlusswiderstand: Der CAN-Abschlusswiderstand in TZ 320 und IO 420 muss eingeschaltet sein.
à
Der Abschlusswidertand für den GEZE-BUS in IO 420 muss eingeschaltet sein. Diese Einstellung ist wichtig für
die Funktion „Klemmenbox“.
à
Zeitschaltuhr-Funktion:
Die TZ 320 muss als „slave“ konfiguriert sein („ZSU-Gruppe x/ Busfunktion ein“).
Ein IO 420 je Segment muss als „master“ konfiguriert sein.
à
Die ZSU-Masterfunktion wird vom IO 420 bei folgenden Modultypen unterstützt:
à
1-Türlösung
à
2-Türlösung
à
4-Türlösung
à
Universal
GEZE
Cockpit