GeoSmart Premium G Installation Information Download Page 23

23

Blower Performance Data cont.

L

G

N

C

High Voltage
Connections

3/16 in. 

1

2

3

4

5

G - Blue

Y1 - Red

AUX - Gray

C - Black

L - Orange
G - Green

N - Brown

Low Voltage

Connections 1/4 in. 

L

G

N

C

1

2

3

4

5

AUX - Gray

G - Blue

Y1 - Red

Y2 - Tan

C - Black

L - Orange
G - Green

N - Brown

High Voltage
Connections

3/16 in. 

Low Voltage

Connections 1/4 in. 

CAUTION: Disconnect all power before 
performing this operation.

Setting Blower Speed - 5-Speed ECM

5-speed ECM blower motors have fi ve (5) speeds of which three (3) are 
selectable on single speed and four (4) are selectable on dual capacity.

5-Speed ECM Motor Connections - Single Speed

5-Speed ECM Motor Connections - Dual Capacity

5-Speed ECM - Dual Capacity

Model

Motor 

Speed

Motor 

Tap

T’stat

Cnct.

Blower 

Size

Motor 

HP

Airfl ow (cfm) at External Static Pressure (in. wg)

0

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

0.50

0.60

0.70

0.80

0.90

1.00

026

High

5

W

9 x 7

1/2

1120

1109

1097

1082

1066

1055

1044

1028

1011

1001

991

932

839

-

-

-

Med High

4

Y2

1020

1006

991

980

968

950

932

922

911

894

876

849

812

-

-

-

Med

3

917

906

895

884

872

854

836

824

812

792

772

754

719

-

-

-

Med Low

2

Y1

836

824

812

794

776

765

754

735

715

703

691

653

631

-

-

-

Low

1

G

735

721

707

687

666

653

640

622

603

589

574

533

-

-

-

-

038

High

5

W

11 x 10

1/2

1530

1503

1476

1453

1429

1413

1397

1376

1355

1342

1329

1276

1231

1173

-

-

Med High

4

Y2

1413

1388

1363

1342

1321

1303

1285

1263

1240

1226

1212

1173

1016

946

-

-

Med

3

Y1

1355

1325

1294

1276

1258

1235

1212

1188

1164

1144

1123

982

909

883

-

-

Med Low

2

1336

1299

1261

1242

1222

1202

1181

1157

1132

1111

1090

937

874

830

-

-

Low

1

G

1243

1182

1121

1061

1000

964

928

856

784

744

703

647

592

-

-

049

High

5

W

11 x 10

1

1934

1910

1886

1871

1855

1827

1799

1780

1760

1747

1734

1700

1659

1617

-

-

Med High

4

1799

1783

1767

1744

1720

1693

1666

1649

1631

1617

1603

1560

1530

1492

-

-

Med

3

Y2

1694

1680

1666

1642

1617

1592

1567

1552

1537

1519

1500

1453

1421

1372

-

-

Med Low

2

Y1

1575

1560

1540

1520

1502

1487

1471

1448

1424

1409

1393

1351

1308

1266

-

-

Low

1

G

1454

1406

1358

1333

1308

1285

1261

1239

1217

1198

1179

1072

1002

988

-

-

064

High

5

W

11 x 10

1

2245

2360

2214

2315

2173

2290

2136

2275

2103

2250

2070

2032

1998

1957

1910

1825

Med High

4

Y2

2092

2073

2054

2035

2015

1995

1975

1958

1940

1922

1904

1880

1843

1806

1767

1728

Med

3

 1951

1931

1910

1889

1868

1850

1831

1812

1793

1774

1755

1722

1688

1654

1612

1562

Med Low

2

Y1

1812

1796

1780

1761

1741

1718

1695

1682

1668

1651

1633

1591

1555

1518

1480

1433

Low

1

G 1682

1661

1640

1616

1591

1573

1555

1533

1510

1495

1480

1441

1400

1351

1316

1263

072

High

5

W

11 x 10

1

2472

2360

2435

2315

2393

2290

2349

2275

2306

2250

2271

2236

2189

2121

2033

1936

Med High

4

Y2

2271

2248

2225

2205

2184

2166

2147

2129

2110

2094

2078

2039

2011

1977

1930

1846

Med

3

2133

2115

2096

2072

2047

2030

2013

1996

1979

1965

1950

1909

1873

1837

1793

1748

Med Low

2

Y1

2008

1985

1962

1939

1915

1898

1880

1862

1843

1828

1812

1774

1742

1703

1669

1635

Low

1

G

1806

1784

1761

1742

1722

1696

1669

1656

1642

1625

1607

1564

1527

1490

1443

1404

Factory speed settings are in Bold

Air fl ow values are with dry coil and standard fi lter
For wet coil performance fi rst calculate the face velocity of the air coil (Face Velocity [fpm] = Airfl ow [cfm] / Face Area [sq ft]).  
Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, 400 fpm by 0.12in. wg., and 500 fpm by 0.16 in. wg.
Highest setting is for auxiliary heat (W) and lowest setting is for constant blower (G).  The “Y1” and “Y2” settings must be between the “G” and “W” settings.

3/16/12

 

PREMIUM G COMPACT INSTALLATION MANUAL

Summary of Contents for Premium G

Page 1: ...L Installation Information Water Piping Connections Electrical Startup Procedures Troubleshooting Preventative Maintenance Premium Compact Forced Air Geothermal Comfort System Geothermal Heat Pumps R...

Page 2: ......

Page 3: ...r Connections 15 Freeze Detection 17 Electrical Connections 17 Electrical Data 18 Blower Performance Data 21 Wiring Schematics 26 Controls 28 Unit Startup 32 Operating Limits 33 Operating Parameters 3...

Page 4: ...072 Water Coil Option C Copper D Insulated Copper N CuproNickel P Insulated CuproNickel Vintage Factory Use Only Non Standard Options SS Standard Drain Pan Option 0 Composite No Secondary Connection...

Page 5: ...ving the units from the packaging if necessary Units in question should also be internally inspected If any damage is noted the carrier should make the proper notation on the delivery receipt acknowle...

Page 6: ...pen return applications Deluxe filter rack for ductable return applications 2 61 cm Service Access Left Return Right Return opposite side 2 61 cm Alternate Service Access Field installed duct flange A...

Page 7: ...lter rack 0 10 in M N P Q R S T U V W Filter Rack Width Supply Width Supply Depth Return Depth Return Height 009 012 in 2 2 10 0 10 0 6 1 5 3 9 8 2 0 18 1 14 0 2 0 cm 5 6 25 4 25 4 15 5 13 5 24 9 5 1...

Page 8: ...AIR COIL SIDE 0 5 in 1 3 cm knockout 1 in 2 5 cm knockout 1 in 2 5 cm knockout 0 5 in 1 3 cm knockout BP BP FILTER RACK FILTER RACK Standard filter rails Standard filter rails Deluxe filter rack opti...

Page 9: ...Supply Depth Return Depth Return Height 009 012 in 5 9 7 2 9 5 6 0 16 4 14 5 2 0 1 4 3 4 cm 15 0 18 3 24 1 15 2 41 7 36 8 5 1 3 6 1 9 015 018 in 6 7 10 5 9 4 4 9 27 4 16 6 2 0 1 4 3 4 cm 17 0 26 7 23...

Page 10: ...ow filter access install hanger brackets as illustrated in the Hanger Bracket Locations section The unit should be pitched approximately 1 4 in towards the drain in both directions to facilitate the r...

Page 11: ...99S500A04 45 8 25 1 21 4 n a cm 116 3 63 8 54 4 n a 038 in 99S500A03 48 8 28 1 24 4 n a cm 124 0 71 4 62 0 n a 049 in 99S500A04 53 8 28 1 24 4 n a cm 136 7 71 4 62 0 n a 064 in 99S500A04 61 8 28 1 24...

Page 12: ...ure proper flow use pressure temperature ports to determine the flow rate These ports should be located at the supply and return water connections on the unit The proper flow rate cannot be accurately...

Page 13: ...deposition will occur Erosion Suspended Solids Less than 10 ppm and filtered for max of 600 micron size Less than 10 ppm and filtered for max of 600 micron size Less than 10 ppm and filtered for max o...

Page 14: ...alkaline pH 7 5 to 8 5 The specified percentage of antifreeze may also be added at this time Use commercial grade antifreeze designed for HVAC systems only Environol brand antifreeze is recommended On...

Page 15: ...the water heater tank 4 Drain the tank by opening the valve on the bottom of the tank then open the pressure relief valve or hot water faucet 5 Flush the tank by opening the cold water inlet valve to...

Page 16: ...t the temperature setting on the tank On tanks with both upper and lower elements the lower element should be turned down to the lowest setting approximately 100 F The upper element should be adjusted...

Page 17: ...rdance with local codes or the National Electric Code whichever is applicable Power Connection Connect the incoming line voltage wires to L1 and L2 of the con tactor for single phase unit Consult the...

Page 18: ...208 230 60 3 187 253 13 9 8 9 58 0 34 8 2 8 11 7 13 9 20 460 60 3 414 506 6 5 4 2 28 0 16 8 1 4 5 6 6 7 10 15 036 208 230 60 1 187 253 22 0 14 1 73 0 29 2 3 5 17 6 21 1 35 265 60 1 238 292 17 5 11 2...

Page 19: ...21 2 13 6 83 1 49 9 7 6 21 2 24 6 35 460 60 3 414 506 9 5 6 1 41 0 24 6 4 0 10 1 11 6 15 060 208 230 60 1 187 253 41 2 26 4 134 0 53 6 7 6 34 0 40 6 60 208 230 60 3 187 253 24 9 16 0 110 0 66 0 7 6 2...

Page 20: ...0 30 460 60 3 414 506 9 5 6 1 41 0 24 6 4 1 10 2 11 7 15 048 208 230 60 1 187 253 31 0 19 9 109 0 43 6 7 0 26 9 31 9 50 208 230 60 3 187 253 21 2 13 6 83 1 49 9 7 0 20 6 24 0 35 460 60 3 414 506 9 5...

Page 21: ...2140 2095 2045 1945 1835 1715 1510 1330 M 2265 2235 2205 2175 2145 2110 2070 2035 2000 1960 1915 1825 1730 1605 1440 1260 L 2075 2050 2020 1995 1965 1940 1915 1885 1850 1820 1785 1720 1610 1505 1335 1...

Page 22: ...520 495 455 420 400 030 High 5 9 x 7 1 2 1407 1381 1354 1327 1300 1267 1233 1201 1168 1131 1094 1009 Med High 4 W 1146 1134 1122 1111 1099 1085 1071 1062 1052 1042 1031 966 Med 3 Y1 1023 1012 1001 98...

Page 23: ...9 1780 1760 1747 1734 1700 1659 1617 Med High 4 1799 1783 1767 1744 1720 1693 1666 1649 1631 1617 1603 1560 1530 1492 Med 3 Y2 1694 1680 1666 1642 1617 1592 1567 1552 1537 1519 1500 1453 1421 1372 Med...

Page 24: ...100 1300 1500 1750 1950 2100 2300 L M H 070 0 75 11 x 10 1 800 950 1100 1300 1500 1750 1950 2100 2300 L M H 3 16 12 Dual Capacity Model Max ESP Blower Size Motor hp Air Flow DIP Switch Settings 1 2 3...

Page 25: ...een displays the current variable speed ECM settings It allows the technician to enter the setup screens to change the variable speed ECM settings Change the highlighted item using the and buttons and...

Page 26: ...lower Off Delay Fault Recognition Delay High Pressure Start Up Bypass Low Pressure Fault Recognition Delay Low Pressure Start Up Bypass Low Water Air Coil Limit Fault Recognition Delay Low Water Air C...

Page 27: ...stalled 5 Wire is provided with the unit but only connected to the X13 motor on dual capacity units Notes Accessory Relay Cycle with Blower Cycle with Compressor Water Valve Slow Open Outdoor Air Damp...

Page 28: ...ne time Test mode will automatically time out after 30 minutes Test mode can be exited by pressing and holding the SW1 button for 2 to 5 seconds or by cycling the power NOTE Test mode will automatical...

Page 29: ...d shall flash the fault code To reset lockout conditions with SW2 8 On thermostat inputs Y1 Y2 and W must be removed for at least 3 seconds To reset lockout conditions with SW2 8 Off thermostat inputs...

Page 30: ...command is removed Regardless of blower input G from the thermostat the blower will remain on for 30 seconds at the end of each heating cycle Cooling Operation In all cooling operations the reversing...

Page 31: ...plugs into the exterior of the cabinet in the AID Tool port ABC Control Board Layout Aurora Base Control LED Displays These three LEDs display the status configuration and fault codes for the control...

Page 32: ...ure drop through the heat exchanger using the P T plugs and comparing to the pressure drop table 6 Check the temperature of both the supply and discharge water Refer to Operating Parameters tables 7 C...

Page 33: ...psig Discharge Pres sure psig Superheat Subcooling Water Temp Rise F Air Temp Drop F DB 30 1 5 115 125 150 170 20 35 10 17 17 22 17 23 3 0 105 120 130 145 20 35 10 17 8 10 17 23 50 1 5 130 140 215 235...

Page 34: ...eratures of 80 F DB 67 F WB Heating performance based on entering air temperature of 70 F DB 2 15 12 Second Stage Operation Entering Water Temp F Water Flow gpm ton Cooling No Hot Water Generation Suc...

Page 35: ...5 3 3 11 0 17 2 0 41 14 0 7 6 6 7 6 3 5 8 5 4 14 0 17 9 0 61 048 6 0 1 1 1 0 1 0 0 9 0 8 1 in 6 0 16 1 0 14 9 0 2 3 2 1 2 0 1 9 1 7 9 0 16 8 0 29 12 0 3 9 3 7 3 4 3 2 3 0 12 0 17 4 0 47 16 0 6 7 6 3 5...

Page 36: ...alves Low High Low High Normal High Low Low TXV Bulb Loss of Charge Low Low Low High High Low Low Scaled Coaxial Heat Exchanger Heating Low Low Low Normal Low High Low Low Scaled Coaxial Heat Exchange...

Page 37: ...a 0 96 1 10 3 88 4 46 5 88 6 76 060 0 42 0 48 0 73 0 85 n a 0 63 0 73 2 98 3 42 4 96 5 70 070 0 33 0 39 0 90 1 04 n a 0 56 0 64 2 34 2 70 3 48 4 00 Dual Capacity 026 1 21 1 39 1 52 1 75 1 38 1 58 2 0...

Page 38: ...5 83 0 15 0 37 9 53 7 69 8 82 9 83 4 91 2 89 4 82 7 76 8 18 0 38 1 54 3 70 9 84 8 83 8 91 9 90 3 83 6 77 6 3 16 12 Dual Capacity Model gpm Heat of Extraction HE MBtu h Heat of Rejection HR MBtu h 30...

Page 39: ...ration is noisy 1 Check compressor for loosened mounting bolts Make sure compressor is floating free on its isolator mounts Check for tubing contact with the compressor or other surfaces Readjust it b...

Page 40: ..._ AMPS n ______ AMPS Watts m x n x 0 85 o _____ WATTS o ______ WATTS 6 CAPACITY Cooling Capacity HR o x 3 413 p _____ btu hr Heating Capacity HE o x 3 413 p _____ btu hr 7 EFFICIENCY Cooling EER p o q...

Page 41: ...tage Loop Open Unit Amp Draw Closed COAX SOURCE HEA7 1 ANALYSIS EXPANSION VALVE F AIR COIL F COMPRESSOR DISCHARGE SUCTION Subcooling Superheat REVERSING VALVE PSI F SAT F PSI SAT F F F LIQUID LINE Lin...

Page 42: ...te Drain In areas where airborne bacteria produce a slime in the drain pan it may be necessary to treat chemically to minimize the problem The condensate drain can pick up lint and dirt especially wit...

Page 43: ...Available 5 Speed ECM Motor Blower 5 Spd ECM Motor 208 230 60 1 Not Available 14P536 01 14P537 01 5 Spd ECM Motor 265 60 1 Not Available 14P536 02 14P537 02 5 Spd ECM Motor 230 60 3 Not Available 14P5...

Page 44: ...02 14S553 02 Not Available 5 Speed ECM Motor Blower 5 Spd ECM Motor 208 230 60 1 Not Available 14P536 01 14P537 01 5 Spd ECM Motor 265 60 1 Not Available 14P536 02 14P537 02 5 Spd ECM Motor 230 60 3...

Page 45: ...le Not Available 14S553 01 14S553 01 Not Available High Static VS ECM Motor 460 60 3 Not Available 14S553 02 14S553 02 Not Available Not Available 14S553 02 14S553 02 Not Available 5 Speed ECM Motor B...

Page 46: ...46 Notes PREMIUM G COMPACT INSTALLATION MANUAL...

Page 47: ...47 Revision Guide PREMIUM G COMPACT INSTALLATION MANUAL Pages Description Date By All Updated with All Aluminum Air Coils 19 May 2014 DS All First Published 13 Sept 2013 DS...

Page 48: ...tem Size 75 6 Ton Single Stage 2 6 Ton Two Stage Document Type Installation Manual Ref Number IM1022AG2 Revision Date 05 14 Revision Number Document Name TEC IOM GB 0514v1 650 Jamieson Parkway Unit 1...

Reviews: