3.3. Analog 4 – 20 mA Output
Analog current 4 – 20 mA output is provided for easier compatibility with older logging and
control systems. Output is implemented as current sink architecture with common ground.
Maximal voltage applied to the sink can go up to 30 VDC, providing greater flexibility in
connections of the sensor to PLCs, loggers, or data concentrators.
Signal range and function for 4 – 20 mA analog output can be configured in the setup
application so the sensor will be able to signal best suitable value range with available current
range. Current step in the sensor is 0.3 µA, which limits the resolution, so care has to be taken
while setting the minimal value to be represented by 4 mA and the maximal value to be
represented by 20 mA so the resolution is sufficient for the system requirements.
Picture 3. Analog 4 – 20 mA Output Internal Architecture
Picture 4. High Side Current Measurement for the 4 – 20 mA Analog Output
Measurement of the current by the client device (logger, PLC, modem etc.) must be
implemented as the high side current measurement as shown on the picture 4. If sensing
resistor is used resistance should be selected from the range 10Ω to 500Ω with recommended
value 100Ω for the sensing resistor.