About the GeyserWise
Application
GeyserWise is suitable for installation 220V pumped solar hot water heaters.
When installing the GeyserWise be sure to follow the appropriate instructions of each particular manufacturer
for all other components as well:
Installation of geyser.
Installation of solar collectors.
Installation of pumps.
Installation
Installation, maintenance and dismantling may only be performed by trained personnel in accordance with
this instruction manual and safety instructions.
Use the GeyserWise only after first thoroughly reading and understanding this instruction manual and the
safety instructions. In the event of any ambiguities regarding the installation and operation, consult trained
personnel or contact our offices.
Technical information
Operating voltage 230VAC / 50HZ.
Main relay contact rating 20AMP.
Secondary relays pump 5Amp.
Operating voltage range 160V - 250V AC.
Recommended ambient temperatures: -20 to 55°C; Max 65°C
Temperature display range 0 - 200°C (“-5” when below -5°C “EA” ).
Temperature setting ranges 30 - 65°C.
Heat failure - when increase at a rate of 4°C or less per hour.
Mechanical thermal cut-out 90°C (300 manual resets) -
Please note this temperature for solar
systems expected to reach temperatures higher than 90°C.
Thermal cut-out - Isolate live.
Dry heat detection - empty cylinder.
Temperature tolerance ± 5°C and manufacturing drift is less than 6°C.
Temperature differential setting 1°C.
Switching differential for the element 6°C.
2nd temperature probe for solar.
Solar differential 7°C (default) - standard system. Settable 7°C - 15°C.
Temperature probe failure detection for both collector and tank.
Temperature probe range for geyser is -30 to +130°C.
Temperature probe range for collector is -30 to +260°C
Isolate both L + N when element in an off state.
Collector anti-freeze protection at 5°C (default). Settable 0°C - 10°C.
Please be sure to use the correct
solar systems for frost prone areas. More details can be found on the ESKOM website:
http://www.eskomidm.co.za/residential/residential-technologies/step-by-step-guide-to-choosing-a-solar-
water-heating-system
Control box insulated - Class 1.
Operating life - 50 000 cycles.