background image

SSPKCLP & SSPK24CLP SERIES

ANSI/UL 1480 AND/OR ANSI/UL 1971 COMPLIANT

SSPKR24 SERIES

ANSI/UL 1480 AND ANSI/UL 1638 COMPLIANT

UNIVERSAL MOUNT LOW PROFILE SPEAKER AND

CEILING MOUNT LOW PROFILE SPEAKER/STROBE

CAUTION:

Strobe light

must be installed within

16 feet of the pillow when

used in a sleeping area.

550-0490

Page 1

MODELS

SSPKCLP*................ LOW PROFILE CEILING OR WALL MOUNT SPEAKER WITHOUT STROBE

SSPK24CLP*............ LOW PROFILE CEILING MOUNT SPEAKER WITH SELECTABLE STROBE

SSPKR24C*..............LOW PROFILE CEILING MOUNT SPEAKER WITH SELECTABLE STROBE AND RED LENS

*

Includes one or more of the following designators, P (plain), R (red) or W (white).

I. INTRODUCTION

The Gentex SSPKCLP/SSPK24CLP/SSPKR24C is a high quality speaker and speaker/strobe ANSI/UL Listed for fire protective signaling systems. The high intensity strobe

utilizes a Xenon flash tube which generates a high-intensity light visible from all sides. The SSPK24CLP strobe is ANSI/UL Listed in compliance with ANSI/UL 1971, Signaling

Appliances for the Hearing Impaired. The SSPKR24 strobe is ANSI/UL Listed in compliance with ANSI/UL 1638, Visual Signaling Appliances - Private Mode Emergency and

General Signaling.

II. PRODUCT INFORMATION

The SSPKCLP/SSPK24CLP/SSPKR24 Series speaker and speaker/strobe offer a choice of field selectable power taps, 1/8, 1/4, 1/2, 1, 2 and 4 Watts for either 25v or 70.7v

audio amplifiers. The SSPK24CLP speaker/strobe offers the option of a high intensity strobe which complies with ANSI/UL 1971. The SSPKR24 speaker/strobe offers the

option of a high intensity strobe which complies with ANSI/UL 1638.The frequency range of the speakers is 400-4000Hz. All devices are suitable for line supervision.

Speaker includes DC blocking capacitor which allows for supervision voltage of either polarity.

III. LOCATION

This appliance is intended for use in Fire Alarm Systems and is to be installed in accordance with this installation manual, the recommendation of the local authorities having

jurisdiction, and other NFPA Standards that provide standards on notification appliances for protective signaling systems. The Gentex SSPKCLP/SSPK24CLP/SSPKR24

Series is intended for indoor installation only. This appliance is

not

listed for

outdoor

or drip proof applications.

**Effective Intensity Requirements for Sleeping Area

Visible Notification Appliance

Distance from Ceiling to Top of Lens

Intensity

greater than or equal to 24" (610mm)

110 Cd

less than 24" (610mm)

177 Cd

SSPK24CLP PRODUCT INFORMATION

Room Spacing for Ceiling-Mounted Visible Appliances per NFPA 72, 2010 Edition

Minimum Required Light Output (Effective Intensity, Cd; One Light)

Maximum Room Size

Maximum Ceiling Height

Meters

Feet

10 Foot Ceiling

20 Foot Ceiling

30 Foot Ceiling

6.10 x 6.10

20 x 20

15

30

55

9.14 x 9.14

30 x 30

30

45

75

13.4 x 13.4

44 x 44

75

75

NA

15.2 x 15.2

50 x 50

95

95

95

Summary of Contents for SSPKCLP series

Page 1: ...atts for either 25v or 70 7v audio amplifiers The SSPK24CLP speaker strobe offers the option of a high intensity strobe which complies with ANSI UL 1971 The SSPKR24 speaker strobe offers the option of a high intensity strobe which complies with ANSI UL 1638 The frequency range of the speakers is 400 4000Hz All devices are suitable for line supervision Speaker includes DC blocking capacitor which a...

Page 2: ... with SSPKR24C Products Candela Regulated 24VDC Max Operating Current mA Regulated 24VFWR Max Operating Current mA 15 128 220 30 128 220 75 225 306 95 235 402 115 341 444 The visual signal must be in the direct viewing area of the occupant in order to be seen Strobe light can not be seen when objects such as doors furniture or walls block strobe light NOTICE VISUAL SIGNALS FOR THE HEARING IMPAIRED...

Page 3: ...E SUPERVISION OF CONNECTION PANEL VOLTAGE DEVICE MINIMUM VOLTAGE TOTAL CURRENT DRAW INCLUDES WIRE TO AND FROM APPLIANCE ASSUMES ALL APPLIANCES ARE AT THE END OF WIRE RUN WORST CASE CAUTION APPLIES ONLY TO REGULATED SUPPLIES MAX WIRE DISTANCE IN FEET X WIRE CONDUCTIVITY STROBE ONLY NOTICE ALL STROBES ARE DESIGNED TO FLASH AS SPECIFIED WITH CONTINUOUS APPLIED VOLTAGE THIS APPLIANCE IS NOT RECOMMENDE...

Page 4: ...ecome inoperable within the warranty period you must return the appliance to Gentex postage prepaid You must prove to the satisfaction of Gentex the date of purchase of your appliance Warranty service may only be performed by Gentex personnel at Gentex s facilities in Zeeland Michigan You must also pack the appliance to minimize the risk of it being damaged in transit You must also enclose a retur...

Reviews: