Electrical Data cont.
CAUTION: When installing a unit with an variable speed ECM blower motor in 460/60/3 voltage, a neutral wire is required to allow proper
unit operation.
Variable Speed ECM Motor
Model
Rated
Voltage
Voltage
Min/Max
Compressor
Blower
Motor
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR Breaker
MCC
RLA
LRA
015
208-230/60/1
187/253
9.2
5.9
29.0
4.0
9.9
11.4
15
265/60/1
238/292
7.8
5.0
28.0
4.1
9.1
10.3
15
018
208-230/60/1
187/253
10.4
6.7
33.5
4.0
10.7
12.4
15
265/60/1
238/292
8.7
5.6
28.0
4.1
9.7
11.1
15
024
208-230/60/1
187/253
13.0
7.4
43.0
4.0
11.4
13.3
20
265/60/1
238/292
12.6
6.7
46.0
4.1
10.8
12.5
20
208-230/60/3
187/253
13.0
5.9
63.0
4.0
9.9
11.4
15
460/60/3
414/506
6.0
2.9
30.0
4.1
7.0
7.7
10/15
030
208-230/60/1
187/253
17.5
9.4
54.0
4.0
13.4
15.8
25
265/60/1
238/292
14.0
8.0
46.0
4.1
12.1
14.1
20
208-230/60/3
187/253
13.5
6.6
63.0
4.0
10.6
12.3
20
460/60/3
414/506
6.4
3.2
30.0
4.1
7.3
8.1
10/15
036
208-230/60/1
187/253
20.5
11.6
74.0
4.0
15.6
18.5
30
265/60/1
238/292
17.7
9.9
67.0
4.1
14.0
16.5
25
208-230/60/3
187/253
13.5
7.4
68.0
4.0
11.4
13.3
20
460/60/3
414/506
7.1
3.8
34.0
4.1
7.9
8.9
15
041
208-230/60/1
187/253
25.0
13.0
88.0
4.0
17.0
20.3
35
208-230/60/3
187/253
14.5
8.6
68.0
4.0
12.6
14.8
25
460/60/3
414/506
7.7
4.2
34.0
4.1
8.3
9.4
15
042
208-230/60/1
187/253
25.0
13.0
88.0
4.0
17.0
20.3
35
208-230/60/3
187/253
14.5
8.6
68.0
4.0
12.6
14.8
25
460/60/3
414/506
7.7
4.2
34.0
4.1
8.3
9.4
15
048
208-230/60/1
187/253
24.5
15.7
84.0
4.0
19.7
23.6
40
208-230/60/3
187/253
17.5
11.0
88.0
4.0
15.0
17.8
30
460/60/3
414/506
8.0
5.6
44.0
4.1
9.7
11.1
15
060
208-230/60/1
187/253
33.0
21.1
105.0
7.0
28.1
33.4
55
208-230/60/3
187/253
22.0
12.9
88.0
7.0
19.9
23.1
35
460/60/3
414/506
12.0
6.7
55.0
6.9
13.6
15.3
25
070
208-230/60/1
187/253
36.0
23.0
130.0
7.0
30.0
35.8
60
208-230/60/3
187/253
24.6
14.3
110.0
7.0
21.3
24.9
40
460/60/3
414/506
11.5
7.1
55.0
6.9
14.0
15.8
25
HACR circuit breaker in USA only 10/15/15