background image

550-0490

Page 3

V. MOUNTING ROUGH-IN BOX AND RUN WIRING

MOUNTING - SPEAKER

TO GBLP BACK BOX

WALL OR CEILING MOUNT

MOUNTING - SPEAKER/STROBE

To 4” Square x 2 1/8” Deep

METALLIC BACK BOX - CEILING MOUNT

SSPKCLP FIELD SELECTABLE CANDELA SELECTOR

Adjust intensity by inserting small flat blade

screwdriver to turn dial. Displayed number will

indicate selected candela.

NOTICE:

FIELD SELECTABLE OPTIONS OF 15, 30,

75, 95 AND 115 CANDELA.

Adjust power taps using

needle nose pliers.

NOTICE:

DO NOT USE LOOPED

WIRE UNDER TERMINALS.

BREAK WIRE RUN TO PROVIDE

SUPERVISION OF CONNECTION

.

PANEL VOLTAGE - DEVICE MINIMUM VOLTAGE

TOTAL CURRENT DRAW

* INCLUDES WIRE TO AND FROM APPLIANCE.

ASSUMES ALL APPLIANCES ARE AT THE END OF WIRE RUN (WORST CASE).

CAUTION:

APPLIES ONLY TO REGULATED SUPPLIES.

*MAX. WIRE DISTANCE (IN FEET) =

X WIRE CONDUCTIVITY

(STROBE ONLY)

NOTICE

: ALL STROBES ARE DESIGNED TO FLASH AS SPECIFIED WITH CONTINUOUS APPLIED VOLTAGE. THIS APPLIANCE IS NOT RECOMMENDED FOR USE ON CODED OR

PULSING SIGNALING CIRCUITS. HOWEVER, USE OF THE AVSM CONTROL MODULE IS PERMITTED TO SYNCHRONIZE THE STROBE.

NOTICE:

REFERENCE AVSM CONTROL MODULE MANUAL (550-0284, DATED 2-1-03) FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS. AVSM MANUAL CAN BE OBTAINED AT

HTTP://WWW.GENTEX.COM OR CALL GENTEX CORPORATION AT 1-800-436-8391.

Summary of Contents for SSPKCLP series

Page 1: ...atts for either 25v or 70 7v audio amplifiers The SSPK24CLP speaker strobe offers the option of a high intensity strobe which complies with ANSI UL 1971 The SSPKR24 speaker strobe offers the option of a high intensity strobe which complies with ANSI UL 1638 The frequency range of the speakers is 400 4000Hz All devices are suitable for line supervision Speaker includes DC blocking capacitor which a...

Page 2: ... with SSPKR24C Products Candela Regulated 24VDC Max Operating Current mA Regulated 24VFWR Max Operating Current mA 15 128 220 30 128 220 75 225 306 95 235 402 115 341 444 The visual signal must be in the direct viewing area of the occupant in order to be seen Strobe light can not be seen when objects such as doors furniture or walls block strobe light NOTICE VISUAL SIGNALS FOR THE HEARING IMPAIRED...

Page 3: ...E SUPERVISION OF CONNECTION PANEL VOLTAGE DEVICE MINIMUM VOLTAGE TOTAL CURRENT DRAW INCLUDES WIRE TO AND FROM APPLIANCE ASSUMES ALL APPLIANCES ARE AT THE END OF WIRE RUN WORST CASE CAUTION APPLIES ONLY TO REGULATED SUPPLIES MAX WIRE DISTANCE IN FEET X WIRE CONDUCTIVITY STROBE ONLY NOTICE ALL STROBES ARE DESIGNED TO FLASH AS SPECIFIED WITH CONTINUOUS APPLIED VOLTAGE THIS APPLIANCE IS NOT RECOMMENDE...

Page 4: ...ecome inoperable within the warranty period you must return the appliance to Gentex postage prepaid You must prove to the satisfaction of Gentex the date of purchase of your appliance Warranty service may only be performed by Gentex personnel at Gentex s facilities in Zeeland Michigan You must also pack the appliance to minimize the risk of it being damaged in transit You must also enclose a retur...

Reviews: