5
The following parameters are displayed depending on the selected value:
“Value [x 0.1s]”
(if an identical
value is set for all channels) or
“Channel 1 value [x 0.1s]”, “Channel 2 value [x 0.1s]”, “Channel 3 value
[x 0.1s]”, “Channel 4 value [x 0.1s]”, “Channel 5 value [x 0.1s]” and “Channel 6 value [x 0.1s]”
(if a
diversity value is set for each channel), which determine the minimum effective time during which the device
must detect the pressing of the button to differentiate between the short operation and the long operation
associated with the channel.
The possible values are:
-
from 3 to 150 with step 1,
5 (default value)
The following example shows the meaning of the above parameters
3.1.3 Transmission delay after start
This parameter is used to define the time that must pass after which the device may transmit the telegrams
on the bus following a drop/recovery of the bus supply voltage, to ensure that, with multiple devices in the
line, the telegrams sent by the various devices do not collide when the bus voltage is restored.
The values that can be set are:
-
11.. 21 seconds (depending on physical address)
(default value)
-
5.. 9 seconds
-
11 seconds
-
13 seconds
-
15 seconds
-
17 seconds
-
19 seconds
-
21 seconds
-
no delay
Setting the values
11.. 21 seconds (depending on the physical address)
and
5.. 9 seconds
, the device
automatically calculates the transmission delay according to an algorithm that examines the physical
address of the device itself; the presented values (11/21 or 5/9) indicate the extremes of the value interval
that can be calculated.
Long operation
minimum time
Start of
pressing
detection
End of
pressing
detection
lon
g
o
p
e
ra
tion
Long operation
minimum time
Start of
pressing
detection
End of
pressing
detection
s
h
o
rt
o
p
e
ra
tion