30
USER INSTRUCTIONS
Setting the adjustment differential for speed 1
Use the
or
button key to set the value of the adjustment
differential of fan coil speed 1 (the gap can be set from 0°C to
2.0°C). If a value of 0°C is set, then when the solenoid valve is
activated fan coil speed 1 will be activated as well. To confirm
your choice and move on to the next parameter, press the
button key within 30 seconds.
Setting the adjustment differential for speed 2
Use the
or
button key to set the value of the adjustment
differential of fan coil speed 2 (the gap can be set from 0.1°C to
2.0°C). To confirm your choice and move on to the next parameter,
press the
button key within 30 seconds.
Setting the adjustment differential for speed 3
Use the
or
button key to set the value of the adjustment
differential of fan coil speed 3 (the gap can be set from 0.1°C to
2.0°C). To confirm your choice and move on to the next parameter,
press the
button key within 30 seconds.
Setting the inertia for speed 1
Use the
or
button key to set the value of the inertia time for
fan coil speed 1 (the gap can be set from 0 to 10 seconds). To
confirm your choice and move on to the next parameter, press the
button key within 30 seconds.
Setting the inertia for speed 2
Use the
or
button key to set the value of the inertia time for
fan coil speed 2 (the gap can be set from 0 to 10 seconds). To
confirm your choice and move on to the next parameter, press the
button key within 30 seconds.
Setting the inertia for speed 3
Use the
or
button key to set the value of the inertia time for
fan coil speed 3 (the gap can be set from 0 to 10 seconds). To
confirm your choice and move on to the next parameter, press the
button key within 30 seconds.
The setting of the timed thermostat parameters is now
complete. Press the
button key to return to normal
operation.