[EN]  CONTROL MODULES WITH HUMIDITY REGULATION

Function

Control modules with humidity regulation use a sensor 
to measure humidity. The humidity value is averaged 
over 24 hours and continuously adjusted. Every two 
seconds it is checked whether the moving average 
value is exceeded by at least 5% and whether the fan 
is started with partial load. If the value exceeds 10%, 
the fan starts at full load. After reaching the average 
values, the fan switches off or switches to base load.

Mounting

1.  Attach the control module and secure it with the 

two screws provided.

2.  The sensor must always be mounted in the corner, 

which is turned 90° counterclockwise to the air out-
let.  Make  a  hole  (Ø  10  mm)  in  the  filter  holder  at 
this point.

3.  Insert the sensor from below through the hole in the 

filter carrier and ensure a secure hold.

4.  Secure the sensor  cable  to  the filter  carrier  rib  so 

that the cable cannot touch the impeller.

5.  Now mount the filter carrier as described in the as-

sembly instructions for the exhaust fan and follow 
the further instructions.

Maintenance/Dismantling

Note that the sensor and sensor cable must be discon-
nected from the filter carrier before the filter carrier is 
removed.