background image

User Manual

Access Control Proximity Reader with Bluetooth

4

2.  Operation Notes

3.  Diagram / Dimensions

The GDG360BT includes one pair of NO/NC/COM output contacts, which can 

directly connect to a locking device or connect in parallel or series with access 

control systems.

Reed Switch

Door closed status: NO contact

Door open status: NC contact

Using Reset Jumper

Note:

1.  Make sure that the power input and SSR rating output (2A/12VDC) are correct.

2.  Make sure that the “+” and “-” wires are connected correctly.

3.  The door strike or relay must have a varistor or a diode across the door strike 

terminals to suppress the back EMF of the strike. Failure to do so will damage 

the relay contacts and electronic components, or even burn the controller.

86mm

86mm

20mm

Plug x2

Pan Head Phillips Screw x2

LED Indicator

Summary of Contents for GDG360BT

Page 1: ...User Manual Please read these instructions carefully before operating the unit and keep for further reference Access Control Proximity Reader with Bluetooth GDG360BT...

Page 2: ...Contents ii 1 Features Specification 3 2 Operation Notes 4 3 Diagram Dimensions 4 4 Wiring Diagram 5 5 Application 6 6 The App Guide 7...

Page 3: ...number ABA format decimal conversion Read Range 3 cm Inputs 1 RTE Request to exit 1 Door sensor DS Outputs 1 SSR Dry contacts N O N C COM 1 Tamper Alarm ALM Indicator Light 3 LED s Red Green Blue Mem...

Page 4: ...tus NO contact Door open status NC contact Using Reset Jumper Note 1 Make sure that the power input and SSR rating output 2A 12VDC are correct 2 Make sure that the and wires are connected correctly 3...

Page 5: ...uetooth 5 4 Wiring Diagram The door strike or SSR must have a diode or varistor across the door strike terminals to suppress the back EMF of the strike failure to do so will damage the SSR contacts an...

Page 6: ...cess Control Proximity Reader with Bluetooth 6 5 Application Note When connecting the GDG360BT to the access control system as shown above set the power supply timer to 0 second and adjust time settin...

Page 7: ...asscode 12345 right after you login as the Admin Go to the Settings page press Admin Passcode to Edit Admin Passcode Login Success Login Failure indications will be shown as following Login Success Yo...

Page 8: ...ings to enter the settings page 7 Auto Proximity Range Adjust Auto Proximity Range in the Settings page The range is between 0 to maximum 20 and it may have different results under different circumsta...

Page 9: ...re 1 Enter or edit 10 numbers from Admin s card fob Step 1 Tap Admin Card Fob The App will show Edit Admin Card Fob Step 2 Enter 10 numbers and press Confirm the App will show Admin s card fob number...

Page 10: ...Name User can only view the Device Name See Figure 8 below Auto Proximity Range User can adjust Auto proximity range between 0 to maximum 20 to access May have different results under different circum...

Page 11: ...Sales 44 0 1707 330541 Enquiries sales genieproducts co uk Website www genieproducts co uk...

Reviews: