UPS
TECHNICAL DATA TABLE
MODELS
1 KW
2 KW
INPUT (1 Ø + N star configuration voltages)
Nominal voltage
220 – 230 – 240 Vac single-phase
Acceptable range
0 - 280 Vac
Voltage range for which no battery
intervention
Maximum voltage 276Vac
Minimum voltage:
from 184 to 138Vac between 100% and 50% of load in linear mode
Return to mains operation at 190Vac
Nominal frequency
50 - 60 Hz ±5 Hz
Maximum current (1)
30A
Nominal current (2)
24A
Power factor
≥
0.95
Current distortion @ maximum load
≤
6%
BYPASS (on L1)
Voltage range accepted for switching
180 - 264 Vac
Frequency range accepted for switching
Frequency selected ±5%
Switching time
0.1ms
BATTERY
Recharge time (8)
6-8 h
OUTPUT
Nominal voltage
220 / 230 / 240 Vac selectable ±1.5%
Static variation (3)
1.5% (7)
Dynamic variation (4)
≤
5% in 20 ms
Waveform
Sinusoidal
Voltage distortion @ linear load
≤
3%
Voltage distortion @ distorting load
≤
6%
Frequency (5)
50 or 60 Hz selectable
Current peak factor
≥
3 : 1
Nominal power in W
1000
2000
Short circuit current
1.5 x In per t=0.5sec
VARIOUS
Leakage current (to ground)
≤
10mA
AC/AC yield
92 %
Ambient temperature (6)
0 – 40 °C
Relative humidity
< 90 % non-condensing
Protections
Excessive battery discharge – overcurrent – short-circuit – overvoltage
– undervoltage –thermal
Hold-up time
≥
40msec
Noise level
< 45 dB(A) at 1 m
TECHNICAL DATA TABLE