Section 5 • Diagnostics
Part No. 227123
GRC
5 - 11
Type "FXXX" Faults
DTC
Number
Message on
GCON LCD
Problem
Description
Possible
Causes
Failure
Mode
F003
F003:SWITCHFAULT
DOWN LIMIT1:Bat+
Short circuit of the down limit
#1 switch at system start up.
• Short circuit of the down limit switch circuit.
• Down limit #1 switch short circuit.
• GCON ECM.
All functions
inhibited except
platform down.
F005
F005:SWITCHFAULT
POTHOLE1:Bat+
Short circuit of the pothole limit
#1 switch at system start up.
• Short circuit of the pothole switch circuit.
• Pothole limit #1 switch short circuit.
• GCON ECM.
All functions
inhibited except
platform down as
long as machine is
in the elevated
position.
If machine is in
stowed position, all
functionality is
resumed.
F007
F007:SWITCHFAULT
CHASSISTILT:Bat+
Short circuit of the chassis
digital tilt switch at system start
up.
• Short circuit of the chassis digital tilt switch
circuit.
• Chassis digital tilt switch short circuit.
• GCON ECM.
All functions
inhibited except
platform down as
long as machine is
in the elevated
position.
If machine is in
stowed position, all
functionality is
resumed.
F032
F032:SWITCHFAULT
OVLD:Bat+
Short circuit of the platform
overload switch with battery
positive.
• Short circuit of the platform overload
switch circuit to battery positive.
• GCON ECM.
All functions
inhibited except
platform down.
F033
F033:SWITCHFAULT
OVLD:OPEN/Bat-
Short circuit of the platform
overload switch circuit to
battery negative.
• Short circuit of the platform overload
switch circuit to battery negative.
• GCON ECM.
All functions
inhibited except
platform down.