6

Model 1137 Humidifier Installation Manual

Breathe Healthier! Residential Whole House Indoor Air Quality

FIG. 6B  WITH WITH CONSTANT POWER TO HUMIDIFIER

Use with mechanical humidistat only.  Mount a junction 

box and 115 volt grounded outlet.  Connect the on-off 

switch in series with the hot or black wire.  Install a field 

supplied 24 volt relay and attach to HUM and C on the 

furnace control board.  Install humidistat and connect one 

side to one yellow wire on humidifier.  Connect the other 

side of the humidistat to one end of switch side of the 

relay.  Connect the other switch side of the relay to the 

remaining yellow wire on humidifier.  

CAUTION:  Red humidifier leads are not used 

for this wiring method.  Do not touch red wires 

together.  Damage to the humidifier will result.

6. 

!

!

AC L

AC N

HUM

SNSR

L1

(HOT)

L2

115v.

60CY.

HUMIDIFIER CONTROL LEADS

(YELLOW WIRES)

FAN CONTROL

ON-OFF

SWITCH

SINGLE SPEED

BLOWER MOTOR

ACC

EAC

(HOT)

C

115v.

60CY.

ON-OFF

SWITCH

6A

6C

6B

GRD

HUMIDIFIER

120v. OUTLET

HUMIDIFIER

COMMON LEAD

120v. OUTLET

C

HI

LO

GA50 CURRENT

SENSING RELAY

MULTI

SPEED

BLOWER

MOTOR

6D

12500 AIR

PRESSURE

SWITCH

NO

C

L1

(HOT)

L2

115v.

60CY.

ON-OFF

SWITCH

GRD

HUMIDIFIER

120v. OUTLET

L1

(HOT)

L2

115v.

60CY.

ON-OFF

SWITCH

GRD

HUMIDIFIER

120v. OUTLET

GRD

FIG. 6A  WITH FURNACE CIRCUIT BOARD

On furnaces with output terminals ACC, or EAC 
check  output voltage to determine that termi-
nals are 115V.  Connect on-off switch in series 
with the hot wire.

WARNING:  CHECK WITH LOCAL AUTHORITIES FOR COMPLIANCE. 
WARNING:  ALL WIRING SHOULD COMPLY WITH LOCAL ELECTRICAL CODES.

FIG. 6C  AIR PRESSURE SWITCH WITH TWO 

SPEED BLOWER MOTOR

On furnaces with a two speed blower, the 

humidifier and a Model 12500 Air Pressure 

Switch may be wired from a continuous 115 

volt power source.  Install the on/off switch 

and Air Pressure Switch in series with the hot 

or black wire.  The Air Pressure Switch will 

detect furnace operation and supply power to 

the humidifier accordingly.

CIRCUIT DESCRIPTION

The humidifier is connected to the 120 volt AC circuit through a control relay. The secondary coil of an 

isolation transformer, a diode and resistor supply 24 volts DC for the control circuit which also includes the 

humidistat and relay coil. When the control circuit is completed by the humidistat, the relay closes, supplying 

120 volts to the fan motor and 24 volts to the solenoid valve.

FIG. 6D  CURRENT SENSING RELAY WITH TWO-SPEED 

BLOWER MOTOR

On furnaces with a two speed blower, the humidifier 

may be wired from a continuous 115 volt power source.  

Install the on/off switch in series with the hot or black 

wire.  Install the GA50 (GFI #7026) Current Sensing Relay 

in series with the humidistat circuit.  The Current Sensing 

Relay will detect furnace operation and supply power to 

the humidifier accordingly.

Installing / Wiring Your Control Cont.

6 B

(HOT)

C

115v.

60CY.

ON-OFF

SWITCH

HUMIDIFIER

120v. OUTLET

GRD

L1

YELLOW WIRES

FROM HUMIDIFIER

FURNACE

CONTROL BOARD

60CY.

24V.

C

HUM

FIELD SUPPLIED

RELAY 24V COIL, N.O.

HUMIDISTAT

C

NO

NC

6B

Summary of Contents for 1137 Series

Page 1: ...Commercial installation voids warranty Modification or alteration of product parts installation instructions or local safety codes voids warranty Read our full warranty policy at the end of this docum...

Page 2: ...ont 5 Installing Wiring The Control 5 6 Installation Cont 7 How the Humidifier Works 7 Maintenance 8 Parts Drawing 8 Trouble Shooting 9 FAQ s 10 Warranty Registration Keep a Copy For Your Records 11 L...

Page 3: ...Stable Automotive Grade Plastic Humidistat Models MHX3C Included Voltage 120V In Box Humidifier humidistat Installation Instructions Vapor Pad Parts Kit Water Tube Kit Humidistat Wire Drain Pan Power...

Page 4: ...dle counterclockwise to open saddle valve leave open for several seconds to flush dirt from pipe and tubing Steel Brass Hard Plastic Pipe 1 Shut off water supply and drain pipe 2 Turn handle clockwise...

Page 5: ...screws Low voltage wire may enter the humidistat under the foam seal 5 Connect wires to screw terminals on the control assembly as shown in wiring diagram Replace housing 6 MHX3C Mounting On The Retur...

Page 6: ...ff switch in series with the hot wire WARNING CHECK WITH LOCAL AUTHORITIES FOR COMPLIANCE WARNING ALL WIRING SHOULD COMPLY WITH LOCAL ELECTRICAL CODES FIG 6C AIR PRESSURE SWITCH WITH TWO SPEED BLOWER...

Page 7: ...id valve The solenoid valve and humidifier fan are controlled by a humidistat connected through an isolation relay The humidistat is designed for wall mounting in the living area or surface mounting o...

Page 8: ...ner screen 990 17 GFI 7005 from the orifice fitting Clean the mineral deposits from all parts If the orifice is clogged it may be opened by inserting a small needle Reinsert the filter into the orific...

Page 9: ...changed replaced your Vapor Pad at the proper intervals once per year to ensure the greatest production of moisture Check the setting of your humidistat to ensure it is set higher than current humidit...

Page 10: ...gile The coating is similar in composition to the minerals that accumulate on the pad If you subject the Vapor Pad to cleaning you usually remove much of the coating and the pad becomes ineffective Th...

Page 11: ...Labor involved in diagnostic calls or in removing repairing servicing or replacing parts is not covered under this Limited Warranty Shipping charges are not covered by this Limited Warranty Agreement...

Page 12: ...no event be liable for incidental or consequential damages This limited warranty gives you specific legal rights and you may also have other rights which vary from state to state Some states do not al...

Reviews: