When installing GENVEX 315, 420, 525,
630 & 840 follow these instructions:
1) Adjust the machine in plumb.
2) Install an airtight water trap on a non-freezing
location, to compensate for fan pressure.
3) The water trap hight must be at least 100
mm.
4) Make sure that the drain flows downwards all
the way from the unit.
5) Poor some water into the driptray in the unit
to verify that it is drained properly.
6) If freezing of the water trap may occur, it is
necessary to install a thermostat and electri-
cal heater to prevent freezing, when the tem-
perature drops below +2C°.
.
IMPORTANT
.
IMPORTANT
.
IMPORTANT
.
IMPORTANT
.
IMPORTANT
.
.
IMPORTANT
.
IMPORTANT
.
IMPORTANT
.
IMPORTANT
.
IMPORTANT
.
100 mm
Extract air
Fresh air
Supply air
Exhaust air
7
For inside outlet
Siphon
Airtight connection
Airtight connection
7) Airflow adjustments must be made on both
supply and exhaust sides prior to normal use
of the machine. It is important to have a ba-
lance between supply and exhaust air volu-
mes
8) It is recommended to keep the ducts closed
until the unit is adjusted and used.
This instruction must be followed. If the drain is
not made according to this instruction, GENVEX
A/S can not be made responsible for any additio-
nal damages, which have nothing to do with the
GENVEX unit.
- Subject to Technical Modifications -