USER INSTRUCTIONS
52
PROPORTIONAL CONTROL
At the end of each cycle time, the timer-thermostat
checks the ambient temperature and, according to the
differences recorded compared to the set point setting, it
modulates the activation or deactivation of the boiler
(PMW) or it sends a 1 byte command (continuous control)
to control the heating or cooling element, according to the
command selected by ETS (1 bit or 1 byte).
P06 - Setting the cycle time
When the P06 code appears on the screen, set the cycle
time using the
keys.
The values available are as follows:
5,10,20,30,40,50,60
minutes
. It is possible to set different cycle times for the
heating and air-conditioning functions.
Press the
key within 30 seconds to confirm the value
set.
P07 - Setting the proportional regulation differential
value
When the P07 code appears on the screen, set the
PMW regulation differential value using the
keys.
Possible values:
from 0.4 °C to 3.2 °C with a pitch of
0.4 °C.
It is possible to set different regulation differentials for the
heating and air-conditioning functions. Press the
key
within 30 seconds to confirm the value set.
If a 1 bit value has been selected as the control value
when configuring with ETS, move on to point P11,
otherwise move on to point P08.
P08 - Minimum percentage value to send the command
When the P08 code appears on the screen, set the
percentage resolution to send to the command to the
thermal regulation control device. The values available
are as follows:
5%, 10%, 20%.
Press the
key within 30 seconds to confirm the value
set.