4.  Technical Specifications 

 

24V / 25A 

110V / 25A 

Input Voltage 

230 V

AC

 or 120 V

AC

 

(±%20) 

230 V

AC

 or 120 V

AC

 

(±%20) 

Input Frequency 

50 or 60 Hz (±%5) 

50 or 60 Hz (±%5) 

Input Current 

5.25 A

max

 

27 A

max

 

Power Factor 

0.82 

0.66 

Output 

Voltage 

Nominal 

27.6 V

DC

 

124 V

DC

 

Range 

20.0 

– 30.0 V

DC

 

90 

– 130 V

DC

 

DC Source Mode 

20.0 

– 30.0 V

DC

 

90 

– 130 V

DC

 

Output 

Current 

Nominal 

I

n

 

I

n

 

Range 

1.0 - I

n

 

1.0 - I

n

 

DC Source Mode 

– 1.5 I

– 1.5 I

n

 

Output Power 

700 W 

3200 W 

Output Ripple 

<5% (w/o battery) 

<5% (w/o battery) 

Output Filtering 

L-C Filter 

L-C Filter 

Efficiency 

≤%75 

≤%81 

Mini Circuit Breaker 

Single or Double Pole, I

CN

=10kA, C-Type 

Double Pole, I

CN

=10kA, C-Type 

Cooling Method 

Fan forced (AF) 

Operating Temperature 

(-20) 

– (+55) °C 

Relative Humidity 

< % 95 RH (without condensation) 

Pollution Degree 

III 

Alarm Contacts 

14 NO mechanical contact, 3A/30V

DC

 or 5A/250V

AC

, 1385 VA / 90 W 

1 NC mechanical contact, 5A/30V

DC

 or 10A/250V

AC

, 2500 VA / 150 W 

750 V

RMS

 breakdown between open contacts 

RS-485 Port 

2 wire, isolated 

Insulation 

Independent 

Circuits 

AC Input 

– DC Output – Earth – Alarm Contacts – RS-485 

Dielectric 

Withstand 

2 kV

AC

 / 50 Hz, 1 min (all independent circuits, including SELV circuits) 

Reference Standard(s) 

IEC 60146-1-1 

 

5.  Order Code 

ARG 

– 24 25 SD 26

 

Battery Capacity

: 18 … 150 Ah 

Optional Features 
• S – Alarm Contact Outputs 
• H – RS-485 Communication 
• D – Deep-Discharge Protection 
• V – AC Surge Protective Device 
• P – Parallel ORing Diode 
 

Output Current

: 5 … 40 A 

Output Voltage: 24 / 48 / 110 V 

Summary of Contents for ARG-110 Series

Page 1: ...GEPA ARG Series Battery Charger with Battery Group User Guide...

Page 2: ...er or sales company is not responsible of faults if user doesn t obey recommendations at the above This is a Class A product In a domestic environment this product may cause radio interference in whic...

Page 3: ...age Supervising 4 2 6 DC Source Mode 4 2 7 Autonomous Battery Maintenance 4 2 7 1 TEDA Turkish Electricity Distribution Authority Method 4 2 7 2 Equalize Timer Mode Method 4 2 8 Surge Protective Devic...

Page 4: ...battery group capacity Wide input voltage tolerance Floating or equalizing charge Independent and adjustable battery charge and total system current output Electronic short circuit protection at DC o...

Page 5: ...al temperature controlled fan Fan is supplied from AC input and controlled by microcontroller according to digital temperature sensor measurement Operating temperature is adjustable 2 2 Battery Chargi...

Page 6: ...ing to Peukert s law This device is intended to use with AGM or gel VRLA batteries so coefficient is 1 1 Overload will trigger if total current output is limited at maximum current for 1 hour Over tem...

Page 7: ...ntenance Battery group should be checked periodically in order to ensure batteries are available to service The device has two different autonomous battery maintenance methods 2 7 1 TEDA Turkish Elect...

Page 8: ...panel Contact terminals are accessible from front side and isolated from other circuits Following alarms are available AC MCB switch off DC low Replace battery DC or battery MCB switch off DC high Ov...

Page 9: ...et Side entry which is next to MCBs and alarm module is easier to access If bottom entry is preferred oIn models with drawers there are no obstacles between terminals and entry or use cable spiral wra...

Page 10: ...re given at the below MCB In varies according to input and output current Schema 1 Power connections of 24V with multiple DC outputs Schema 2 Power connections of 110V and 24V Schema 3 Alarm module co...

Page 11: ...shown with LEDs Charging mode LED is on and steady if floating or flashing if equalizing charge mode is active AC High Low and DC High Low LEDs are on and steady if over or flashing if under preset va...

Page 12: ...Press SET again to adjust any parameter on the screen After pressing SET cursor will be move onto U parameter 3 Use UP and DOWN buttons to adjust the parameter To cancel press ESC Press SET to move o...

Page 13: ...ter Description Range Step Default Duration Duration of equalizing charge 1 9 hrs 1 hr 1 hr Status Status of equalizing charge mode Active Passive Passive DC Source Mode Parameter Description Range St...

Page 14: ...ge Step Default Annual Battery Maintenance Quantity This parameter determines how many times this method will be applied 1 6 1 4 Maintenance Voltage Minimum battery voltage to stop discharge 21 24 V f...

Page 15: ...10kA C Type Cooling Method Fan forced AF Operating Temperature 20 55 C Relative Humidity 95 RH without condensation Pollution Degree III Alarm Contacts 14 NO mechanical contact 3A 30VDC or 5A 250VAC...

Page 16: ...GEPA Elektronik San ve Tic Ltd ti Zubeyde Hanim Dist Sebzebahceleri St No 93 36 Iskitler 06070 Altindag Ankara Turkey Tel 90 312 341 4104 Fax 90 312 384 0436 www gepaelk com gepa gepaelk com Rev 4 04...

Reviews: