550-0490
Page 3
V. MOUNTING ROUGH-IN BOX AND RUN WIRING
MOUNTING - SPEAKER
TO GBLP BACK BOX
WALL OR CEILING MOUNT
MOUNTING - SPEAKER/STROBE
To 4” Square x 2 1/8” Deep
METALLIC BACK BOX - CEILING MOUNT
SSPKCLP FIELD SELECTABLE CANDELA SELECTOR
Adjust intensity by inserting small flat blade
screwdriver to turn dial. Displayed number will
indicate selected candela.
NOTICE:
FIELD SELECTABLE OPTIONS OF 15, 30,
75, 95 AND 115 CANDELA.
Adjust power taps using
needle nose pliers.
NOTICE:
DO NOT USE LOOPED
WIRE UNDER TERMINALS.
BREAK WIRE RUN TO PROVIDE
SUPERVISION OF CONNECTION
.
PANEL VOLTAGE - DEVICE MINIMUM VOLTAGE
TOTAL CURRENT DRAW
* INCLUDES WIRE TO AND FROM APPLIANCE.
ASSUMES ALL APPLIANCES ARE AT THE END OF WIRE RUN (WORST CASE).
CAUTION:
APPLIES ONLY TO REGULATED SUPPLIES.
*MAX. WIRE DISTANCE (IN FEET) =
X WIRE CONDUCTIVITY
(STROBE ONLY)
NOTICE
: ALL STROBES ARE DESIGNED TO FLASH AS SPECIFIED WITH CONTINUOUS APPLIED VOLTAGE. THIS APPLIANCE IS NOT RECOMMENDED FOR USE ON CODED OR
PULSING SIGNALING CIRCUITS. HOWEVER, USE OF THE AVSM CONTROL MODULE IS PERMITTED TO SYNCHRONIZE THE STROBE.
NOTICE:
REFERENCE AVSM CONTROL MODULE MANUAL (550-0284, DATED 2-1-03) FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS. AVSM MANUAL CAN BE OBTAINED AT