TRS 5-52 - Installation & Operating Manual -
819175-05
In the system: Wiring temperature sensors
Connecting the temperature sensor
The TRS 5-52 temperature switch can be combined in a circuit with the TRG 5-63, TRG 5-64, TRG 5-65,
TRG 5-66, TRG 5-67 and TRG 5-68 temperature sensors.
To connect the equipment, please use a shielded, multi-core control cable with a minimum conductor
size of 0.5 mm
2
, e.g. LiYCY 3 x 0.5 mm
2
, maximum length 100 m.
The shield is applied
only
to the temperature sensor via the cable gland.
Attention
n
Please refer to the TRG 5-6x Installation & Operating Manual.
n
Route connecting cables to items of equipment separately from power lines.
Note
Alternatively, indicating devices can be connected to the terminals of the
TRG 5-64 and TRG 5-68, marked yellow and black above.
Fig. 12
Factory settings
Temperature switch TRS 5-52
The temperature switch is supplied with the following factory settings:
n
MAX switchpoint AL.Hi = 150 °C, reset hysteresis: – 5 K (fixed)
n
MIN switchpoint AL.Lo = 50 °C, reset hysteresis: + 5 K (fixed)
n
Current output Sout 20 mA = 200 °C
n
Password PW: oFF
Code switch:
All switches OFF
Wiring diagram for temperature sensors
Fig. 4
55
33
22
66
yellow
black
red
TRG 5-63, TRG 5-65,
TRG 5-66, TRG 5-67
TRG 5-64
TRG 5-68
black
TRS 5-..
TRS 5-..