25
Single Panel Applications
Basic Pump Control
If you have a single ORS SITEPRO™ panel that is being used strictly as a blower/water pump controller and has no
external interlock or network connections, no system configuration is required. Proceed directly to Chapter 4 for startup
and operation instructions.
Configuring for Interlocks
If you are using a single ORS SITEPRO™ panel with external interlock devices, the panel must be configured to receive
the sensor input and react appropriately. This is accomplished by setting the RECEIVE and LOGIC dip switches as
detailed in the flowcharts in figures 18 and 19.
Set RECEIVE Switches
Set the RECEIVE switches according to the flowchart figure 18.
The four dip switches on the RECEIVE switch are numbered 5-8 and coincide with
alarm channels
1-4, respectively.
The switches also coincide with
interlock
input terminals 1-4 on terminal strips TB2 and TB3. See figures 8 and 16 for
terminal and switch numbering. For example, if an external
interlock
device is wired to terminals 1 and 5 (common) on
connector TB3, turn RECEIVE dip switch 5 to the ON position as shown below.