54
FUNCTION
DESCRIPTION
PREDEFINED
POSSIBLE CONFIGURATIONS
MODE
Alarm threshold
for maximum
load
Selects the user
overload limit
Disabled
•
Disabled
•
0 ÷ 103 in 1% steps
Display
brightness
Selects the level of
brightness of the LCD
display
Maximum
Minimum ÷ Maximum in 20 steps
Acoustic alarm
Selects the operating
mode of the acoustic
alarm
Low
•
Normal
•
Low: does not sound for momentary
bypass intervention
Auxiliary socket
(power share)
Selects the operating
mode of the auxiliary
socket
Always
connected
•
Always connected
•
Disconnection after
n
seconds of
operation from battery
•
Disconnection after
n
seconds from
the end of discharge prealarm signal
•
... (see configuration software
manual)
ADVANCED SETTINGS
Input frequency
tolerance
Selects the allowed
input frequency range
for the passage onto
bypass and for
synchronization of the
output
± 5%
•
± 0.25%
•
± 0.5%
•
± 0.75%
•
± 1÷ ±10 in 1% steps
Bypass voltage
thresholds
Selects the allowed
voltage range for the
passage onto bypass
Low: 180V
High: 264V
Low: 180 ÷ 200 in 1V steps
High: 250 ÷ 264 in 1V steps
Bypass voltage
thresholds for
ECO
Selects the allowed
voltage range for
operation in ECO
mode
Low: 200V
High: 253V
Low: 180 ÷ 220 in 1V steps
High: 240 ÷ 264 in 1V steps
Sensitivity of
intervention for
ECO
Selects the sensitivity
of intervention during
operation in ECO
mode
Normal
•
Low
•
Normal
•
High
Power supply of
the load in stand-
by
Power supply of the
load on bypass with
UPS switched off
(stand-by state)
Disabled (load
NOT powered)
•
Disabled (not powered)
•
Enabled (powered)
Bypass operation
Selects the mode of
use of the bypass line
Enabled /
High sensitivity
•
Enabled/High sensitivity
•
Enabled/Low sensitivity
•
Disabled with input/output
synchronization
•
Disabled without input/output
synchronization
USE