background image

550-0490

Page 2

SSPKR24C PRODUCT INFORMATION

Model

Color Lens

SSPKR24C

Red

SYSTEM CONSIDERATIONS

1. To select the proper wattage input for the speaker, move the jumper to the appropriate pin.

2. Always maintain electrical isolation between speaker and strobe wiring on combination units.

3. Do not exceed 130% of rated speaker voltage. If excessive distortion is heard, check amplifier for signal clipping. If clipping exists, reduce either amplifier input or gain.

4. Four screws are provided, two for securing speaker to the back box and two for aesthetics. The two non-functional screws will be held in place by the pressure fit of the

faceplate.

IV. ELECTRICAL SPECIFICATIONS

NOTICE:

DC VOLTAGE RANGE LIMITS: 16-33V. FWR VOLTAGE RANGE LIMITS: 16-33V. THIS PRODUCT WAS ONLY TESTED TO THE STATED VOLTAGE RANGE(S);

DO NOT APPLY 80% AND 110% OF THIS RANGE FOR SYSTEM OPERATION.

CLEAR Lens Strobe Current Ratings

Use with SSPK24CLP Products

Candela

Regulated 24VDC

Max. Operating

Current (mA)

Regulated 24VFWR

Max. Operating

Current (mA)

15

120

190

30

120

191

75

200

277

95

220

298

115

290

418

Field Selectable Power Tap Selection

Voltage

1/8 Watt

1/4 Watt

1/2 Watt

1 Watt

2 Watt

4 Watt

25 Volts

74.6 dBA @ 10ft.

77.7 dBA @ 10ft.

80.5 dBA @ 10ft.

83.1 dBA @ 10ft.

85.6 dBA @ 10ft.

87.9 dBA @ 10ft.

70.7 Volts

73.7 dBA @ 10ft.

76.7 dBA @ 10ft.

79.6 dBA @ 10ft.

82.5 dBA @ 10ft.

85.4 dBA @ 10ft.

87.9 dBA @ 10ft.

RED Lens Strobe Current Ratings

Use with SSPKR24C Products

Candela

Regulated 24VDC

Max. Operating

Current (mA)

Regulated 24VFWR

Max. Operating

Current (mA)

15

128

220

30

128

220

75

225

306

95

235

402

115

341

444

The visual signal must be in the direct viewing area of the occupant in order to be seen.
Strobe light can not be seen when objects such as doors, furniture or walls block strobe light.

NOTICE:

VISUAL SIGNALS FOR THE HEARING IMPAIRED ARE ONLY ONE METHOD OF ALERTING THE HEARING IMPAIRED. VISUAL SIGNALS MAY NOT BE THE

PREFERRED METHOD FOR NOTIFYING ALL HEARING IMPAIRED INDIVIDUALS.

NOTICE:

THE STROBE LIGHT MUST BE SEEN BY THE SLEEPING PERSON. IF THE PERSON HAS HEAD TURNED OR OTHERWISE UNABLE TO BE ALERTED BY

VISUAL, THE STROBE WILL NOT BE EFFECTIVE.

Visual signal should NEVER be relied upon as the primary fire alert for the hearing impaired under these common sense conditions:

a. Sleeping face down on the bedding or pillow

b. Use of sleep medications of any kind

c. Use of alcoholic beverages or recreational drugs

d. Use of eye shades

e. If there are tendencies of deep sleep conditions

f. If a fire cuts power to AC circuits, the visual signal will not operate

g. If person is not within line of sight of visual signals

Under these and other similar common situations an alternate fire alert method such as a non-hearing impaired attendant is needed. The visual signal only

increases the chance of being alerted to the presence of fire. No system of this type can fully protect the hearing impaired in case of fire.

CAUTION

WHEN INSTALLING, ROUTE FIELD WIRING AWAY FROM SHARP

PROJECTIONS, CORNERS AND INTERNAL COMPONENTS.

Summary of Contents for SSPKCLP series

Page 1: ...atts for either 25v or 70 7v audio amplifiers The SSPK24CLP speaker strobe offers the option of a high intensity strobe which complies with ANSI UL 1971 The SSPKR24 speaker strobe offers the option of a high intensity strobe which complies with ANSI UL 1638 The frequency range of the speakers is 400 4000Hz All devices are suitable for line supervision Speaker includes DC blocking capacitor which a...

Page 2: ... with SSPKR24C Products Candela Regulated 24VDC Max Operating Current mA Regulated 24VFWR Max Operating Current mA 15 128 220 30 128 220 75 225 306 95 235 402 115 341 444 The visual signal must be in the direct viewing area of the occupant in order to be seen Strobe light can not be seen when objects such as doors furniture or walls block strobe light NOTICE VISUAL SIGNALS FOR THE HEARING IMPAIRED...

Page 3: ...E SUPERVISION OF CONNECTION PANEL VOLTAGE DEVICE MINIMUM VOLTAGE TOTAL CURRENT DRAW INCLUDES WIRE TO AND FROM APPLIANCE ASSUMES ALL APPLIANCES ARE AT THE END OF WIRE RUN WORST CASE CAUTION APPLIES ONLY TO REGULATED SUPPLIES MAX WIRE DISTANCE IN FEET X WIRE CONDUCTIVITY STROBE ONLY NOTICE ALL STROBES ARE DESIGNED TO FLASH AS SPECIFIED WITH CONTINUOUS APPLIED VOLTAGE THIS APPLIANCE IS NOT RECOMMENDE...

Page 4: ...ecome inoperable within the warranty period you must return the appliance to Gentex postage prepaid You must prove to the satisfaction of Gentex the date of purchase of your appliance Warranty service may only be performed by Gentex personnel at Gentex s facilities in Zeeland Michigan You must also pack the appliance to minimize the risk of it being damaged in transit You must also enclose a retur...

Reviews: