28
NRS 1-50 For TWO electrodes - USA - Installation & Operating Manual -
850694-00
Fault indications and troubleshooting
Fault indication
Status
Diagnosis
Function
Next action
Error on evaluation of level
electrode 1, channel 1
Diagnostic LED 1 and
Alarm 1 LED light up
Output contacts open
without a delay.
Signal output 1 closes
without a delay.
Next:
Press
button 1
Error on evaluation of level
electrode 2, channel 2
Diagnostic LED 2 and
Alarm 2 LED light up
Output contacts open
without a delay.
Signal output 2 closes
without a delay.
Next:
Press
button 2
Error detected in level
switch
Diagnostic LED 3 and
Alarm 1 and 2 LEDs
light up
Output contacts open
without a delay.
Signal outputs 1 and 2 close
without a delay.
Next:
Press
button 1 or
button 2
Diagnosis
Indication 1 and action
Indication 2 Error
Corrective action
Alarm 1 LED and
diagnostic LED 1 light up.
Press and hold
button 1
Diagnostic
LED 1
flashes
Error in level electrode 1,
error in level switch,
wiring error,
measuring voltage error.
- Check wiring,
- measure electrode voltages,
- clean level electrode, replace
if necessary,
- replace level switch.
Diagnostic
LED 2
flashes
Error in level electrode 1,
error in level switch,
wiring error.
Diagnostic
LED 3
flashes
External voltage error, boiler
wall has no PE.
Provide shielding and grounding,
connect boiler to PE.
Alarm 2 LED and
diagnostic LED 2 light up,
press and hold
button 2
Diagnostic
LED 1
flashes
Error in level electrode 2,
error in level switch,
wiring error,
measuring voltage error.
- Check wiring,
- measure electrode voltages,
- clean level electrode, replace
if necessary,
- replace level switch.
Diagnostic
LED 2
flashes
Error in level electrode 2,
error in level switch,
wiring error.
Diagnostic
LED 3
flashes
External voltage error, boiler
wall has no PE.
Provide shielding and grounding,
connect boiler to PE.
Alarm 1 and 2 LEDs and
diagnostic LED 3 light up,
press and hold
button 1
or 2
Diagnostic
LED 1
flashes
Processor error, standby
error.
Replace level switch.
Diagnostic
LED 2
flashes
Internal voltage error.
Replace level switch.
Diagnostic
LED 3
flashes
Relay error.
Once the error has been rectified, the level switch reverts to normal operation.
After troubleshooting, please switch the mains supply off and on again after approx. 5 s.
Indications, diagnosis and corrective action